4.7 Indications of the two-colour LED

4.8 System and servicing indications

Operation

Niveau max. attained

Manual drainage open

Code U1: Servicing signal

Code U2: Excess current

Code U3: Humidifier fills continuously

Code U4: Microcontroller uncoded

The newly-developed electronic controls unit with microcontroller
continuously monitors the operations of the NOVAP 3000 humidifier. Any
deviations from the operating condition (U codes) are shown with
the two-colour LED. The status of the LED can be shining continuously or
flashing in the red and green colours. The combination of these
different possibilities permits the indication of all U codes.

LED shining green continuously

The humidistat or humidity controller demands humidification. The NOVAP
3000 humidifier operates automatically. Without demand of humidity the
LED remains dark.

red flash in the shining green of the LED

Occurs when the Niveau max. sensor has been attained.

LED flashing red-green-red-green

When the manual drainage is activated by pressing the black button on
the electronic print.

LED flashing green

The steam cylinder can no longer attain the nominal output and needs,
therefore, to be cleaned or perhaps replaced. A visual inspection of the
inside of the cylinder is necessary to be able to decide whether it needs
replacing. Code U1 is purely a servicing code; the unit does not switch off
automatically. The humidifier continues to function at a reduced output.
Acknowledgement is effected by switching the unit off and on with the
black power switch.

LED shining red continuously

Whenever there is excess current (140% of the nominal value) during nor-
mal operations, the humidifier switches itself off automatically for safety
reasons. After the fault has been rectified, the humidifier is put back into
operation by switching the unit off and on with the black power switch.

LED flashing red

Either there is no heating phase or no water in the cylinder due to the
water supply having been cut off. The humidifier switches itself off
automatically after 30 minutes and is put back into operation by switching
the unit off and on with the black power switch.

LED flashing red-red-green-green

This signal appears if a replacement electronic controls unit has been
fitted to the humidifier without being coded. The humidifier is prevented
from operating. The signal disappears as soon as the electronic controls
unit has been coded.

Содержание NOVAP 3000

Страница 1: ...Operating Instructions Steam Humidifier 2401917 EN 0801 Nordmann NOVAP 3000 NORDMANN E N G I N E E R I N G NORDMANN E N G I N E E R I N G Dampfluftbefeuchter econoVap...

Страница 2: ...letely satisfied with our products 1 1 Dimensions 1 2 Steam nozzle 1 3 Fitting the humidifier 1 4 Fitting the steam distribution pipe 1 5 Fitting the blowers 1 6 Laying the steam hose 1 7 Laying the c...

Страница 3: ...nd third parties Apart from these safety instructions you should observe all national and local regulations The NOVAP 3000 steam humidifiers are intended solely for indirect via a steam distribution p...

Страница 4: ...8 5 15 1 470 645 305 1 x 35 1 x 22 17 32 23 1 470 645 305 1 x 35 1 x 22 18 33 32 1 525 715 360 1 x 35 1 x 22 28 53 45 1 525 715 360 2 x 35 1 x 22 29 54 64 2 975 730 385 2 x 35 2 x 22 62 112 90 2 975 7...

Страница 5: ...Fig Art no 22 300 300 22 176 60 5 902 00 00 22 450 450 22 300 70 5 902 00 01 22 650 650 22 504 70 5 902 00 02 22 850 850 22 696 70 5 902 00 03 35 300 300 35 200 55 5 902 00 04 35 450 450 35 300 80 5 9...

Страница 6: ...F Fig 10 Fig 11 B C A D E G F H J B C A D E G F H J A B D C E F G Type A B 4 8 kg 100 130 15 23 kg 180 240 Fig Type A B C D E F G mm mm mm mm mm mm mm 8 4 8 kg h 230 205 220 145 165 22 8 9 15 23 kg h...

Страница 7: ...s minimum distances that have been stipulated To open the humidifier turn the screw using the correct screwdriver in an anti clockwise direction the door to the water componentry or the electrics then...

Страница 8: ...he steam distribution pipes can be fitted either vertically or horizontally though you must ensure that the steam outlets are always vertical to the air flow If fitted horizontally these apertures mus...

Страница 9: ...on pipes of the humidifier the condensate can be bled off in the immediate vicinity An alternative method of bleeding off the condensate can be seen in the diagram Fig 22 Pressure compensation hose St...

Страница 10: ...all For the humidifier to work best correct steam distribution is essential For this reason you must observe the minimum distances when installing the equipment B A 10 Fig 23 Fig 25 Fig 24 Max steam A...

Страница 11: ...er hoses are utilised NORDMANN cannot be held responsible for any damage that may occur A hose clamp should be used to link the hose to the steam distribution pipe When laying the steam hose in pipes...

Страница 12: ...f the hose in the filling cup In this instance a small siphon should be formed with the condensate hose If the condensate is drained off directly it is advisable to feed back the condensate hose separ...

Страница 13: ...DMANN s electrode steam humidifiers allow you to use water ranging from soft to very hard without the need for prior treatment However for fairly hard water and above we recommend the use of the SC sy...

Страница 14: ...stomer is responsible for verifying the qualifications of the technicians concerned Before performing any electrical work all power to the humidifier must be disconnected Please observe local regulati...

Страница 15: ...with the connection requirements cf technical specifications of the type of humidifier employed The electric supply cables must be connected to the unit s terminals correctly We recommend to re tighte...

Страница 16: ...n be processed 0 2 V 0 5 V 0 10 V 0 16 V 0 20 V SCS 1 5 V 2 10 V 0 20 mA 4 20 mA potentiometer min 135 Ohm 16 Type of Terminals Cross section of Cross section of Screw terminals humidifier mm2 heating...

Страница 17: ...smallest of adjustments to the water level can effect a change in the steam output Therefore the unit reacts quickly and accurately to any setpoint changes Because of its ultimate degree of efficiency...

Страница 18: ...ctronic print see Fig 34 and then removed After the drainage filter has been taken out the cylinder can be well flushed with tap water using no chemical substances The SC System is a patented self cle...

Страница 19: ...t 10 20 30 1000 500 1500 2000 t h d H rte Fig 33 1 DH 1 25 English hardness 1 DH 1 79 French hardness 1 DH 1 05 American hardness 1 DH 17 9 mg I CaCo3 ppm Hours with SC System without SC System DH Ger...

Страница 20: ...maximum water level or Niveau max can be attained When Niveau max has been reached the inlet valve closes briefly this is a normal occurrence during the steam cylinder s concentration phase The lengt...

Страница 21: ...no longer attain the nominal output and needs therefore to be cleaned or perhaps replaced A visual inspection of the inside of the cylinder is necessary to be able to decide whether it needs replacing...

Страница 22: ...on turns itself off automatically and Code U2 appears on the two colour LED 22 5 Servicing and maintenance Before commencing switch off all power to the humidifier and disconnect the unit from the mai...

Страница 23: ...advisable to wet slightly either the O ring seal on the drainer or the outside of the cylinder s drainage aperture since this makes it easier to fit the new cylinder The humidifier is re started in a...

Страница 24: ...gular servicing helps to maintain the operability and reliability of the humidifier All work must be carried out by qualified personnel only The customer is responsible for verifying the qualification...

Страница 25: ...any humidity A safety element such as a maximum humidistat etc is not allowing humidification to take place The safety link between terminals L1 and H has not been made if a proportional adaptor is us...

Страница 26: ...nal adaptor Allows the steam output of the NOVAP 3000 humidifiers to be set anywhere between 20 and 100 The proportional adaptor can be simply inserted onto the electronic controls unit Step adaptor A...

Страница 27: ...30 730 depth mm 230 230 230 230 305 305 360 360 385 385 Weight empty kg 11 11 12 12 17 18 28 29 62 64 Operating weight max kg 14 5 14 5 18 5 18 5 32 33 53 54 112 114 Accessories Humidity controller qt...

Страница 28: ...Consulting Sales and Service Reg No 40002 2 Solutions for Indoor Climate Manufacturer Nordmann Engineering AG www nordmann engineering com info nordmann engineering com NORDMANN E N G I N E E R I N G...

Отзывы: