6.6 DESCRIPTION OF THE MENU SYSTEM
Menu 1 –
Access protection
PAon
password active
to deactivate: enter password.
PAof
password inactive
to activate: enter password.
The default password is “0005”; modification of the password is described in
“Special menu 4”.
Menu 2 – Indication of the start of the measuring range (zero point)
Value defined at order, no input option.
Menu 3 – Indication of the end of the measuring range (end point)
Value defined at order, no input option.
Menu 4 and Menu 5 – Set zero point / end point
&
The configuration of the zero point affects the analog output,
whereas the display value remains unchanged (zero and endpoint can be
configured within the limits of the nominal pressure range, according to the
manufacturing label); for more information, see “6.3 Configuration the analog
output (example).”
Menu 6 – Set damping
This feature eliminates problems caused by rapidly changing
pressure values. By setting the time (0.3 – 30 sec), the current output signal
can be delayed. The higher the value entered, the longer it takes to reach the
current pressure output signal's value.
Menu 7 – Excess value message
Set “On” or “Off”.
Menu 8 – Switch output selector S1
“P1”, “P2” (the switching point reacts to the static pressure at the
appropriate input) or “DIFF” (difference pressure between P1 and P2)
Menu 9 – Set switch-on point for switching output S1
Set a switch-on value for S1 output.
(S1on)
Menu 10 – Set switch-off point for switching output S1
Set a switch-off value for S1 output.
(S1of)
Menu 11 – Switch output selector S2
“P1”, “P2” (the switching point reacts to the static pressure at the
appropriate input) or “DIFF” (difference pressure between P1 and P2)
Menu 12 – Set switch-on point for switching output S2
Set a switch-on value for S2 output. (
S2on
).
Menu 13 – Set switch-off point for switching output S2
Set a switch-off value for S2 output.
(S2of)
Menu 14 – Select hysteresis or compare mode of S1 output
&
Select the hysteresis mode (HY 1) or compare mode
(CP 1) for the contact 1. You can find a description from the hysteresis and
compare mode are in chapter 6.4.
Menu 15 – Select hysteresis or compare mode of S2 output
&
Select the hysteresis mode (HY 2) or compare mode
(CP 2) for the contact 1. You can find a description from the hysteresis and
compare mode at 6.4 chapter.
Menu 16 – Set switch-on delay for S1 output
Set the switch-on delay value for the S1 output. (0 – 100 sec).