1.5 Fitting the steam blowers
All installation work must be performed by trained personnel.
The customer himself is responsible for verifying their qualifications.
The steam blower for distributing the steam in the room can be fitted either directly onto the humidifier itself
(excepting types 32 to 130 kg/h) or onto a wall.
For the humidifier to work best, correct steam distribution is essential. For this reason, you must observe the minimum
distances when installing the equipment.
Minimum distances for steam blowers of type 4-23 kg/h
Minimum distances for steam blowers of type 32-65 kg/h
B
A
Fig. 23
Fig. 25
Fig. 24
450 mm
450 mm
min.
15 m
. 15 m
Type 32: min. 1500 mm
Type 45: min. 2000 mm
Technical specifications for steam blowers
!
Type
A B
min.
min.
4 kg
600 mm
3 m
8 kg
900 mm
5 m
15 kg
1000 mm
7 m
23 kg
1000 mm
10 m
Max. steam
Air flow
Power
Nominal
Weight
Steam pipe
Condensate
Noise
output
m
3
/h
supply
power
kg
H
pipe G
level (1m)
4 kg/h-8 kg/h
110 200/240 V
25 W
5
Ø 22 mm
Ø 8 mm
46 dB (A)
15 kg/h-23 kg/h
650 50/60 Hz
170 W
15
Ø 35 mm
Ø 8 mm
54 dB (A)
32 kg/h
800 220/240 V
110 W
8
Ø 35 mm
Ø 8 mm
72 dB (A)
45
&
65 kg/h
800 50/60 Hz
110 W
8
2 x Ø 35 mm
Ø 8 mm
72 dB (A)
Type 32: min. 1500 mm
Type 45
&
65: min. 2000 mm