CVCF Mode

 (constant voltage and constant frequency function)

  Enable: CVCF function is enabled. The output frequency will be fixed at 

50Hz or 60Hz according to setting of “OP Freq.”. The input frequency could 

be from 46Hz to 64Hz.

  Disable: CVCF function is disabled. The output frequency will synchronize 

with the bypass frequency within 46~54 Hz for 50Hz system or within 

56~64 Hz for 60Hz system. Disable is the default setting.

Bypass Forbid:

  Enable: Bypass forbid is enabled. When selected, it’s not allowed for 

running in Bypass mode under any situations.

  Disable: Bypass forbid is disabled. When selected, UPS will run in Bypass 

mode depending on “Bypass at UPS off” setting. It is the default setting.

Neutral Line Check:

  Disable: Disable the neutral line check function. The UPS will not detect if 

the neutral line is loss or not. 

  Auto: The UPS will automatically detect if the neutral is lost or not. If 

neutral loss is detected, an alarm will be generated. If the UPS is turned on, it 

will transfer to battery mode. When neutral line is restored and detected, the 

alarm will be muted automatically and the UPS will go back to normal mode 

automatically. 

  Check: The UPS will automatically detect the neutral loss. If neutral loss is 

detected, an alarm will be generated. If the UPS is turned on, it will transfer 

to battery mode. When neutral is restored, the alarm will NOT be muted 

automatically and the UPS will NOT go back to normal mode automatically. 

  ISO Compensation: When UPS is connected to output isolation, it will 

compensate the output voltage.

Electronic Menu page 2

Bypass at UPS off:

 Select the bypass status when manually turning off the 

UPS. This setting is only available when “Bypass forbid.” is set to “Disable”.

  Enable: Bypass enabled. When selected, bypass mode is activated.

  Disable: Bypass disabled. When selected, no output through bypass when 

manually turning off the UPS.

Bypass Voltage Range:

 Set the bypass voltage range.

  L: Low voltage point for bypass. The setting range is 176V ~ 209V.

  H: High voltage point for bypass. The setting range is 231V ~ 264V.

Bypass FREE Range:

 Set the bypass frequency range.

The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 

50Hz system and from 56Hz to 64Hz when UPS is 60Hz system.

ECO mode:

 Enable/Disable ECO mode. Default setting is “Disable”.

ECO Voltage Range:

 Set the ECO voltage range.

  L: Low voltage point for ECO mode. The setting range is from “Rated 

output voltage – 5V” to “Rated output voltage - 11V”. “Rated output voltage 

– 5V” is default setting.

  H: High voltage point for ECO mode. The setting range is from “Rated 

output v 5V” to “Rated output v 11V”. “Rated output voltage 

+ 5V” is default setting.

ECO FREE Range: 

Set the ECO frequency range. The setting range is from 

46Hz to 54Hz when the UPS is 50Hz system and from 56Hz to 64Hz when 

the UPS is 60Hz system.

 •

 

BATTERY

Battery setting page

Содержание Ranger 60KT

Страница 1: ...Ranger Series User Manual 60KT 3 Phase IN 3 Phase OUT UPS UP33TOP160KRAAZ01B 234 35 21 0 Before using this product carefully read all product documentation and retain it for future reference...

Страница 2: ...MC instructions 5 1 1 Transportation and storage 5 1 2 Preparation 5 1 3 Installation 5 1 4 Connection warnings 6 1 5 Operation 7 1 6 Standards 7 2 Installation and operation 8 2 1 Unpacking and inspe...

Страница 3: ...lation An integral emergency shutoff switch which prevents additional load from the UPS in any mode of operation should be implemented during the installation Secure the grounding earthing wire before...

Страница 4: ...ee phase input NOTE There can be no derivation in the line that goes from the Backfeed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary po...

Страница 5: ...packaging for future use It is recommended to keep each equipment and battery set in their original packaging because they have been designed to provide maximum protection during transportation and st...

Страница 6: ...in 1000m the UPS power will not be derated When the altitude is over 1000m the output power will be derated by following the table Vertical No vibration and the degree of deviation from vertical shoul...

Страница 7: ...anger 60KT NOTE Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protective function if necessary Battery wire connec...

Страница 8: ...ation make sure that the two strings of batteries are connected correctly in order of GND terminals and the breaker of the battery pack is at ON position only in case of external battery packs presenc...

Страница 9: ...that takes a few seconds After initialization the main screen will display as shown below On the bottom there are five icons to represent five sub menus CONTROL MEASURE SETTING INFO DATALOG Main scree...

Страница 10: ...te All if the UPS is mute already Touch Yes activate audio function or No to keep mute Touch Back to return to CONTROL screen Mute All Cancel Mute All ON OFF Charger It will show Turn on Charger when...

Страница 11: ...Current Discharging Current The real time value of DC related information Temperature Temperature of R S and T phases Measure screen page 3 INPUT W R S and T input power in watt INPUT VA R S and T inp...

Страница 12: ...the acceptable input frequency will be fixed at the range of 40 70Hz This setting value will show on the status bar Service Contact Set the name of contact person and the maximum length is 18 characte...

Страница 13: ...sword is wrong it will ask to enter again Password error page Advance Setting Menu page There are three sub menus under Advance User setting ELECTRONIC BATTERY and MISCELLANEOUS ELECTRONIC Electronic...

Страница 14: ...When neutral is restored the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode automatically ISO Compensation When UPS is connected to output isolation it will compensa...

Страница 15: ...then utility restores the UPS will return to line mode Disable After Disable is set once UPS shutdown occurs and the utility restores the UPS will not automatically turn on Shutdown Delay Min UPS wil...

Страница 16: ...ble ECO function Auto Restart Enable disable auto restart function PARAMETER information Parameter Information Page1 Line Voltage Range The acceptable line input voltage range Line FRE Range The accep...

Страница 17: ...S operates in Bypass mode and supplies power to the load via the bypass NOTE When UPS is in Bypass mode the output voltage will draw power from utility after you switch on the input breaker In Bypass...

Страница 18: ...may vary from different environment temperature and load type When setting backup time for 16 5 hours default value from LCD menu after discharging 16 5 hours UPS will shut down automatically to prote...

Страница 19: ...nician that installed the UPS if you need to start parallel operations 3 5 1 Parallel system initial startup Please make sure that all of the running UPSs are parallel models and have the same configu...

Страница 20: ...d in each UPS and then turn off the running system All UPSs will transfer to Bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS position Turn off all...

Страница 21: ...current in A phase 34 Synchronous trigger signal failure 75 INV IGBT over current in B phase 35 Parallel communication loss 76 INV IGBT over current in C phase 36 Parallel output current unbalance 77...

Страница 22: ...UPS output and restart it Troubleshooting 4 Problem Possible cause Solutions Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit occurs on the UPS output...

Страница 23: ...capacitor such as BUS capacitors Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must...

Страница 24: ...nd other European countries with separate collection systems EU Declaration of Conformity We manufacturer importer declare that the products UPS Ranger Series UP33TOP160KRAAZ01B are in conformity with...

Страница 25: ...Memo...

Отзывы: