2.4. Single UPS installation

Installation and wiring must be carried out in accordance with the local 

electric laws and regulations by trained professionals.

  Step 1.

  Make sure that the mains wire and breakers of the building are 

rated for the capacity of the UPS to prevent electric shock or risk of fire.

NOTE!

Do not use the wall receptacle as the input power source for the UPS, as its rated 

current is less than the UPS’s maximum input current. The receptacle may be 

damaged and destroyed.

  Step 2.

  Switch off the mains switch in the building before installation.

  Step 3.

  Turn off all the connected devices before connecting to the UPS.

  Step 4.

  Prepare wires based on the following table:

Model

Wiring spec (minimum A cable should support)

Input (Ph)

Output (Ph)

Neutral

Battery Cabinet

Ground

Ranger 

60KT

100A

100A

165A

196A

100A

• 

The cables for 

Ranger 60KT

 should be able to withstand over 100A 

current for Input and Output phase, 165A for Neutral, 196A for battery 

cabinet and 100A for Ground. Please use corresponding thickness for each 

wire.

  Step 5.

  Remove the terminal block cover at the rear panel of UPS. Then 

connect the wires according to the following terminal block diagrams: 

(In case 

power wires need to be connected please connect the grounding/earthing wire 

first. On the contrary, in case you want to disconnect the power wires then please 

disconnect the grounding/earthing wire last.)

 

  

Diagram 3: 

Terminal block wiring diagram for Ranger 60KT

        

NOTE!

Please install the output breaker between the output terminal and the load, 

and the breaker should be qualified with leakage current protective function 

if necessary.

Battery wire connect schematic in additional battery cabinet

• 

Make sure that the wires are connected tightly with the terminals.

  Step 6.

  Put the terminal block cover back at the rear panel of the UPS.

IMPORTANT!

• 

Make sure a DC breaker or other protective device between UPS and the 

external battery pack is installed. If not, please install it carefully. Switch off 

the battery breaker before installation.

• 

Set the battery pack breaker in “OFF” position and then install the battery pack.

• 

Pay high attention to the rated battery voltage marked on the rear panel. 

If you want to change the numbers of the battery pack, please make sure 

you modify the setting simultaneously. The connection with wrong battery 

voltage may cause permanent damage of the UPS. Make sure the voltage of 

the battery pack is correct.

• 

Pay high attention to the polarity marking on external battery terminal 

block. And make sure the correct battery polarity is connected. Wrong 

connection may cause permanent damage of the UPS.

• 

Make sure the protective earth ground wiring is correct. The wire current 

spec, color, position, connection and conductance reliability should be 

checked carefully.

• 

Make sure the utility input & output wire is correct. The wire current spec, 

color, position, connection and conductance reliability should be checked 

carefully. Make sure the L/N side is correct, not reverse or short-circuited.

Battery wire connect 

schematic

Battery terminal block wiring 

diagram for HV 60KT

Содержание Ranger 60KT

Страница 1: ...Ranger Series User Manual 60KT 3 Phase IN 3 Phase OUT UPS UP33TOP160KRAAZ01B 234 35 21 0 Before using this product carefully read all product documentation and retain it for future reference...

Страница 2: ...MC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8 2 1 Unpacking and inspe...

Страница 3: ...lation An integral emergency shutoff switch which prevents additional load from the UPS in any mode of operation should be implemented during the installation Secure the grounding earthing wire before...

Страница 4: ...ee phase input NOTE There can be no derivation in the line that goes from the Backfeed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary po...

Страница 5: ...packaging for future use It is recommended to keep each equipment and battery set in their original packaging because they have been designed to provide maximum protection during transportation and st...

Страница 6: ...in 1000m the UPS power will not be derated When the altitude is over 1000m the output power will be derated by following the table Vertical No vibration and the degree of deviation from vertical shoul...

Страница 7: ...anger 60KT NOTE Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protective function if necessary Battery wire connec...

Страница 8: ...ation make sure that the two strings of batteries are connected correctly in order of GND terminals and the breaker of the battery pack is at ON position only in case of external battery packs presenc...

Страница 9: ...that takes a few seconds After initialization the main screen will display as shown below On the bottom there are five icons to represent five sub menus CONTROL MEASURE SETTING INFO DATALOG Main scree...

Страница 10: ...te All if the UPS is mute already Touch Yes activate audio function or No to keep mute Touch Back to return to CONTROL screen Mute All Cancel Mute All ON OFF Charger It will show Turn on Charger when...

Страница 11: ...Current Discharging Current The real time value of DC related information Temperature Temperature of R S and T phases Measure screen page 3 INPUT W R S and T input power in watt INPUT VA R S and T inp...

Страница 12: ...the acceptable input frequency will be fixed at the range of 40 70Hz This setting value will show on the status bar Service Contact Set the name of contact person and the maximum length is 18 characte...

Страница 13: ...sword is wrong it will ask to enter again Password error page Advance Setting Menu page There are three sub menus under Advance User setting ELECTRONIC BATTERY and MISCELLANEOUS ELECTRONIC Electronic...

Страница 14: ...When neutral is restored the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode automatically ISO Compensation When UPS is connected to output isolation it will compensa...

Страница 15: ...then utility restores the UPS will return to line mode Disable After Disable is set once UPS shutdown occurs and the utility restores the UPS will not automatically turn on Shutdown Delay Min UPS wil...

Страница 16: ...ble ECO function Auto Restart Enable disable auto restart function PARAMETER information Parameter Information Page1 Line Voltage Range The acceptable line input voltage range Line FRE Range The accep...

Страница 17: ...S operates in Bypass mode and supplies power to the load via the bypass NOTE When UPS is in Bypass mode the output voltage will draw power from utility after you switch on the input breaker In Bypass...

Страница 18: ...may vary from different environment temperature and load type When setting backup time for 16 5 hours default value from LCD menu after discharging 16 5 hours UPS will shut down automatically to prote...

Страница 19: ...nician that installed the UPS if you need to start parallel operations 3 5 1 Parallel system initial startup Please make sure that all of the running UPSs are parallel models and have the same configu...

Страница 20: ...d in each UPS and then turn off the running system All UPSs will transfer to Bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS position Turn off all...

Страница 21: ...current in A phase 34 Synchronous trigger signal failure 75 INV IGBT over current in B phase 35 Parallel communication loss 76 INV IGBT over current in C phase 36 Parallel output current unbalance 77...

Страница 22: ...UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit occurs on the UPS output...

Страница 23: ...capacitor such as BUS capacitors Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must...

Страница 24: ...nd other European countries with separate collection systems EU Declaration of Conformity We manufacturer importer declare that the products UPS Ranger Series UP33TOP160KRAAZ01B are in conformity with...

Страница 25: ...Memo...

Отзывы: