- Page 18
-
to any unrepeated number from 2 – 240 before initializing the next sensor in a
network.
CAUTION: All sensors are supplied from the factory with the Sensor Address set
at 01. A unique address must be assigned to each sensor as it is added to the network
(powered ON). This procedure allows the Controller to establish communication
and provide a unique address for each sensor as it is added to the network. Failure
to follow this procedure will result in multiple sensors having the same address and
will prevent communication.
Press the Soft Key next to
Sensor Setup Complete
to finalize setup of the sensor.
The
Power Next Sensor Screen
(Figure 4.17) will appear. Apply power to the
EchoSmart Power Supply Unit connected to the next sensor and repeat the steps
above.
After all sensors have been initialized, Press the Soft Key next to the
Network Setup
Complete
prompt (Figure 4.17).
Figure 4.17: Power Next Sensor
All EchoSmart Sensors are now operational. See also Section 13.2 in the Quick
Start Guide of this manual.
4.4.3.
Replacing a Controller with Existing Sensor(s) (Figure 4.15)
If Smart Sensors have previously been initialized and the Controller is being
replaced, select
Replacing Controller with Existing Sensors
and press the Soft Key
next to
Replace Controller Only
. The Controller will automatically detect the
existing sensors and return to full operation after the initialization routine is
completed.
Содержание Echo Smart Series
Страница 2: ......
Страница 33: ... Page 24 Figure 6 1 EchoSmart Sensor Mounting Arrangements ...
Страница 37: ... Page 28 Figure 6 4 Controller Installation Drawing ...
Страница 38: ... Page 29 Figure 6 5 EchoSmart Power Supply Unit Installation Drawing ...
Страница 73: ... Page 64 Figure 13 1 Installation Recommendations and Field Measurement for Filter Applications ...