EasyTREK Compact Ultrasonic Level Transmitters
1.2 Current Output
P10:
Value (of distance, level, volume or flow) assigned to 4 mA current output
P11:
Value (of distance, level, volume or flow) assigned to 20 mA current output
Values are interpreted according to
P01(a)
. Please note that in case of programming for (LEV or VOL) % measurement the min and max value
has to be entered in the relevant engineering units of LEV (m, ft) or VOL (m
3
, ft
3
).
Assignment can be made so that the proportion between the change of the (measured or calculated) process value and the change of the current
output be either direct or inverse. E.g. lev 1m assigned to 4mA and lev 10m assigned to 20mA represents direct proportion and lev 1m assigned
to 20mA and lev 10 m assigned to 4mA represents the inverse proportion.
FACTORY DEFAULT:
P10 (4mA); 0
P11 (20mA)
P12: - - - a
Error indication by the current output
In case of error the EasyTREK will provide one of the current outputs below. (For errors and their indications see Chapter 7).
a
Error indication (according to NAMUR)
0
Hold last value
1
3.6 mA
2
22 mA
FACTORY DEFAULT: 0