APPENDIX A – O5LD-091A-12-R
O5LD-091A-12-R furnace may be used with the following oil burners.
Please note: The Beckett AF oil burner is for applications using indoor air for combustion only.
Table A-1 Beckett AF Oil Burner Set-Up
Beckett AF Series Oil Burners
(For use with chimney vented units only)
Furnace Model
Output
BTU/Hr
Burner
Model
Nozzle
Pump
Pressure
Flow
Rate
Head
1
Static
Plate
O5LD-070A-12-R
2
59,000 AF76BNHS
0.50 /
80°A
100 psig
0.50
usgph
F3 3-
⅜
in.
O5LD-091A-12-R
76,000 AF76BNHS
0.65 /
80°A
100 psig
0.65
usgph
F3 3-
⅜
in.
O5LD-105A-12-R 85,000 AF76BNHS
0.75 /
80°A
100 psig
0.75
usgph
F3 3-
⅜
in.
1
Head is shielded by ceramic insulator.
2
Low Firing Rate Baffle required when using a 0.50-gallon
nozzle. Bold models indicate the factory equipped firing rate.
A.1 OIL BURNER AIR ADJUSTMENT
For complete details, consult the oil burner instruction
manual provided in the furnace documents envelope.
Beckett AF Burner
Adjust the air shutter by loosening the locking screws
and moving the air shutter, and if necessary, the bulk
air band.
A.2 BURNER ELECTRODES
Adjustment of the electrode tips with respect to each
other, the nozzle, and to the rest of the burner is very
important to ensure smooth start-ups and to permit
efficient combustion.
Beckett AF Burner
Electrode gap: 5/32 inch.
Distance above horizontal centerline: 5/16 inch. Older
instruction sheets specify 7/16 inch. The current
specification is 5/16 inch.
Distance ahead of nozzle: 1/16 inch.
“Z” dimension, the distance from the front of the end
cone (head) to the face of the nozzle should be 1-1/8
inches. If a ceramic head is used, the distance from
the end cone to the nozzle face is increased to 1-3/8
inches.
A.3 START UP
The furnace should be operated for a minimum of 10
minutes to reach steady state conditions before fine
tuning combustion. The warm up time is ideal for
testing the oil pump pressure.
Drill a 1/4-inch test port in the venting between the
furnace flue outlet and draft regulator (barometric
damper). Insert a stack thermometer and note the flue
gas temperature. The flue gases should be within a
range of 350°F to 450°F. If the flue gases are below
the range, it may be necessary to slow down the
blower fan. If the flue gases are above the range, the
blower fan may require speeding up. Stack
temperature varies directly with the system
temperature rise. System temperature rise is the
difference between the furnace outlet temperature and
furnace inlet temperature as measured in the vicinity of
the connection between the plenum take-offs and the
trunk ducts. Temperature rise value is listed on the
system rating plate.
Perform a smoke spot test. The smoke spot should not
exceed No. 1 on the Bacharach Scale.
10
Содержание O5LD-091A-12-R
Страница 14: ...Chimney Vent Burner Wiring Diagram O5LD 091A 12 R APPENDIX B WIRING DIAGRAMS 14...
Страница 17: ...17 FIGURE 2 UNITED TECHNOLOGIES 1158 120 FAN TIMER BOARD O5LD 019A 12 R...
Страница 25: ...25...
Страница 26: ...26...
Страница 27: ...NOTES 27...
Страница 28: ...28 NOTES Nordyne Inc 8000 Phoenix Parkway O Fallon Missouri 63368...