Nordyne M3 RL-060 Скачать руководство пользователя страница 28

28

TIME FOR

TIME FOR

ONE REVOLUTION

ONE REVOLUTION

(SECONDS)

1

5

10

(SECONDS)

1

5

10

24

150

750

1500

80

45

225

450

26

138

692

1385

82

44

220

439

28

129

643

1286

84

43

214

429

30

120

600

1200

86

42

209

419

32

113

563

1125

88

41

205

409

34

106

529

1059

90

40

200

400

36

100

500

1000

92

39

196

391

38

95

474

947

94

38

191

383

40

90

450

900

96

38

188

375

42

86

429

857

98

37

184

367

44

82

409

818

100

36

180

360

46

78

391

783

102

35

176

353

48

75

375

750

104

35

173

346

50

72

360

720

106

34

170

340

52

69

346

692

108

33

167

333

54

67

333

667

110

33

164

327

56

64

321

643

112

32

161

321

58

62

310

621

114

32

158

316

60

60

300

600

116

31

155

310

62

58

290

581

118

31

153

305

64

56

281

563

120

30

150

300

GAS FLOW RATE (CUBIC FEET PER HOUR)

CUBIC FEET PER REVOLUTION OF 

METER

CUBIC FEET PER REVOLUTION OF 

METER

Table 11.  Gas Flow Rate

after the gas valve is closed. This timing can be
changed using the BLOWER OFF timing switch
opposite the terminal block on the control board
(See Figure 27).

Verifying Burner Operation
To verify operation of the burners, remove front
door and ensure that the  door switch is in the “on”
position (see Figure 29). Set the thermostat above
room temperature and observe the ignition se-
quence. The flame can be observed  through the
small clear window on the burner box. The burner
flame should carry over between all burners. The
flames should be blue, without yellow tips. Flames
should extend from each burner without lifting,
curling, or floating. After verifying ignition, set the
thermostat below room temperature and verify
that the burner flame extinguishes completely.
Replace the front door.

Verifying Operation of the Supply Air
Limit Switch
To verify operation of the supply air limit switch,
make sure that the blower door is in place and
that there is power to the furnace.  Completely
block the return airflow to the furnace by install-
ing a close-off plate in place of or upstream of
the filter(s). Set the thermostat above room

temperature and verify that the Sequence of
Operation is as described in these instructions.
The supply air  limit switch should function to
turn off the gas valve within approximately five
minutes. The circulating air and combustion
blowers should continue to run when the supply
air limit switch opens. Remove the close-off
plate immediately after the supply air  limit switch
opens. If the furnace operates for more than five
minutes with no return air, set the thermostat
below room temperature, shut off the power to
the furnace, and replace the supply air limit
switch.

DESCRIPTION OF COMPONENTS

Figure 29 shows the location of each of the
functional components described below. If any
component of the furnace must be replaced,
use only factory authorized replacement parts.
Contact your distributor for the approved re-
placement parts.

Flame Sensor – The flame sensor acts to
prove that flame has carried over from the
ignitor to the opposite end burner. If no flame is
sensed, the furnace will be shut down automati-
cally.

Содержание M3 RL-060

Страница 1: ...sup plier Ne pas entreposer ni utiliser de l essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ni de tout autre appareil QUE FAIRE S IL Y A UNE ODEUR DE GAZ Ne pa...

Страница 2: ...2...

Страница 3: ...nance 30 System Operation Information 30 Sequence of Operation 30 Furnace Fails to Operate 31 Location of Major Components 32 Wiring Diagram 33 Installation Performance Checklist 35 General 4 UnitDime...

Страница 4: ...2 Shipping Weight Table 3 Furnace Specifications Airflow Data GENERAL Note Data is for Operation with Filter Factory Wired Cooling Tap Factory Wired Heating Tap Furnace Specifications Airflow Data Fur...

Страница 5: ...s with an open flame Use a commercially available soap solution made specifically for the detection of leak to check all connections 6 Always install furnace to operate within the furnace s intended t...

Страница 6: ...ring problems in the electrical circuit supplying the furnace 4 Resetting circuit breakers blown fuses or other switches 5 Correcting problems due to improper gas supply pressure to the furnace 6 Prov...

Страница 7: ...OVE ALL MODELS Inches Inches Front 1 1 Back 0 0 Sides 0 0 Vent 0 0 Top 6 6 Duct Plenum w Coil Box 0 0 w o Coil Box 1 4 1 4 within 3 feet bustible material other than wood flooring The furnace may be i...

Страница 8: ...ast 400 sq in of free airflow area d The cross sectional area of the return duct system leading into the closet when located Figure 2 Non Platinum Supply Duct System A Single trunk duct B Dual trunk d...

Страница 9: ...e where it can be easily read when the closet door is open The marking shall read CAUTION HAZARD OF ASPHYXIATION Do not cover or restrict return air opening l Air conditioning systems may require more...

Страница 10: ...construction use the 14 round plenum p n 903896 NON PLATINUM SERIES a Determine depth of floor cavity from surface of floor to top of supply air duct See Figure 3 b Select appropriate model from Tabl...

Страница 11: ...duct connector at rear of the floor opening See Figure 9 INSTALLING PLATINUM SERIES 14 ROUND DUCT CONNECTOR a Place duct connector through the floor open ing See Figure 9 b Secure duct connector to fl...

Страница 12: ...oor open ing with bottom tabs extending through the duct opening See Figure 9 b Secure duct connector to floor c Bendbottomtabsunderanduptightlyagainst the supply air duct See Figure 10 NOTE The duct...

Страница 13: ...te tabs d Secure front with one 1 fastener at each corner See Figure 13 or 14 NOTE Additional fasteners may be used at rear sides or through door frame as desired to secure furnace to closet or alcove...

Страница 14: ...ckage or re striction leakage corrosion and other deficiencies which could cause an unsafe condition 3 So far as is practical close all building doors and windows and all doors between the space in wh...

Страница 15: ...30 cm B Clearance to window or door that may be opened 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3 kW and 100 00 Btuh 30 kW 36 inches 91 cm for applianc...

Страница 16: ...sive atmosphere The quality of outdoor air must also be considered Be sure that the combustion air intake is not located near a source of solvent fumes or other chemicals which can cause corrosion of...

Страница 17: ...t should be as close to furnace as possible Combustion Air Intake Pipe 5 Combustion Air Intake Pipe Vent Support System on Vertical Rise Below Joints 5 Avoid areas where condensate drainage may cause...

Страница 18: ...Extend the vent pipe through the wall approximately 1 and seal the area be tween the wall and pipe 3 Apply couplings to the vent pipe on the interior and exterior sides of the wall to insure the pipe...

Страница 19: ...the drainage hose of the furnace NOTE The condensate drain should be pro tected from freezing when in unheated spaces The furnace is supplied with an internal conden sate drain trap CAUTION Do not in...

Страница 20: ...y line and the entry hole in the furnace casing to avoid unwanted noise and or damage to the furnace All gas piping must be installed in compliance with local codes and utility regulations Some localr...

Страница 21: ...proved method High Altitude Derate The nameplate input rating for the furnaces apply for elevations up to 4 000 feet above sea level for US and Canada If the elevation for the furnace location is high...

Страница 22: ...emove the four 4 fasteners that secure the gas manifold to the burner box as shown in Figure 25 Carefully remove the gas manifold assembly from the burner box Note that the gas manifold assembly consi...

Страница 23: ...auge Installation NOTE For natural gas installations the in coming gas line pressure at the gas valve inlet must be between 4 5 WC and 10 0 WC For LP gas installations the incoming gas line pres sure...

Страница 24: ...operation CAUTION To avoid electric shock personal injury or death turn off the power at the disconnect or the main service panel before making any electrical connections ELECTRICAL WIRING General El...

Страница 25: ...XFMR Unused Motor Leads EAC Electronic Air Tap 5A 120 VAC Status Light Red Humidifier Tap 5A 120 VAC Connect Neutral Lead of Electronic Air Cleaner and or Humidifier Here Common Leads Blower Off Timin...

Страница 26: ...the require ments of all applicable local and federal codes For installation of the VentilAire III or IV follow the instructions provided with the VentilAire kit START UPANDADJUSTMENTS General Prior t...

Страница 27: ...in water column for use with natural gas Themanifoldpressuremustbesetat10 0in water column for use with LP gas Verifying and Adjusting Temperature Rise Verify that the temperature rise through the fur...

Страница 28: ...ould extend from each burner without lifting curling orfloating Afterverifyingignition setthe thermostat below room temperature and verify that the burner flame extinguishes completely Replace the fro...

Страница 29: ...ury or death turn off the power at the disconnect or the main service panel before performing any maintenance WARNING Holesintheventpipeorheatexchanger can cause products of combustion to enter the oc...

Страница 30: ...flammable vapors and liquids in the vicinity of the furnace Change or replace the air filters monthly during any period when the circulating blower is operating regularly Always replace the doors on t...

Страница 31: ...ately The blowers continue to operate until the limit closes When the limit closes the inducer blower is de energized immediately The circulating airblowercontinuestooperateforthespeci fied delay fact...

Страница 32: ...ollout Switch 7 J Trap Hard Tube 8 LowVoltageTransformer 9 In Line Drain Assembly 10 Junction Box 11 Vent Safety Switch Figure 29 Location of Major Components 12 Ignitor Assembly 13 Burner View Port 1...

Страница 33: ...L C WHITE RED ORANGE BLUE BLACK MOTOR PLUG 1 2 3 4 5 6 BLACK BLUE FLAME ROLL OUT SWITCH ALL MODELS PRESSURE SWITCH R Y G W C Y 180 120 90 60 Legend Field Wiring Factory Wiring Low Voltage High Voltag...

Страница 34: ...34...

Страница 35: ...r Temperature __________ F Return Air Temperature _________ F Temperature Rise ______________ F UNIT SERIAL NUMBER ________________ Are Flue Connections tight _____________ Is there Proper Draft _____...

Страница 36: ...O Fallon MO 708219D Replaces708219C Specificationsandillustrationssubjecttochangewithout noticeandwithoutincurringobligations Printedin U S A 04 04 7082197 708219D...

Отзывы: