NORDAC SK 1xxE

 

BU 0100 GB 

Technical Modifications Reserved 

1    General description 

The product series NORDAC SK 1xxE constitutes a motor or wall-mounted electronic component that can be 
used to handle simple drive or switching functions. The following types are part of this product series: 

SK 140E 

Electronic motor starter

 

 

 

(Startup in one direction) 

SK 150E 

Electronic soft starter

  

 

 

(Soft startup and run-down with adjustment of time and torque) 

SK 160E 

Electronic reversing starter

  

 

 

(Startup possible in both directions) 

The electronics of this motor starter series are integrated into the motor's terminal box. They can be directly 
mounted on top of the motor (motor-integrated) or on the wall (proximity of motor). Each starter possesses an 
assessment of a thermal protector (temperature probe or control) and an optional brake rectifier. A red or a 
green LED visable from the outside through a transparent screw plug, indicating the devices status. 

 

The 

NORDAC SK 140E

 enables a switching operation of a three-phase asynchronous motor in one direction. 

This allows for cost-efficient switching directly at the drive. 

The 

NORDAC SK 150E

 enables a soft start-up and run-down of three-phase asynchronous motors. This 

allows for starting and stopping of the drive smoothly. With the soft starter, both torque and times can be set 
separately for the startup and rundown of a drive.  

The 

NORDAC SK 160E 

enables the switching operation of a three-phase asynchronous motor in both 

directions. 2 rotary dip code switches are used to set a locking time to protect the installation against damage 
caused by too quick a reversal. 

 

The entire power range of the motor starter series is covered by one component size. The power range of the 

SK 

140E

 reaches from 

0.12 kW to 3.0 kW

, that of the 

SK 150E

 and 

SK 160E

 cover a range from 

0.12 to 4.0 kW

Motor sizes 80 to 112 (with the SK 140E up to size 100) allow for direct mounting; sizes 63 to 71 require a simple 
adapter plate (Mat. No. 11015410). 

The number of poles of a motor is immaterial; the only determining variable for the motor starter are the power 
consumption and the motor size. 

The control electronics require 24 VDC (15 ...30 VDC, 

 50 mA) supply voltage, e.g., from a PLC or another power 

supply. 

Optionally, each SK 1xxE is available with an integrated fast acting rectifier (BSG2). The electromechanical brake 
can then be directly connected to the device; no additional supply voltage is required for the brake. 

A bus access is possible for all electronic starters of the SK 1xxE series by means of an optional AS interface 
(AS1). 

With the option (MS) there is the possibility of realising the power input or motor output of the starter by means of a 
system plug of the Harting HAN 10E type. 

All devices of the 

SK150E/160E

 series in the versions with and without integrated brake rectifiers fulfil the 

requirements for explosion protection  (

ATEX

) in 

Zone 22

 according to the currently valid standards according 

to EN 50281 (Guideline 94/9/EG). However, this only applies if no further add-on options (AS interface, plug 
connectors) are included. 

The most current information and documentation can be downloaded free of charge from the homepage of 
Getriebebau NORD at 

www.nord.com

 

Содержание NORDAC SK 1 E Series

Страница 1: ...Manual NORDAC SK 1xxE Series SK 140E Electronic motor starter SK 150E Electronic soft starter SK 160E Electronic reversing starter BU 0100 GB Getriebebau NORD GmbH Co KG...

Страница 2: ...60E 18 4 1 Principle of function 18 4 2 Device design 19 4 2 1 SK 160E 1 O C 3D T125 20 4 2 2 SK 160E 1 BSG2 C 3D T125 20 4 2 3 SK 160E 1 x C MS 20 4 2 4 SK 160E AS1 x C MS 20 4 3 Electrical connectio...

Страница 3: ...itches are used to set a locking time to protect the installation against damage caused by too quick a reversal The entire power range of the motor starter series is covered by one component size The...

Страница 4: ...nection from system power ATTENTION Touching open or exposed terminals can lead to serious injuries or death Always use insulated screw drivers on these terminal panels Make sure that the input voltag...

Страница 5: ...thermally monitored through temperature probes acting as overload cutout There are 2 monitoring modes that can be selected by means of a slide switch During automatic operation slide switch set to ON...

Страница 6: ...ted fast acting brake rectifier has the designation SK 140E 1 BSG2 Mat No 275101405 With this device design a fast acting brake rectifier has been added to the basic function to directly control a bra...

Страница 7: ...ple circuit diagram L L O N 1 O FF 2x L3 L2 L1 24V DC OK RUN GND Bremsspule Kaltleiter oder Temperaturw chter Br cke f r langsames Abschalten Motorklemmen Terminal Function Data Power unit System pote...

Страница 8: ...sed to switch the automatic operation on or off This refers to the characteristics of switching on again after the motor starter has cut off because of excess motor temperature ON Switching off OK mes...

Страница 9: ...leased o During the entire operation the motor can be thermally monitored through temperature probes PTC resistor or temperature control thereby acting like an overload cut out There are 2 monitoring...

Страница 10: ...s the designation SK 150E 1 BSG2 Mat No 275101505 With this device design a fast acting brake rectifier has been added to the basic function to directly control a brake mounted to the motor Consequent...

Страница 11: ...ptional M12 plug Principle circuit diagram Terminal Function Data Power unit System potential L1 L2 L3 System connection 4 mm 2 200 380 480 V 50 60 Hz PE Housing ground 4 mm 2 L Bridge L 1 5 mm 2 BR B...

Страница 12: ...h maximum torque Motor receives full voltage red LED ON a fault is present green LED Blinking 1 x Pause RUN RIGHT was already active before applying the 24 VDC Blinking 2 x Pause Automatic feature is...

Страница 13: ...he principle of the phase control must always be observed by which the variable torque is merely determined by the voltage applied to the motor This does not allow ramp times and torques to be realize...

Страница 14: ...he value set at P1 The starting ramp begins here and reaches the maximum moment full voltage at motor after the time set in P2 This time also applies to the run down ramp after removing the release RU...

Страница 15: ...1 and 10 but without run down time or engagement time of the brake Dip switches 3 and 4 Time basis for potentiometers P2 and P4 00 This setting is used to determine which time range applies for the po...

Страница 16: ...code or switch position 0 0 P3 Run down moment P4 Run down time P1 Start up moment P2 Start up time 0 1 P3 Initial breakaway moment P4 Initial breakaway time P1 Start up Run down moment P2 Start up R...

Страница 17: ...peration The slide switch is used to switch the automatic operation on or off It refers to the characteristics of switching on again after the motor starter has cut off because of excess temperature o...

Страница 18: ...can be thermally monitored through temperature probes acting like an overload cut out There are 2 monitoring modes that can be selected through a slide switch During automatic operation slide switch s...

Страница 19: ...SK 160E AS1 BSG2 MS 275101625 with with with Protection class IP 66 SK 160E 1 O C 3D T125 275151600 without external without without SK 160E 1 BSG2 C 3D T125 275151605 with without without SK 160E 1 O...

Страница 20: ...ith a Harting HAN 10E plug connector The configuration in the terminal box is described in Section 5 3 According to the version without or with an integrated brake rectifier the corresponding designat...

Страница 21: ...lten Schaltlogik Reversier steuerung RUN RIGHT Kaltleiter oder Temperaturw chter OK GND L3 L2 L1 2x 2x L R Motorklemmen Terminal Function Data Power unit System potential L1 L2 L3 System connection 4...

Страница 22: ...ches is active see chapter 0 Permanently on Electronic switch is active ON motor turns red LED ON a fault is present green LED Blinking 1 x Pause RUN RIGHT or RUN LEFT was already active before applyi...

Страница 23: ...the time accuracy is very high and can be exactly set again even if a device is replaced 4 4 3 Slide switch for automatic operation The slide switch is used to switch the automatic operation on or of...

Страница 24: ...rately installed brake rectifier must be used for supply voltages smaller than 380 V The bridge L allows conversion to a gradual switch off Bridge L open Direct current switch off quick cut in Bridge...

Страница 25: ...is mounted in the immediate vicinity of the drive and is not attached directly to the motor The optional Wall mounting kit is required for this and contains the pertaining mounting plate for the respe...

Страница 26: ...ed below Type designation SK 140E 1 O MS Mat No 275101410 SK 140E 1 BSG2 MS Mat No 275101415 Harting plug for SK 150E SK 160E The placement of the Harting plug is always on the opposite side of the sc...

Страница 27: ...n of the signals RUN and OK This plug in connection facilitates a quick replacement of a drive without problems The signal plug M12 is inserted into the M16 screwed cable gland of the terminal box Pin...

Страница 28: ...xxE is included in the table below Apart from the motor activation up to 3 additional sensors can be connected to M12 sockets and read Together they may draw max 130 mA current AS1 Assignment of M12 s...

Страница 29: ...at No 275101920 5 5 2 AS interface as additional optional assembly For the SK 160E with the use of the assembly MS Harting HAN 10E plug connector there is alternatively the possibility of leading out...

Страница 30: ...monitoring PTC or bimetallic switch assessment applied to system potential Interface 24 VDC M12 plug optional AS Interface optional Electrically separated Control logic digital input against system vo...

Страница 31: ...e SK 1xxE SK 140E SK 150E SK 160E g o g1 m n p g1 m n p BG 63 123 192 158 9 153 108 167 8 185 139 BG 71 138 214 167 17 176 0 BG 80 156 236 159 26 169 9 BG 90 176 276 164 30 174 14 BG 100 194 306 175 3...

Страница 32: ...Co KG Rudolf Diesel Str 1 22941 Bargteheide For questions regarding the repair please contact Getriebebau NORD GmbH Co KG Telephone 04532 401 515 Telefax 04532 401 555 If a NORDAC SK 1xxE is returned...

Страница 33: ...cking time 23 M maintenance 32 motor starter 3 5 O operating modes 13 options 24 P plug M12 27 potentiometer 13 17 power supply 3 protection class 30 R rectifier 24 reversing starter 3 18 rotary dip c...

Страница 34: ...om Indonesia Indonesien PT NORD Indonesia Jln Raya Serpong KM 7 Kompleks Rumah Multi Guna Blok D No 1 Pakulonan Serpong Tangerang West Java Indonesia Fon 62 21 5312 2222 Fax 62 21 5312 2288 info nord...

Страница 35: ...fo nord hg com Italy Italien NORD Motoriduttori s r l Via Newton 22 IT 40017 San Giovanni in Persiceto BO Fon 39 051 6870 711 Fax 39 051 6870 793 info nord it com Netherlands Niederlande NORD Aandrijv...

Страница 36: ...911 67 24 71 NL Nuernberg nord de com Agency Hans Hermann Wohlers Handelsgesellschaft mbH Ellerbuscher Str 179 32584 L hne Telephone 05732 40 72 Telefax 05732 123 18 NL Bielefeld nord de com Sales off...

Отзывы: