30 / 32
pmm5111a0600p_01
11.2
M
ODBUS
C
OMMUNICATION
The unit uses the following Modbus functions:
MODBUS
DECIMAL
FUNCTION CODE
PARAMETER
FORMAT
MODBUS MEANING
DESCRIPTION
01/02
Bit
Read coil/ Input status
Read output/input status bits at given
address
03/04
Word
Read holding/Input registers
Read current binary value of specified
number of parameters at given
address.
Up to 64 parameters can be accessed
with one Query
05 Bit
Force
single
coil
Writes a single binary bit to the
Specified Slave Bit address
06 Word
Pre-set
single
register
Writes two bytes to a specified word
address
08
-
Diagnostics
Used for loopback test.
16
Word
Pre-set multiple register
Writes up to 1 word parameter values
to the specified address range.
11.3
C
OMMUNICATION
P
ARAMETERS
Communication parameters RO indicates a parameter which is read only, R/W indicates it can also be
written to. Communications writes will not implemented if the
(Communications Write Parameter) is
disabled in the Configuration Mode.
11.3.1
B
IT
P
ARAMETERS
MODBUS PARAMETER
NUMBER MODE
CONTROLLING PARAMETER
NOTES
1
RO
Communication Write Status
1 = Write Enabled
0 = Write Disabled
2
R/W
Auto / Manual
1 = Manual Control
0 = Automatic Control
3
R/W
Self Tune
1 = Activate(d)
0 = Dis-engage(d)
4
R/W
Pre tune
1 = Activate(d)
0 = Dis-engage(d)
5
RO
Alarm 1 Status
1 = Active
0 = Inactive
6
RO
Alarm 2 Status
1 = Active
0 = Inactive
7
R/W
Setpoint Ramping
1 = Enable(d)
0 = Disable(d)
10
R/W
Loop Alarm Status
1 = Active/Enable
0 = Inactive/Disable
12
R/W
Loop Alarm
Read to get loop alarm status.
Write 0/1 to disable/enable
Note:
To set the bit value to 1 write FF, to set the bit value to 0 write 00.