7

Connecting Refrigerant Tubing Between the Indoor 
& Outdoor Unit

 CAUTION:

This system uses R-22 refrigerant which may 
contain mineral oil or POE oil. See page 9 for 
additional info. When servicing, cover or seal 
openings to minimize the exposure of the 
refrigerant system to air to prevent accumulation 
of moisture and other contaminants.

After outdoor and indoor unit placement has been 
determined, route refrigerant tubing between the 
equipment in accordance with sound installation practices.

•  When  connecting  refrigerant  linesets  together,  it  is 

recommended that dry nitrogen be flowing through 
the joints during brazing to prevent internal oxidation 
and scaling.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 
in the tubing. If precise forming of refrigerant lines is 
required, a copper tubing bender is recommended. 
Avoid sharp bends and contact of the refrigerant lines 
with metal surfaces.

•  Refrigerant tubing should be supported in a manner 

that the tubing will not vibrate or abrade during system 
operation.

•  Tubing should be kept clean of foreign debris during 

installation.

•  Every effort should be made by the installer to ensure 

that the field installed refrigerant containing components 
of the system have been installed in accordance with 
these instructions and sound installation practices to 
insure reliable system operation and longevity.

•  The  maximum  recommended  interconnecting 

refrigerant line lengths is 75 ft. and the vertical elevation 
difference between the indoor and outdoor sections 
should not exceed 20 ft.

ELECTRICAL WIRING

 WARNING:

To avoid risk of electrical shock, personal injury, 
or death, disconnect all electrical power to the unit 
before performing any maintenance or service. 
The unit may have more than one electrical 
supply.

Label all wires prior to disconnection when 
servicing the unit. Wiring errors can cause 
improper and dangerous operation.

•  All electrical connections must be in compliance with 

all applicable local codes and ordinances, and with 
the current revision of the National Electric Code 

 

(ANSI/NFPA 70).

•  For Canadian installations the electrical connections 

and grounding shall comply with the current Canadian 
Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

  Verify that the voltage, frequency, and phase of the 

supply source match the specifications on the unit 
rating plate. See Table 17 (page 24).

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 
Refer to the unit wiring label for proper voltage wiring.

  Verify factory wiring is in accordance with the unit 

wiring diagram or Figure 12 (page 23). Inspect for 
loose connections.

Line Voltage

•  A wiring diagram is located on the inside cover of the 

electrical box of the outdoor unit. The installer should 
become familiar with the wiring diagram before making 
any electrical connections to the outdoor unit.

• 

An electrical disconnect must be located within 
sight of and readily accessible to the unit
. This 
switch shall be capable of electrically de-energizing 
the outdoor unit.

•  Line  voltage  to  the  unit  should  be  supplied  from  a 

dedicated branch circuit containing the correct fuse 
or circuit breaker for the unit. Incoming field wiring 
and minimum size of electrical conductors and circuit 

COPPER WIRE SIZE — AWG

(1% Voltage Drop)

Supply Wire Length-Feet

Supply Circuit

Ampacity

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

Table 1. Copper Wire Size

•  To  maintain  the  unit's  warranty,  it  is  required  that  a 

filter drier be installed when the system is open to 
the atmosphere. This includes, but is not limited to, 
replacing the evaporator and/or condenser of a system. 
The filter drier must be installed in strict accordance 
with the manufacturer’s installation instructions.

•  Optional  equipment  such  as  liquid  line  solenoid 

valves, low ambient, etc., should be installed in 
strict accordance with the manufacturer’s installation 
instructions.

Содержание T5BD Series

Страница 1: ...eliminate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalco...

Страница 2: ...nits 18 Refrigerant Charging Tables Heating Mode 19 Table 10 T5BD 018K 1 5 Ton Units 19 Table 11 T5BD 024KA 2 Ton Units 19 Table 12 T5BD 030KA 2 5 Ton Units 20 Table 13 T5BD 036K 3 Ton Units 20 Table...

Страница 3: ...system mode to COOL or AUTO and change the fan mode to AUTO See Figure 1 2 Setthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to ma...

Страница 4: ...e aluminum fins Check and remove any obstructions such as twigs sticks etc TROUBLESHOOTING If the unit fails to operate check the following The thermostat is properly set See Cooling Operation for air...

Страница 5: ...erant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individu...

Страница 6: ...ility of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine the best location for mounting the outdoor unit See Figur...

Страница 7: ...be in compliance with all applicable local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and groun...

Страница 8: ...marked 208V Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC ANSI NFPA 70 applicable local codes and the instructions provided wit...

Страница 9: ...oom temperature and verify the outdoor unit and indoor blower energize 2 Verify blower wheel is spinning in direction indicated by arrow Feel the air being circulated by the indoor blower and verify t...

Страница 10: ...he required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged Heat Pump MAINT...

Страница 11: ...4 060K 43 30 3 4 30 3 4 D W H DO NOT OBSTRUCT TOP OF UNIT Allow adequate clearance for airflow reffrigerant Charging Charts Figure 5 Charging Chart for 1 5 Ton Units 125 150 175 200 225 250 275 300 32...

Страница 12: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units T5BD 030KA Charging Chart 150 175 200 225 250 275 300 325...

Страница 13: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units T5BD 042K Charging Chart 150 175 200 225 250 275 300 325...

Страница 14: ...g Add refrigerant when below curve Remove refrigerant when above curve T5BD 048K Charging Chart Figure 11 Charging Chart for 5 Ton Units 150 170 190 210 230 250 270 290 310 330 350 75 80 85 90 95 100...

Страница 15: ...Liq Press Dis Temp Liq Press Dis Temp 73 140 135 75 143 140 155 137 77 145 146 157 143 170 140 79 147 150 160 148 172 145 185 142 81 151 153 162 152 175 150 187 147 200 144 83 166 155 177 154 189 151...

Страница 16: ...ss Dis Temp Liq Press Dis Temp 71 148 144 73 150 149 164 147 75 152 155 166 152 179 149 77 155 158 168 157 181 154 195 152 79 159 161 171 161 183 159 197 156 210 154 81 174 164 187 163 199 161 212 158...

Страница 17: ...ss Dis Temp Liq Press Dis Temp 69 132 130 71 134 136 149 135 73 136 141 151 140 166 140 75 137 149 153 145 168 145 183 145 77 140 152 154 152 170 150 185 149 200 149 79 158 155 172 155 188 154 203 153...

Страница 18: ...7 84 222 178 235 176 248 174 260 171 86 238 180 252 178 265 176 88 255 182 268 180 90 271 185 92 Shaded boxes indicate flooded conditions Rated design values The suction pressure will vary from design...

Страница 19: ...ress Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 12 120 107 21 135 119 29 150 131 37 165 142 46 169 158 56 184 177 66...

Страница 20: ...ss Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 13 116 120 22 136 125 31 156 130 40 176 136 49 183 151 59 201 175 68 21...

Страница 21: ...ess Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 23 129 118 27 140 124 31 151 130 35 162 136 44 173 149 58 206 168 72 2...

Страница 22: ...159 139 31 182 143 39 206 147 48 230 158 58 257 175 68 283 193 16 142 133 24 165 137 32 187 141 40 209 145 49 237 155 59 264 171 69 290 187 17 149 131 25 171 135 33 192 139 41 213 143 50 244 152 60 27...

Страница 23: ...avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 volt a la terre Single Phase OPTIONAL HARD START KIT Start Capacitor 2 5 Sta...

Страница 24: ...8 1 4 1 4 1 4 1 4 1 4 Fan Blade Dia Blades 24 3 SCFM 2370 2370 3000 3000 3000 4000 4000 Compressor Data RLA 8 3 10 8 13 4 15 3 19 2 19 8 25 3 LRA 40 3 56 68 87 112 105 146 Refrigerant suction line Le...

Отзывы: