23
9. Technical specifications
Type mark
Type
424
434
824
834
1534
2364
3264
4564
6464
6564
9064
13064
Heating voltage
V
400 V, 50/60 Hz
Number of phases
~
1
3
1
3
3
3
3
3
3
3
3
3
Heating current
A
7.6
4.4
15.2
8.8
16.5
25.2
35.1
49.4
2 x 35.1
71.3
2 x 49.4 2 x 71.3
External fuses p. phase
A
16
10
25
16
25
40
50
80
2 x 50
100
2 x 80
2 x 100
Type mark
Type
422
432
822
832
1532
2362
3262
6462
Heating voltage
V
230 V, 50/60 Hz
Number of phases
~
1
3
1
3
3
3
3
3
Heating current
A
13.2
7.6
26.4
15.3
28.6
43.9
61.0
2 x 61.0
External fuses p. phase
A
20
16
40
25
40
63
100
2 x 100
Steam output
kg/h
4
4
8
8
15
23
32
45
64
65
90
130
Minimum capacity
kg/h steam
0.8
0.8
1.6
1.6
3
4.6
6.4
9
6.4
13
9
13
Nominal power
kW
3.0
3.0
6.1
6.1
11.4
17.5
24.3
34.2
2 x 24.3
49.4
2 x 34.2 2 x 49.4
Design data
Dimensions
width mm
390
390
390
390
470
470
525
525
975
525
975
975
height mm
585
585
585
585
645
645
715
715
730
715
730
730
depth mm
230
230
230
230
305
305
360
360
385
360
385
385
Steam outlet diameter
mm
1 x 22
1 x 22
1 x 22
1 x 22
1 x 35
1 x 35
1 x 35
2 x 35
2 x 35
2 x 35
4 x 35
4 x 35
Weight (empty)
kg
11
11
12
12
17
18
28
29
62
30
64
66
Operating weight
kg
14.5
14.5
18.5
18.5
32
33
53
54
112
55
114
116
Accessories
Humidity controller
qty
1
1
1
1
1
1
1
1
2
1
2
2
Steam nozzle
qty
1
1
Control electronics
Supply voltage
V
220–240 V, 50/60 Hz, 1~
Proportional adaptor
qty
1
1
1
1
1
1
1
1
2
1
2
2
Steam distribution pipes for dct use
22-xxx mm
qty
1
1
1
1
35-300 mm
qty
1
35-450 mm
qty
1
1
2
35-600, 35-900 mm
35-1200, 35-1500 mm
qty
1
1
1
2
2
2
4
4
Steam hose
Ø
22/29 mm
qty x mm
1
1
1
1
Ø
35/43 mm
qty x mm
1
1
1
2
2
2
4
4
Condensate hose
Ø
6/10 mm
qty x mm
1
1
1
1
1
1
1
2
2
2
4
4
Steam blowers for direct room humidification
Fitted onto humidifier
qty
1
1
1
1
1
1
Fitted separately
qty
1
1
1
1
1
1
1
1
2
1
2