
ddc4f52a0600p_01 10 / 17
6.3 CONFIGURING THE ANALOG OUTPUT (EXAMPLE)
The analog output can be configured in the menus
ZP
(zero point) and
EP
(end point). The following example shows how to use them:
In this example, the device has a measurement range of 0–6 bar (0–87 psi), and it is connected to P1. The analogous signal amounts to 4…20 mA / 3-wire and were
configured in the menu 26 “SiAn” on “P1.”
The output analog signal:
0 bar (0 psi) = 4.00 mA
3 bar (43.5 psi) = 12.00 mA
6 bar (87 psi) = 20 mA.
If the value is changed from 0 to 1 in ZP and the EP value from 6 to 5 , the output signal changes as follows:
1 bar (14.5 psi) = 4.00 mA
3 bar (43.5 psi) = 12.00 mA
5 bar (72.51) = 20 mA.
The values of ZP and EP are adjustable up to 1:10 of the nominal pressure range.
6.4 HYSTERESIS AND COMPARE MODES
The diagrams below show the operation of the switch outputs.
To reverse the relevant modes, you have to swap the values for the switch-on and switch-off points.
Compare mode inverted
Compare mode
Hysteresis mode inverted
Hysteresis mode
Содержание NIPRESS DD-400
Страница 1: ...ddc4f52a0600p_01 1 17...
Страница 2: ...ddc4f52a0600p_01 2 17...
Страница 11: ...ddc4f52a0600p_01 11 17 6 5 STRUCTURE OF THE MENU SYSTEM...
Страница 17: ...ddc4f52a0600p_01 17 17...