9

2. Jumper the “T2”-”DFT” test pins. This will 

indicate to the board that the defrost T-stat 
is closed(if the compressor is running). 
Defrost T-stat is closed at 32° or below and 
is open at 68° or above.  But it’s state is 
unknown if the temperature is between 32°F 
and 68°F.  The defrost thermostat tells the 
board whether a defrost cycle needs to be 
started or terminated.  With the DFT closed 
the unit will run for 30/60/90 minutes in heat 
mode and then defrost the outdoor coil.  The 
defrost will turn off the outdoor fan, turn on the 
compressor and raise the coil temperature to 
68°F.  This will open the DFT and terminate 
the defrost.  If the DFT does not open the 
defrost will end after 10 minutes.

3.  Defrost board speed-up.  With compressor 

running in heat mode, next jump the “Test” 
pin to “C” on terminal strip. This will initiate 
a defrost test in 5, 10 or 15 seconds (This 
is determined by the 30, 60 or 90 minute 
defrost pin settings. The factory setting will 
be 30 minutes).  Note that this will bypass the 
compressor off delay when the unit goes into 
defrost test and if left in defrost test, the delay 
will be bypassed when the test is terminated 
by the processor.  If the jumper is removed 
before the test is over the processor will 
perform the remainder of a normal defrost.  
See step 2 above.

4.  Remove the jumpers.

Note: 

The delay/no-delay pin concerns 

compressor operation during defrosts. The default 
setting is delay. Reciprocating compressors 
should only use this setting in conjunction with 
an approved hard start kit. Scroll compressors 
that have noise issues while going into or coming 
out of defrost should use this 30 second delay to 
reduce the defrost noise. To switch from no-delay 
to delay remove the pin from the “no-delay” pin 
location and shift it to the “delay” pin location.

Speed up changes:

Manually initiating a defrost will cause the 

compressor to run continually when entering 
defrost.

Normal defrost operation:

To test normal defrost operation when the 
temperature is above 35°F, jumper “R” to 
“DFT” on the 624656 board and allow the unit 
to run for 30 minutes.  Defrost will continue 
until the “R” to “DFT” jumper is removed or 
for 10 minutes.  Remove the jumper.

The 5 minute time delay feature can be shortened 
1 time to 1 second by jumping the “Test” to “C” 
terminal.  Remove the jumper and repeat as 
desired.

Note: If jumper is left on the “Test” to “common” 
pins permanently, the defrost cycle will become 
inoperable. 

Defrost Test Procedure for 624656

1.  Jumper “T2” to “DFT” at the test terminals.
2.  With unit running in heat mode, short the 

“TEST” terminal to the common terminal near 
it.  This will speed up the board and cause 
it to enter defrost mode in 5/10/15 seconds 
depending on the defrost time selection. 

 

Compressor delay will not function during 
speed-up.

3.  This test will end in 5 seconds if the “TEST”-

common short is not removed.

4.  Remove both the short and the “T2” to “DFT” 

jumper to terminate the defrost cycle.  The 
30 second compressor delay should operate 
normally.

5.  Test is complete, reset thermostat to home 

owner preference.

Содержание T3BN

Страница 1: ...ation of heating and or air conditioning appliances Some local codes require licensed installation service personnel for this type of equipment Read all instructions carefully before starting the inst...

Страница 2: ...e heat in place of the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit may develop a coating of snow and ice on the heat t...

Страница 3: ...defrost cycle the outdoor fanwillstop andthecompressorwillcontinue to run and heat the outdoor coil causing the snow and ice to melt After the snow and ice have melted some steam may rise from the out...

Страница 4: ...his equipment follow all precautions in the literature on tags and on labels provided with theequipment Readandthoroughlyunderstand theinstructionsprovidedwiththeequipmentprior to performing the insta...

Страница 5: ...bMount Thesiteselectedforaslabmount installation requires a stable foundation and one not subject to erosion The slab should be level and anchored if necessary prior to placing the equipment on the sl...

Страница 6: ...ze based on N E C for 60 type copper conductors COPPER WIRE SIZE AWG 1 Voltage Drop Supply Wire Length Feet Supply Circuit 200 150 100 50 Ampacity 6 8 10 14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4...

Страница 7: ...hermostat R Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler O NOTE Jumper betweenW2 and E is required when no OD T Stat is used C W2 to be connected to Electric Heat Y W2...

Страница 8: ...inimumoffiveminutes increase the setpoint temperature of the thermostat to the maximumsetting Verifythattheoutdoorunitand indoor blower have energized Feel the air being circulated by the indoor blowe...

Страница 9: ...delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit Scroll compressors thathavenoiseissueswhilegoingintoorcoming out of defrost should use this...

Страница 10: ...7 5 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remo...

Страница 11: ...10 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remov...

Страница 12: ...Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp 19 134 135 20 140 135 21 146 136 22 152 136 32 162 157 51 199 198 61 248 179 20 141 133 21 146 133 22 151 134 23 156 134 33 169...

Страница 13: ...ons for control circuit and optional Relay Transformer Kits 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de...

Страница 14: ...8 2 18 Tube Dia 3 8 OD 3 8 OD 3 8 OD 3 8 OD Fan Motor Volts Phase Hz 280 230 3 60 460 3 60 280 230 3 60 460 3 60 380 420 3 50 380 420 3 50 Qty 1 1 1 1 Horsepower 3 4 3 4 3 4 3 4 Full Load Amps 3 3 1 7...

Страница 15: ...15...

Страница 16: ...AVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708538G 708538A 708538A replaces 7085380 Specifications and illustrations subject to change without notice and without incurring obligations Prin...

Отзывы: