background image

8

Indoor Blower —

 Set the thermostat function 

switch to COOLING and the fan switch to ON. 
Verify that the indoor blower is operating and 
that airfl ow is not restricted. Set the fan switch 
back to AUTO.

Low-Pressure Switch — 

A low-pressure switch 

is factory-installed (see attached). This switch 
is located in the suction line internal to the out-
door unit. The switch is designed to protect the 
compressor from a loss of charge. Under normal 
conditions, the switch is closed. If the suction 
pressure falls below 5 psig, then the switch will 
open and de-energize the outdoor unit. The 
switch will close again once the suction pressure 
increases above 20 psig. Please note that the 
switch interrupts the thermostat inputs to the unit. 
Thus, when the switch opens and then closes, 
there will be a 5 minute short cycling delay before 
the outdoor unit will energize.

Cooling —

 Gradually lower the thermostat 

temperature setpoint below the actual room 
temperature and observe that the outdoor unit 
and indoor blower energize. Feel the air being 
circulated by the indoor blower and verify that 
it is cooler than ambient temperature. Listen 
for any unusual noises. If present, locate and 
determine the source of the noise and correct 
as necessary.

Short Cycle Protection —

 With the system 

operating in COOLING mode, note the setpoint 
temperature setting of the thermostat, and 
gradually raise the setpoint temperature until 
the outdoor unit and indoor blower de-energize. 
Immediately lower the setpoint temperature of 
the thermostat to its original setting and verify 
that the indoor blower is energized and that the 
outdoor unit remains de-energized. Verify that, 
after approximately 5 minutes, the outdoor unit 
energizes and that the temperature of the air 
supplied to the facility is cooler than ambient 
temperature.

Heating —

 Lower the thermostat setpoint 

temperature to the lowest obtainable setting and 
set the thermostat function switch to HEATING. 
The indoor blower and outdoor unit should stop 
running. After a minimum of fi ve minutes, increase 
the setpoint temperature of the thermostat to the 
maximum setting. Verify that the outdoor unit and 

indoor blower have energized. Feel the air being 
circulated by the indoor blower and verify that 
it is warmer than ambient temperature. Listen 
for any unusual noises. If present, locate and 
determine the source of the noise and correct 
as necessary.

NOTE:

 Other sources for heating (i.e.: electric 

furnace, fossil fuel furnace, air handler with 
electric heat options, etc.) that interface with 
the unit should be functionally checked to verify 
system operation and compatibility. Refer to the 
installation instructions for this equipment and 
perform a functional checkout in accordance 
with the manufacturer’s instructions.

Defrost Cycle Timer — 

The defrost cycle timer 

controls the accumulated run time interval of 
the hot gas defrost after the defrost sensor 
closes. It is located in the upper right corner of 
the defrost control board. Three interval settings 
are available: 30 minutes, 60 minutes, and 90 
minutes. Time setting selection is dependent on 
the climate where the unit is being installed. The 
default defrost cycle timer is set to 30 minutes. To 
adjust the cycle time, move the jumper to cover 
the two pins directly adjacent to the desired 
cycle time.

Example 1. Dry climate of Southern 
Arizona. A 90 minute setting is 
recommended.

Example 2. Moist climate of Seattle, 
Washington. A 30 minute setting is 
recommended.

High-Pressure Switch — 

A high-pressure 

switch is factory-installed and located in the liquid 
line internal to the outdoor unit. The switch is 
designed to protect the system when very high 
pressures occur during abnormal conditions. 
Under normal conditions, the switch is closed. 
If the liquid pressure rises above 425 psig, then 
the switch will open and de-energize the outdoor 
unit. The switch will close again once the liquid 
pressure decreases to 350 psig. Thus, when the 
switch opens and then closes, there will be a 5 
minute short cycling delay before the outdoor 
unit will energize.

DEFROST CONTROL BOARD OPERATION 
AND TESTING

1. Terminals “R”-”C” must have 24±V present 

between them in order for the time delay and 
defrost sequences to be operational.

Содержание T3BN

Страница 1: ...ation of heating and or air conditioning appliances Some local codes require licensed installation service personnel for this type of equipment Read all instructions carefully before starting the inst...

Страница 2: ...e heat in place of the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit may develop a coating of snow and ice on the heat t...

Страница 3: ...defrost cycle the outdoor fanwillstop andthecompressorwillcontinue to run and heat the outdoor coil causing the snow and ice to melt After the snow and ice have melted some steam may rise from the out...

Страница 4: ...his equipment follow all precautions in the literature on tags and on labels provided with theequipment Readandthoroughlyunderstand theinstructionsprovidedwiththeequipmentprior to performing the insta...

Страница 5: ...bMount Thesiteselectedforaslabmount installation requires a stable foundation and one not subject to erosion The slab should be level and anchored if necessary prior to placing the equipment on the sl...

Страница 6: ...ze based on N E C for 60 type copper conductors COPPER WIRE SIZE AWG 1 Voltage Drop Supply Wire Length Feet Supply Circuit 200 150 100 50 Ampacity 6 8 10 14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4...

Страница 7: ...hermostat R Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler O NOTE Jumper betweenW2 and E is required when no OD T Stat is used C W2 to be connected to Electric Heat Y W2...

Страница 8: ...inimumoffiveminutes increase the setpoint temperature of the thermostat to the maximumsetting Verifythattheoutdoorunitand indoor blower have energized Feel the air being circulated by the indoor blowe...

Страница 9: ...delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit Scroll compressors thathavenoiseissueswhilegoingintoorcoming out of defrost should use this...

Страница 10: ...7 5 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remo...

Страница 11: ...10 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remov...

Страница 12: ...Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp 19 134 135 20 140 135 21 146 136 22 152 136 32 162 157 51 199 198 61 248 179 20 141 133 21 146 133 22 151 134 23 156 134 33 169...

Страница 13: ...ons for control circuit and optional Relay Transformer Kits 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de...

Страница 14: ...8 2 18 Tube Dia 3 8 OD 3 8 OD 3 8 OD 3 8 OD Fan Motor Volts Phase Hz 280 230 3 60 460 3 60 280 230 3 60 460 3 60 380 420 3 50 380 420 3 50 Qty 1 1 1 1 Horsepower 3 4 3 4 3 4 3 4 Full Load Amps 3 3 1 7...

Страница 15: ...15...

Страница 16: ...AVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708538G 708538A 708538A replaces 7085380 Specifications and illustrations subject to change without notice and without incurring obligations Prin...

Отзывы: