background image

34

35

  If the UPS is overload, the buzzer will beep twice every second.

  If the UPS is overloaded, please remove some loads immediately. It is 

recommended to have the total loads connected to the UPS less than 80% of 

its nominal power capacity to prevent overload for system safety.

  If the overload time is longer than the acceptable time listed in spec at AC 

mode, the UPS will automatically transfer to Bypass mode. After the overload 

is removed, it will return to AC mode. If the overload time is longer than the 

acceptable time listed in spec at Battery mode, the UPS will enter into fault 

status. At this time, if bypass is enabled, the UPS will power to the load via 

bypass. If bypass function is disabled or the input power is not within bypass 

acceptable range, it will cut off output directly.

 3.4.4.

 

Charge the batteries

  After the UPS is connected to the utility power, the charger will charge 

the batteries automatically except in battery mode or during battery self-test 

or overload or battery high voltage.

  Suggest to charge batteries at least 10 hours before use. Otherwise, the 

backup time may be shorter than expected.

  3.4.5.

 

Battery mode operation

  When the UPS is in Battery mode, the buzzer will sound according to 

different battery capacity. If the battery capacity is more than 25%, the 

buzzer will beep once every 4 seconds. If the battery voltage drops to the 

alarm level, the buzzer will beep quickly (once every sec) to remind users that 

the battery is at low level and the UPS will shut down automatically soon. 

Users could switch off some non-critical loads to disable the shutdown alarm 

and prolong the backup time. If there is no more load to be switched off at 

that time, you have to shut down all loads as soon as possible to protect the 

devices or save data. Otherwise, there is a risk of data loss or load failure.

  In Battery mode, users can touch “SETTING” 

 “Basic” 

 Audio Mute to 

enable “Mode Mute” to disable the buzzer.

  The backup time of the long-run model depends on the external battery 

capacity.

  The backup time may vary from different environment temperature and 

load type.

  When setting backup time for 16.5 hours (default value from LCD menu), 

after discharging 16.5 hours, UPS will shut down automatically to protect the 

battery. This battery discharge protection can be enabled or disabled through 

LCD menu.

 3.4.6.

 

Test the batteries

  If you need to check the battery status when the UPS is running in AC 

mode/CVCF mode, you could touch “CONTROL” and select “Battery Test”. 

Refer to “Battery Test” screen.

  Users also can set battery self-test through monitoring software.

 3.4.7.

 

Turn off the UPS with utility power supply in AC mode

  Touch “CONTROL” and select “Turn off UPS” icon to turn off the UPS. 

Refer to “UPS on/off” screen.

NOTE! 

 

If the UPS has been set to bypass output, it will bypass voltage from the utility 

power to output terminal even though you have turned off the UPS (inverter).

  After turning off the UPS, please be aware that the UPS is working at Bypass 

mode and there is risk of power loss for connected devices.

  In Bypass mode, output voltage of the UPS is still present. In order to 

cut off the output, switch off the line input breaker(for dual input unit, also 

switch off the bypass line breaker). A few seconds later, there is no display 

shown on the display panel and UPS is completely off.

  In Bypass mode, output voltage of the UPS is still present. In order to cut 

off the output, switch off the line input breaker and switch off the bypass line 

breaker. A few seconds later, there is no display shown on the display panel 

and UPS is complete off.

  3.4.8.

 

Turn off the UPS without utility power supply in Battery mode

  Touch “CONTROL” and select “Turn off UPS” icon to turn off the UPS. 

Refer to “UPS on/off” screen.

  Then UPS will cut off power to output terminals.

 3.4.9.

 

Mute the buzzer

  Touch “SETTING” and select “BASIC” item. There are two events available 

to mute. Refer to “SETTING” screen.

  Some warning alarms can’t be muted unless the error is fixed. Please refer 

to section 3-3 for details.

 3.4.10.

 

Operation in warning status

  When Fault LED illuminates and the buzzer beeps once every second, 

it means that there are problems for UPS operation. Users can read the 

warning message(s) from “DATA LOG” menu. Please refer to the Section 3-2-

6 for details.

Содержание Ranger 60KT

Страница 1: ...Ranger Series User Manual 60KT 3 Phase IN 3 Phase OUT UPS UP33TOP160KRAAZ01B 234 35 21 0 Before using this product carefully read all product documentation and retain it for future reference...

Страница 2: ...MC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8 2 1 Unpacking and inspe...

Страница 3: ...lation An integral emergency shutoff switch which prevents additional load from the UPS in any mode of operation should be implemented during the installation Secure the grounding earthing wire before...

Страница 4: ...ee phase input NOTE There can be no derivation in the line that goes from the Backfeed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary po...

Страница 5: ...packaging for future use It is recommended to keep each equipment and battery set in their original packaging because they have been designed to provide maximum protection during transportation and st...

Страница 6: ...in 1000m the UPS power will not be derated When the altitude is over 1000m the output power will be derated by following the table Vertical No vibration and the degree of deviation from vertical shoul...

Страница 7: ...anger 60KT NOTE Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protective function if necessary Battery wire connec...

Страница 8: ...ation make sure that the two strings of batteries are connected correctly in order of GND terminals and the breaker of the battery pack is at ON position only in case of external battery packs presenc...

Страница 9: ...that takes a few seconds After initialization the main screen will display as shown below On the bottom there are five icons to represent five sub menus CONTROL MEASURE SETTING INFO DATALOG Main scree...

Страница 10: ...te All if the UPS is mute already Touch Yes activate audio function or No to keep mute Touch Back to return to CONTROL screen Mute All Cancel Mute All ON OFF Charger It will show Turn on Charger when...

Страница 11: ...Current Discharging Current The real time value of DC related information Temperature Temperature of R S and T phases Measure screen page 3 INPUT W R S and T input power in watt INPUT VA R S and T inp...

Страница 12: ...the acceptable input frequency will be fixed at the range of 40 70Hz This setting value will show on the status bar Service Contact Set the name of contact person and the maximum length is 18 characte...

Страница 13: ...sword is wrong it will ask to enter again Password error page Advance Setting Menu page There are three sub menus under Advance User setting ELECTRONIC BATTERY and MISCELLANEOUS ELECTRONIC Electronic...

Страница 14: ...When neutral is restored the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode automatically ISO Compensation When UPS is connected to output isolation it will compensa...

Страница 15: ...then utility restores the UPS will return to line mode Disable After Disable is set once UPS shutdown occurs and the utility restores the UPS will not automatically turn on Shutdown Delay Min UPS wil...

Страница 16: ...ble ECO function Auto Restart Enable disable auto restart function PARAMETER information Parameter Information Page1 Line Voltage Range The acceptable line input voltage range Line FRE Range The accep...

Страница 17: ...S operates in Bypass mode and supplies power to the load via the bypass NOTE When UPS is in Bypass mode the output voltage will draw power from utility after you switch on the input breaker In Bypass...

Страница 18: ...may vary from different environment temperature and load type When setting backup time for 16 5 hours default value from LCD menu after discharging 16 5 hours UPS will shut down automatically to prote...

Страница 19: ...nician that installed the UPS if you need to start parallel operations 3 5 1 Parallel system initial startup Please make sure that all of the running UPSs are parallel models and have the same configu...

Страница 20: ...d in each UPS and then turn off the running system All UPSs will transfer to Bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS position Turn off all...

Страница 21: ...current in A phase 34 Synchronous trigger signal failure 75 INV IGBT over current in B phase 35 Parallel communication loss 76 INV IGBT over current in C phase 36 Parallel output current unbalance 77...

Страница 22: ...UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit occurs on the UPS output...

Страница 23: ...capacitor such as BUS capacitors Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must...

Страница 24: ...nd other European countries with separate collection systems EU Declaration of Conformity We manufacturer importer declare that the products UPS Ranger Series UP33TOP160KRAAZ01B are in conformity with...

Страница 25: ...Memo...

Отзывы: