background image

16

3.  Set the thermostat above room temperature and 

verify the sequence of operation. (See Operating 
Sequence on page 25.)

4. 

Verify that the compressor and outdoor fan motor 
are not energized.

5. 

After the unit  has run for approximately fi ve minutes, 
set the thermostat below room temperature and 
verify the shutdown sequence. (See Operating 
Sequence on page 25.)

Verifying and Adjusting Firing Rate —

 The fi ring rate 

must be verifi ed for each installation to prevent over-fi ring 
of the furnace.

CAUTION:

Do not re-drill the burner orifi ces. If the orifi ce 
size must be changed, use only new orifi ces.

IMPORTANT NOTE:  The fi ring rate must not exceed 
the rate shown on the unit data label. At altitudes 
above 2,000 ft. it must not exceed that on the data 
label less 4% for each 1,000 ft.

Follow the procedure below to determine the fi ring rate:

1. 

Shut off all other gas fi red appliances.

Start the unit in heating mode and allow it to run 
for at least three minutes.

3. 

Measure the time (in seconds) required for the gas 
meter to complete one revolution.

4. 

Convert the time per revolution to cubic feet of gas 
per hour using 

Table 8

.

5. 

Multiply the gas fl ow rate in cubic feet per hour by 
the heating value of the gas in Btu per cubic foot 
to obtain the fi ring rate in Btu per hour. Example:
a.  Time for one revolution of a gas meter with a       

one cubic foot dial = 40 seconds.

b. From 

Table 8

 read 90 cubic feet per hour of 

gas.

c.  Heating value of the gas (obtained from gas   

supplier) = 1040 Btu per cubic foot.

d.  Firing rate = 1040 x 90 = 93,600 Btuh.

6.  Adjustments to the fi ring rate can be made by 

adjusting the gas manifold pressure. See the High 
Altitude Application  section for additional information 
of fi ring rate at elevations above 2000 ft.

The manifold pressure must be set to the appropriate value 
for your installation.  Refer to either 

Table 5

 for natural 

gas or 

Table 6

 for LP/propane gas to verify the manifold 

pressure setting required for your particular installation. 
To adjust the manifold pressure, remove the regulator cap 
and turn the adjusting screw clockwise to increase pres-
sure or counterclockwise to reduce pressure. Replace the 
regulator cap after adjustments are complete. 

•  Verify that the thermostat is wired correctly.  The 

thermostat function switch should be set to “Off” and 
the thermostat fan switch should be set to “Auto.”

 WARNING:

If the unit is equipped with a crankcase heater, 
allow 24 hours prior to continuing the start up 
procedures to allow for heating of the refrigerant 
compressor crankcase.  Failure to comply may 
result in damage and could cause premature 
failure of the system.  This warning should be 
followed at initial start up and any time the power 
has been removed for 12 hours or longer.

 CAUTION:

This unit uses refrigerant R-410A. DO NOT 

under any circumstances use any other 
refrigerant besides R-410A in this unit. Use of 
another refrigerant will damage this unit.

START-UP PROCEDURE

Close all electrical disconnects to energize the system.

Air Circulation —

 Leave the thermostat system switch 

set to “Off” and set the thermostat fan switch to “On.”  The 
blower motor should run continuously. Check for air delivery 
at the register(s). Ensure that there are no obstructions at 
the registers or in the ductwork. Set thermostat fan switch 
to “Auto,” the blower will shut down in 60 seconds.

System Cooling

1.    Set the thermostat system switch to “Cool” and 

the thermostat fan switch to “Auto.”  Gradually 
lower the thermostat temperature switch below 
room temperature and observe that the blower, 
compressor and fan energize. Check that air cooler 
than room temperature is being discharged at the 
register. Listen for any unusual noises.  Locate the 
source and correct as needed.

2.      After allowing the unit to run for several minutes, set 

the temperature selector above room temperature, 
verify that:

 

a.  The fan and compressor cycle off with the  
 thermostat.

 

b.  The blower also stops after the 85 second  
 delay.

System Heating

1. 

Set the thermostat to the lowest setting.

2.  Follow the procedures given on the operating 

instruction label, in this installation instructions 
or attached inside the louvered control access 
panel.

Содержание R6GD-X36C072

Страница 1: ...agency or the gas supplier These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes require licensed installa...

Страница 2: ...eral 13 Line Voltage 14 Blower Speed 14 Electrical Data Table 15 Room Thermostat 15 SYSTEM CHECK 15 Pre Start Check List 15 START UP PROCEDURE 16 Air Circulation 16 System Cooling 16 System Heating 16...

Страница 3: ...he data label This furnace is NOT to be used for temporary heating of buildings or structures under construction Equipment Check All units have been securely packaged at the point of shipment After un...

Страница 4: ...Supply Entry Low Voltage Entry Gas Supply Entry 16 6 24 6 31 0 2 9 1 8 4 0 12 45 12 45 4 0 55 8 8 75 Horizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing C...

Страница 5: ...DIMENSIONS Continued Top View Denotes either C or X Model Number R6GD Unit Weight Shipping Weight Center of Gravity Height in inches A B C with base rails without base rails X36C072 470 480 26 5 26 5...

Страница 6: ...the unit such that exhaust from the vent termination is directed into window wells stairwells under decks or in alcoves or similarly recessed areas The vent termination must not be located above any...

Страница 7: ...nner as the first Again check to insure that the media is captured by the channels of the filter rack 3 Replace access cover by sliding the top edge of panel under the lip of the unit s Top Panel Secu...

Страница 8: ...llation on combustible flooring or class A B or C roofing material Can be C or X B A C D E Minimum Clearances to Combustible Material Model Number Heating Input Btuh Minimum Clearances Inches Blower C...

Страница 9: ...ors and liquids in the vicinity of the unit Figure 5 Ground Level Installation AIR SUPPLY FOR COMBUSTION AND VENTILATION Provisions must be made in the installation of this unit to provide an adequate...

Страница 10: ...zontal applications On roof curb installations the ducts must be attached to the curb duct supports not the unit It is recommended that the outlet duct be provided with a removable access panel This o...

Страница 11: ...5 66 99 980 70 75 925 74 95 875 820 785 T2 1410 49 17 1330 52 13 1250 55 47 1195 58 02 1140 60 82 1085 63 90 1030 67 31 975 71 11 T3 1525 45 46 1450 47 82 1370 50 61 1320 52 53 1270 54 59 1210 57 30 1...

Страница 12: ...sure Theplugshouldbereadilyaccessibleforservice use A drip leg should be installed in the pipe run to the unit Table 4 lists gas flow capacities for standard pipe sizes as a function of length in typi...

Страница 13: ...n Canada at altitudes between zero and 4500ft abovesealevel Followtheinstallationinstructions supplied with the kit for proper installation WARNING To avoid the risk of electrical shock personal injur...

Страница 14: ...box Do not use gas piping as an electrical ground CAUTION To avoid personal injury or property damage make certain that the motor leads cannot come into contact with any uninsulated metal components...

Страница 15: ...cted the fan only speed can be different than the heating or cooling speed If no jumper is present thecontroldefaultstothe 2 SPD modeofoperation A call for heating or cooling takes priority over fan o...

Страница 16: ...st the manifold pressure remove the regulator cap and turn the adjusting screw clockwise to increase pres sure or counterclockwise to reduce pressure Replace the regulator cap after adjustments are co...

Страница 17: ...eating and cooling speed selection is made by moving the leads on the blower motor terminal block The wiring diagram on the unit and in Figure 10 show the speed taps for adjusting motor speed Refer to...

Страница 18: ...opper conductors only 3 Not suitable on systems that exceed 150v to ground 4 If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a...

Страница 19: ...perate if the over temperature limit control opens UNIT MAINTENANCE WARNING To avoid risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any...

Страница 20: ...ompagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser d...

Страница 21: ...the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary CAUTION Label all wires prior to disconnection when servicing controls Wiring errors c...

Страница 22: ...ytheuseofaroundwirebrushattachedtoalength of high grade stainless steel cable such as drain cleanout cable Attach variable speed reversible drill to the other end of the spring cable Slowly rotate the...

Страница 23: ...ble until the limit circuit closes While the limit is open the red LED will pulse at a rate of 1 blink per unit time 3 Thefurnacecontrolchecksforcontinuityacrossthe pressure switch 24 VAC If the press...

Страница 24: ...n place 5 The 3 amp fuse is operational 6 The anti short cycle timer s 5 minute cycle has finished for single phase units If the unit does not operate in the heating mode be certain to check the follo...

Страница 25: ...mperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve R6GD X48 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 52...

Страница 26: ...220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below cur...

Страница 27: ...he homeowner _________________________________ Has the Literature Package been left with the homeowner _________________________________ Minimum Clearances per Table 1 ________________ Electrical Conn...

Страница 28: ...7088280 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 02 08 O Fallon MO INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WI...

Отзывы: