EasyTREK Compact Ultrasonic Level Transmitters
P05:
Minimum measuring distance (Close-end blocking)
The EasyTREK will not accept any echo within the
blocking distance set here.
Automatic Close-end-blocking (Automatic Dead Band control)
(P05= X
m
)
By using the factory default value, the unit will automatically set the smallest possible close-end-blocking distance i.e. the dead band.
Manual close-end-blocking
(P05> X
m
)
Manual close-end-blocking would be used for example to block out the echo originating from the bottom rim of a stand-off pipe or from any object
protruding into the ultrasonic cone near to the transmitter.
By entering a value, higher than the factory default, the minimum measuring range will be extended and fixed to the specified value.
EasyTREK
Minimum measuring distance (dead band)
Level transmitters
(m/ft)
SCA-38_
0,25 / 0,82
SCA-36_
0,35 / 1,2
FACTORY DEFAULT: automatic dead band control