Table 6. Manifold Pressure (in WC) for LP/Propane Gas at Various Altitudes

Table 5. Manifold Pressure (in WC) for Natural Gas at Various Altitudes and Heating Values

See 

Figure 10

 or the unit wiring label for proper high 

and low voltage wiring. Make all electrical connections in 
accordance with all applicable codes and ordinances.

Use a separate branch electrical circuit for this unit. A 
means of electrical disconnect must be located within 
sight of and readily accessibility to the unit.

The unit is shipped from the factory wired for 240 volt 
transformer operation.  For 208 volt operation, remove 
the lead from the transformer terminal marked 240V and 
connect it to the terminal marked 208V. For maximum 
circuit ampacity and maximum over current protection, 
see the unit rating plate or 

Table 7.

Overcurrent protection must be provided at the branch 
circuit distribution panel and sized as shown in 

Table 7

 

or on the unit rating label and according to the National 
Electric Code and applicable local codes.

Provide power supply (or supplies) for the unit in 
accordance with the unit wiring diagram, and the unit rating 
plate. Connect the line-voltage leads to the corresponding 
terminals on the contactor inside the control compartment.  
Use only copper wire for the line voltage power supply 
to this unit. Use proper code agency listed conduit and 
a conduit connector for connecting the supply wires to 
the unit and for obtaining proper grounding.  Grounding 
may also be accomplished by using the grounding lug 
provided in the control box. Do not use gas piping as an 
electrical ground.

 CAUTION:

To avoid personal injury or property damage, 
make certain that the motor leads cannot 
come into contact with any uninsulated metal 
components of the unit.

Blower Speed —

 The blower speeds are preset at the 

factory. See

 Table  3

 for factory settings. For optimum 

system performance and comfort, it may be necessary 
to change the factory set speed. To change the blower 
speed:

1.    Disconnect all electrical power to the unit and remove 

the blower panel. 

2.  Locate the orange, red and blue wires terminated to 

the blower motor. The orange wire controls cooling 
operation while the red wire controls heating operation. 
The blue wire controls fan-only operation.

3.  Verify the required speed from the airfl ow data found 

in table 3. Place appropriate wire on the appropriate 
motor speed tap for the required airfl ow point.

For a Natural Gas Sea Level Heating Value of 800 to 899 Btu/ cu.ft.

Elevation (feet above sea level)

zero to

1999

2000 to

4999

5000 to

5999

6000 to

7999

8000 to

10000

Manifold Pressure Setting (in WC)

3.5

3.5

3.5

3.5

3

For a Natural Gas Sea Level Heating Value of 900 to 999 Btu/ cu.ft.

Elevation (feet above sea level)

zero to

1999

2000 to

4999

5000 to

5999

6000 to

7999

8000 to

10000

Manifold Pressure Setting (in WC)

3.5

3.5

3.5

3.2

2.8

For a Natural Gas Sea Level Heating Value of 1000 to 1100 Btu/ cu.ft.

Elevation (feet above sea level)

zero to

1999

2000 to

4999

5000 to

5999

6000 to

7999

8000 to

10000

Manifold Pressure Setting (in WC)

3.5

3.5

3

2.8

2.5

Elevation (feet above sea level)

zero to

1999

2000 to

4999

5000 to

5999

6000 to

7999

8000 to

10000

Manifold Pressure in (WC) Based on Sea Level 

LP Heating Value of 2,500 Btu/ft.3

10

8.5

10

9

8.5

Orifi ce Size

3.5

3.5

3.5

3.5

3

Содержание R6GD-X36C072

Страница 1: ...agency or the gas supplier These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes require licensed installa...

Страница 2: ...eral 13 Line Voltage 14 Blower Speed 14 Electrical Data Table 15 Room Thermostat 15 SYSTEM CHECK 15 Pre Start Check List 15 START UP PROCEDURE 16 Air Circulation 16 System Cooling 16 System Heating 16...

Страница 3: ...he data label This furnace is NOT to be used for temporary heating of buildings or structures under construction Equipment Check All units have been securely packaged at the point of shipment After un...

Страница 4: ...Supply Entry Low Voltage Entry Gas Supply Entry 16 6 24 6 31 0 2 9 1 8 4 0 12 45 12 45 4 0 55 8 8 75 Horizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing C...

Страница 5: ...DIMENSIONS Continued Top View Denotes either C or X Model Number R6GD Unit Weight Shipping Weight Center of Gravity Height in inches A B C with base rails without base rails X36C072 470 480 26 5 26 5...

Страница 6: ...the unit such that exhaust from the vent termination is directed into window wells stairwells under decks or in alcoves or similarly recessed areas The vent termination must not be located above any...

Страница 7: ...nner as the first Again check to insure that the media is captured by the channels of the filter rack 3 Replace access cover by sliding the top edge of panel under the lip of the unit s Top Panel Secu...

Страница 8: ...llation on combustible flooring or class A B or C roofing material Can be C or X B A C D E Minimum Clearances to Combustible Material Model Number Heating Input Btuh Minimum Clearances Inches Blower C...

Страница 9: ...ors and liquids in the vicinity of the unit Figure 5 Ground Level Installation AIR SUPPLY FOR COMBUSTION AND VENTILATION Provisions must be made in the installation of this unit to provide an adequate...

Страница 10: ...zontal applications On roof curb installations the ducts must be attached to the curb duct supports not the unit It is recommended that the outlet duct be provided with a removable access panel This o...

Страница 11: ...5 66 99 980 70 75 925 74 95 875 820 785 T2 1410 49 17 1330 52 13 1250 55 47 1195 58 02 1140 60 82 1085 63 90 1030 67 31 975 71 11 T3 1525 45 46 1450 47 82 1370 50 61 1320 52 53 1270 54 59 1210 57 30 1...

Страница 12: ...sure Theplugshouldbereadilyaccessibleforservice use A drip leg should be installed in the pipe run to the unit Table 4 lists gas flow capacities for standard pipe sizes as a function of length in typi...

Страница 13: ...n Canada at altitudes between zero and 4500ft abovesealevel Followtheinstallationinstructions supplied with the kit for proper installation WARNING To avoid the risk of electrical shock personal injur...

Страница 14: ...box Do not use gas piping as an electrical ground CAUTION To avoid personal injury or property damage make certain that the motor leads cannot come into contact with any uninsulated metal components...

Страница 15: ...cted the fan only speed can be different than the heating or cooling speed If no jumper is present thecontroldefaultstothe 2 SPD modeofoperation A call for heating or cooling takes priority over fan o...

Страница 16: ...st the manifold pressure remove the regulator cap and turn the adjusting screw clockwise to increase pres sure or counterclockwise to reduce pressure Replace the regulator cap after adjustments are co...

Страница 17: ...eating and cooling speed selection is made by moving the leads on the blower motor terminal block The wiring diagram on the unit and in Figure 10 show the speed taps for adjusting motor speed Refer to...

Страница 18: ...opper conductors only 3 Not suitable on systems that exceed 150v to ground 4 If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a...

Страница 19: ...perate if the over temperature limit control opens UNIT MAINTENANCE WARNING To avoid risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any...

Страница 20: ...ompagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser d...

Страница 21: ...the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary CAUTION Label all wires prior to disconnection when servicing controls Wiring errors c...

Страница 22: ...ytheuseofaroundwirebrushattachedtoalength of high grade stainless steel cable such as drain cleanout cable Attach variable speed reversible drill to the other end of the spring cable Slowly rotate the...

Страница 23: ...ble until the limit circuit closes While the limit is open the red LED will pulse at a rate of 1 blink per unit time 3 Thefurnacecontrolchecksforcontinuityacrossthe pressure switch 24 VAC If the press...

Страница 24: ...n place 5 The 3 amp fuse is operational 6 The anti short cycle timer s 5 minute cycle has finished for single phase units If the unit does not operate in the heating mode be certain to check the follo...

Страница 25: ...mperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve R6GD X48 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 52...

Страница 26: ...220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below cur...

Страница 27: ...he homeowner _________________________________ Has the Literature Package been left with the homeowner _________________________________ Minimum Clearances per Table 1 ________________ Electrical Conn...

Страница 28: ...7088280 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 02 08 O Fallon MO INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WI...

Отзывы:

Похожие инструкции для R6GD-X36C072