pmm5111a0600p_01
21 / 32
10.3
S
ET
-
UP
M
ODE
This mode is normally selected only after Configuration Mode has been completed, or is used when a
change to the process set up is required. These parameters must be set as required before attempting to
use the indicator in an application.
When in Set-up Mode, the MAN LED indicator flashes.
Navigating in Set-up Mode:
+
Select Mode
Toggle to the
next parameter
+
Return to the
Select Mode
Set-up
mode
Entering unlock code
Default value: 5
Entering set-up
mode menu
Toggle menu points
Setting the value
ar required
Caution
:
Entering an incorrect unlock code will result to return to Select Mode.
Only parameters that are applicable to the hardware options chosen will be displayed.
Once the displayed value is changed, it is effective and immediately. No confirmation of the change is
required.
If there is no key activity for 2 minutes the controller automatically returns to operator mode!
PARAMETER
SV-
DISPLAY
PV-DISPLAY
ADJUSTMENT RANGE
DEFAULT
VALUE
Input Filter Time constant
This parameter is used to filter out extraneous impulses on the
process variable. The filtered PV is used for all PV-dependent
functions (display control, alarm etc). The time constant is
adjustable from 0.0 seconds (off) to 100.0 seconds in 0.5
second increments.
2.0
Process Variable Offset
±Span of controller between -999…+999
0
Primary Power
The current Primary Output Power. Read Only
N/A
Secondary Power
Only visible when
=
set
The current Secondary Output Power. Read Only.
N/A
Primary Output Proportional Band
(P)
0.0% (ON/OFF control) and 0.5% to 999.9% of input span.
10.0
Secondary Output
Proportional Band (P)
Only visible when
=
set
0.0% (ON/OFF control) and 0.5% to 999.9% of input span
10.0
Automatic Reset (Integral Time
Constant) (I)
Only visible when
≠
0.0
0.01 to 99.59 (1 sec to 99 mins 59 secs)
OFF=0.00
5.00
Rate (Derivative Time Constant) (D)
Only visible when
≠
0.0
0.00 to 99.59 (OFF to 99 mins 59 secs)
1.15