background image

12

Figure 7.  Typical Right Side Entry 

Gas Service Connection.

Ground Joint
Union

Dripleg

Shut-Off Valve

with 1/8 NPT

plugged tap

Burner
Assembly

Manifold

Some utilities

require Shut-Off

Valve to be

4 to 5 feet

above floor

Automatic Gas

Valve (with manual

shut-off)

2.  Lift the cap out of the unit.  The cap can be pushed 

up from the bottom by reaching through the fork 
slot. 

3.  Cover the horizontal duct opening with the cap.  The 

insulation will be on the indoor side.

4.  Fasten the cover with screws and seal to prevent 

air leakage.

GAS SUPPLY AND PIPING

This unit has right side gas entry.  A typical gas service 
hookup is shown in 

Figure 7.

 When making the gas 

connection, provide clearance between the gas supply line 
and the entry hole in the unit’s casing to avoid unwanted 
noise and/or damage to the unit.

All gas piping must be installed in compliance with local 
codes and utility regulations. Some local regulations 
require the installation of a manual main shut-off valve 
and ground joint union external to the unit.  The shut-off 
valve should be readily accessible for service and/or 
emergency use.  Consult the local utility or gas supplier 
for additional requirements regarding placement of the 
manual main gas shut-off. In the absence of local codes 
the gas line installation must comply with the latest edition 
of the National Fuel Gas Code ANSI Z223.1 or CAN/CGA 
B149 Installation Codes.

CAUTION:

Do not use matches, lighters, candles or other 
sources of open fl ame to check for gas leaks.

A 1/8 inch NPT plugged tap must be installed in the gas 
line immediately upstream of the gas supply connection 
to the furnace for use when measuring the gas supply 
pressure. The plug should be readily accessible for service 
use. A drip leg should be installed in the pipe run to the 
unit. 

Table 4

 lists gas fl ow capacities for standard pipe 

sizes as a function of length in typical applications based 
on nominal pressure drop in the line.

IMPORTANT NOTES:

1.   Gas piping must not be run in or through air ducts, 

chimneys, gas vents, elevator shafts, etc.

2.   Compounds used on threaded joints of gas piping 

must be resistant to the actions of liquefi ed petroleum 
gases.

3.  The main manual gas valve and main power 

disconnect to the furnace must be properly labeled 
by the installer in case emergency shutdown is 
required.

Leak Check —

 After the gas piping to the unit is complete, 

all connections must be tested for gas leaks. To check for 
leaks in gas piping systems, use only a soap and water 
solution or other approved method.

IMPORTANT NOTE: When pressure testing the gas 
supply lines at pressures greater than 1/2 psig (14 
inches WC), the unit must be disconnected from the 
gas supply piping system to prevent damage to the 
gas control valve.

If the test pressure is less than or equal to 1/2 psig 
(14 inches WC), the unit must be isolated from the gas 
supply line by closing the manual shut-off valve.

 WARNING:

This unit was equipped at the factory for use with 
natural gas only.  A special kit, supplied by the 
manufacturer, is required to convert the unit to 
operate on LP/propane  gas.  Failure to use the 
proper conversion kit can cause fi re, explosion, 
property damage, carbon monoxide poisoning, 
personal injury, or death.

GAS AND HIGH ALTITUDE CONVERSIONS

Conversion: conversion of this unit must be performed by 
qualifi ed service personnel, using only approved parts.

High Altitude Application

High altitude application with this furnace can be fi eld 
performed by a simple adjustment of manifold pressure 
and if necessary, a change of the orifi ces. The changes 

Содержание R6GD-X36C072

Страница 1: ...agency or the gas supplier These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes require licensed installa...

Страница 2: ...eral 13 Line Voltage 14 Blower Speed 14 Electrical Data Table 15 Room Thermostat 15 SYSTEM CHECK 15 Pre Start Check List 15 START UP PROCEDURE 16 Air Circulation 16 System Cooling 16 System Heating 16...

Страница 3: ...he data label This furnace is NOT to be used for temporary heating of buildings or structures under construction Equipment Check All units have been securely packaged at the point of shipment After un...

Страница 4: ...Supply Entry Low Voltage Entry Gas Supply Entry 16 6 24 6 31 0 2 9 1 8 4 0 12 45 12 45 4 0 55 8 8 75 Horizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing C...

Страница 5: ...DIMENSIONS Continued Top View Denotes either C or X Model Number R6GD Unit Weight Shipping Weight Center of Gravity Height in inches A B C with base rails without base rails X36C072 470 480 26 5 26 5...

Страница 6: ...the unit such that exhaust from the vent termination is directed into window wells stairwells under decks or in alcoves or similarly recessed areas The vent termination must not be located above any...

Страница 7: ...nner as the first Again check to insure that the media is captured by the channels of the filter rack 3 Replace access cover by sliding the top edge of panel under the lip of the unit s Top Panel Secu...

Страница 8: ...llation on combustible flooring or class A B or C roofing material Can be C or X B A C D E Minimum Clearances to Combustible Material Model Number Heating Input Btuh Minimum Clearances Inches Blower C...

Страница 9: ...ors and liquids in the vicinity of the unit Figure 5 Ground Level Installation AIR SUPPLY FOR COMBUSTION AND VENTILATION Provisions must be made in the installation of this unit to provide an adequate...

Страница 10: ...zontal applications On roof curb installations the ducts must be attached to the curb duct supports not the unit It is recommended that the outlet duct be provided with a removable access panel This o...

Страница 11: ...5 66 99 980 70 75 925 74 95 875 820 785 T2 1410 49 17 1330 52 13 1250 55 47 1195 58 02 1140 60 82 1085 63 90 1030 67 31 975 71 11 T3 1525 45 46 1450 47 82 1370 50 61 1320 52 53 1270 54 59 1210 57 30 1...

Страница 12: ...sure Theplugshouldbereadilyaccessibleforservice use A drip leg should be installed in the pipe run to the unit Table 4 lists gas flow capacities for standard pipe sizes as a function of length in typi...

Страница 13: ...n Canada at altitudes between zero and 4500ft abovesealevel Followtheinstallationinstructions supplied with the kit for proper installation WARNING To avoid the risk of electrical shock personal injur...

Страница 14: ...box Do not use gas piping as an electrical ground CAUTION To avoid personal injury or property damage make certain that the motor leads cannot come into contact with any uninsulated metal components...

Страница 15: ...cted the fan only speed can be different than the heating or cooling speed If no jumper is present thecontroldefaultstothe 2 SPD modeofoperation A call for heating or cooling takes priority over fan o...

Страница 16: ...st the manifold pressure remove the regulator cap and turn the adjusting screw clockwise to increase pres sure or counterclockwise to reduce pressure Replace the regulator cap after adjustments are co...

Страница 17: ...eating and cooling speed selection is made by moving the leads on the blower motor terminal block The wiring diagram on the unit and in Figure 10 show the speed taps for adjusting motor speed Refer to...

Страница 18: ...opper conductors only 3 Not suitable on systems that exceed 150v to ground 4 If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a...

Страница 19: ...perate if the over temperature limit control opens UNIT MAINTENANCE WARNING To avoid risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any...

Страница 20: ...ompagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser d...

Страница 21: ...the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary CAUTION Label all wires prior to disconnection when servicing controls Wiring errors c...

Страница 22: ...ytheuseofaroundwirebrushattachedtoalength of high grade stainless steel cable such as drain cleanout cable Attach variable speed reversible drill to the other end of the spring cable Slowly rotate the...

Страница 23: ...ble until the limit circuit closes While the limit is open the red LED will pulse at a rate of 1 blink per unit time 3 Thefurnacecontrolchecksforcontinuityacrossthe pressure switch 24 VAC If the press...

Страница 24: ...n place 5 The 3 amp fuse is operational 6 The anti short cycle timer s 5 minute cycle has finished for single phase units If the unit does not operate in the heating mode be certain to check the follo...

Страница 25: ...mperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve R6GD X48 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 52...

Страница 26: ...220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below cur...

Страница 27: ...he homeowner _________________________________ Has the Literature Package been left with the homeowner _________________________________ Minimum Clearances per Table 1 ________________ Electrical Conn...

Страница 28: ...7088280 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 02 08 O Fallon MO INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WI...

Отзывы:

Похожие инструкции для R6GD-X36C072