APPENDIX A – O5LD-091A-12-R  

O5LD-091A-12-R furnace may be used with the following oil burners. 
Please note:  The Beckett AF oil burner is for applications using indoor air for combustion only. 

 

Table A-1 Beckett AF Oil Burner Set-Up

 

Beckett AF Series Oil Burners 

(For use with chimney vented units only) 

Furnace Model 

Output 

BTU/Hr 

Burner 

Model 

Nozzle 

Pump 

Pressure 

Flow 

Rate 

Head 

1

 

Static 

Plate 

  

O5LD-070A-12-R

2

 59,000 AF76BNHS

0.50 / 

80°A 

100 psig 

0.50 

usgph 

F3 3- 

 in.

O5LD-091A-12-R 

76,000 AF76BNHS

0.65 / 

80°A 

100 psig 

0.65 

usgph 

F3 3- 

 in.

O5LD-105A-12-R 85,000 AF76BNHS

0.75 / 

80°A 

100 psig 

0.75 

usgph 

F3 3- 

 in.

Head is shielded by ceramic insulator.   

2

 Low Firing Rate Baffle required when using a 0.50-gallon 

nozzle.  Bold models indicate the factory equipped firing rate. 
  

A.1 OIL BURNER AIR ADJUSTMENT 

For complete details, consult the oil burner instruction 
manual provided in the furnace documents envelope. 

Beckett AF Burner 

Adjust the air shutter by loosening the locking screws 
and moving the air shutter, and if necessary, the bulk 
air band. 

 

A.2 BURNER ELECTRODES 

Adjustment of the electrode tips with respect to each 
other, the nozzle, and to the rest of the burner is very 
important to ensure smooth start-ups and to permit 
efficient combustion. 

Beckett AF Burner

 

Electrode gap: 5/32 inch. 

Distance above horizontal centerline: 5/16 inch. Older 
instruction sheets specify 7/16 inch. The current 
specification is 5/16 inch. 

Distance ahead of nozzle: 1/16 inch. 

“Z” dimension, the distance from the front of the end 
cone (head) to the face of the nozzle should be 1-1/8 
inches. If a ceramic head is used, the distance from 
the end cone to the nozzle face is increased to 1-3/8 
inches. 

 

 

A.3 START UP 

The furnace should be operated for a minimum of 10 
minutes to reach steady state conditions before fine 
tuning combustion. The warm up time is ideal for 
testing the oil pump pressure. 

Drill a 1/4-inch test port in the venting between the 
furnace flue outlet and draft regulator (barometric 
damper). Insert a stack thermometer and note the flue 
gas temperature. The flue gases should be within a 
range of 350°F to 450°F. If the flue gases are below 
the range, it may be necessary to slow down the 
blower fan. If the flue gases are above the range, the 
blower fan may require speeding up. Stack 
temperature varies directly with the system 
temperature rise. System temperature rise is the 
difference between the furnace outlet temperature and 
furnace inlet temperature as measured in the vicinity of 
the connection between the plenum take-offs and the 
trunk ducts. Temperature rise value is listed on the 
system rating plate. 

Perform a smoke spot test. The smoke spot should not 
exceed No. 1 on the Bacharach Scale. 

 

 

 

 

 

 

10

Содержание O5LD-091A-12-R

Страница 1: ...flammable liquids or vapors in the vicinity of this or any other appliance ALL INSTALLATIONS MUST MEET ALL LOCAL PROVINCIAL STATE AND FEDERAL CODES WHICH MAY DIFFER FROM THIS MANUAL NORDYNE INC Read...

Страница 2: ...NNECTIONS 5 10 HUMIDIFIER 6 11 PIPING INSTALLATION 6 12 OIL FILTER 6 13 OIL BURNER NOZZLES 6 14 OIL BURNER ADJUSTMENT 6 15 BURNER ELECTRODES 6 16 BURNER PRIMARY SAFETY CONTROL 7 17 COMBUSTION CHAMBER...

Страница 3: ...n doubt please consult your local authorities Location Clearance to Combustibles Top 1 Bottom 0 S A Plenum 1 Rear 6 Sides 1 Front 1 Flue Pipe 4 in measured horizontally or below flue pipe 8 in measure...

Страница 4: ...utlet should be at least two feet above the highest point of a peaked roof All unused chimney openings should be closed Chimneys must conform to local provincial or state codes or in the absence of lo...

Страница 5: ...f 30 On Off 60 Off On 90 On On 120 Off Off 2 On Off 3 Off On 4 On On 6 9 ELECTRICAL CONNECTIONS The furnace is listed by the Canadian Standards Association under the NRTL North American Standard It is...

Страница 6: ...ms should include an oil filter between the fuel oil storage tank and the oil burner When using an oil burner nozzle smaller than 0 65 U S Gallons Per Hour install an additional 7 to 10 micron filter...

Страница 7: ...duct systems were not designed to provide static pressure They typically feature special reducing fittings at each branch run and lack block ends on the trunk ducts This system may require modificatio...

Страница 8: ...O THE FURNACE and remove the burner Using a stiff brush with a wire handle brush off scale and soot from inside the drum and flue pipe To clean the radiator remove the clean out caps screws and remove...

Страница 9: ...T TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOUR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT NEVER BURN GARBAGE OR PAPER IN THE FURNACE AND NEVER LEAVE PAPER OR...

Страница 10: ...ckett AF Burner Electrode gap 5 32 inch Distance above horizontal centerline 5 16 inch Older instruction sheets specify 7 16 inch The current specification is 5 16 inch Distance ahead of nozzle 1 16 i...

Страница 11: ...mounting plate as shown in Figure 2 The draft should be adjusted to 0 02 inches w c In the United States the Beckett AF Burner may be equipped with Beckett s Inlet Air Shut Off to increase efficiency...

Страница 12: ...DD Med Low 1 2 HP Med Low 1 2 HP 3 1 2 HP 700 1600 O5LD 105A 12 R 10 10T DD Med Low 1 2 HP Med High 1 2 HP 3 1 2 HP 700 1600 Table A 6 Direct Drive Blower Characteristics CFM External Static Pressure...

Страница 13: ...ENUM OPENINGS FLUE WIDTH A LENGTH B HEIGHT C SUPPLY D X E RETURN F X G DIAM HEIGHT H FILTER PERM SHIP WEIGHT LBS O5LD 091A 12 R 22 51 32 20 x 19 20 x 18 5 26 25 20 x 20 x 1 240 Table A 9 General Dimen...

Страница 14: ...Chimney Vent Burner Wiring Diagram O5LD 091A 12 R APPENDIX B WIRING DIAGRAMS 14...

Страница 15: ...The fan adjustments can be made by moving the dipswitch settings on the timer control board for fan off delay To check the operation of the limit switch shut off power to the furnace Temporarily remov...

Страница 16: ...and Y terminals are de energized Cooling contactor is de energized immediately Circulator fan turns off immediately Thermostat begins call for fan G terminal is energized Circulator fan is energized i...

Страница 17: ...17 FIGURE 2 UNITED TECHNOLOGIES 1158 120 FAN TIMER BOARD O5LD 019A 12 R...

Страница 18: ...and burner motor reset button if equipped Check the limit switches to ensure that the switch contacts are closed Check the electrode gap and position Check the contacts between the oil primary contro...

Страница 19: ...ive Check fuel oil lines Replace any compression fittings found with high quality flared fittings Check for any signs of oil leaks Any oil leak is a potential source of air or contaminants Furnace wil...

Страница 20: ...ombustion air band and draft regulator to gain the highest practical CO2 or lowest practical O2 content in the flue gases See Burner Set Up Too much smoke Heat exchanger partially clogged Check for so...

Страница 21: ...uct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary FINAL CHECK OUT 3 Where the oil shut off valve from the oil storage tank is located ENSURE THAT ALL SAFE...

Страница 22: ...al No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No If different from Installation Contractor Service Tech Telephone No After Hours No Fuel Supplier Fuel Oil Suppli...

Страница 23: ...le 30152 14 Clean out Gasket Retainer 2 per unit 29161 Clean out Gasket 2 per unit 29163 15 Oil Burner Mounting Plate Assembly 109007674 Inspection Door Gasket 29871 16 Pouch Gasket 2080175 17 Flue Pi...

Страница 24: ...Firing Rate Baffle Nozzle 0 50 80 A 29880 25521101 29389 29 Blower Assembly Complete Direct Drive hp 4 Speed 29668 Blower Housing and Wheel 100 10T DD 30626 Blower Motor hp 4 Speed 102000131 Motor Mou...

Страница 25: ...25...

Страница 26: ...26...

Страница 27: ...NOTES 27...

Страница 28: ...28 NOTES Nordyne Inc 8000 Phoenix Parkway O Fallon Missouri 63368...

Отзывы: