5.3.2.4
Output current error mode
Parameter: P12:
a
Menu path:
OUTPUT SETUP / ANALOG OUTPUT / ERROR MODE
Default value:
20.5 mA
Description:
Error indication on the current output.
OFF
Error indication is OFF. The device transmits in accordance to the last calculation.
3.9 mA in case of error, the output current gets 3.9 mA.
20.5 mA in case of error, the output current gets 20.5 mA.
Warning! This error indication will be active as long as the failure is fixed or otherwise resolved! Manual mode and HART mode
overwrite the error current.
5.3.2.5
Fixed output current
Parameter: P08
Menu path:
OUTPUT SETUP / ANALOG OUTPUT / MANUAL VALUE
Default value:
4 mA
Description:
Parameter for setting the fixed output current.
The values entered here must be between 3.9 and 20.5. The output current will take the entered value and analogue transmission will
be suspended. The set (current) value overrides the 4 mA output of HART multidrop mode. (See 5.3.2.1)
5.3.3
Digital output
HART short address
Parameter: P19
Menu path:
OUTPUT SETUP / SERIAL OUTPUT / ADDRESS
Default value:
01
Description:
HART short address
The short address can be set between 0 and 15. If there is only one device, the short address can be 0, and this case the device
transmits 4…20 mA on its output. In Multidrop (if there is more than one device) mode, the short address must be other than zero, and
the output current is fixed at 4 mA. The fixed 4 mA output can be overridden as described in
chapter 5.3.2.5.