EasyTREK Compact Ultrasonic Level Transmitters
11
P23: - - - a
Angle of repose (repose formation) Will not be used
P24: - - - a
Target tracking speed
a
Tracking speed
Remark
0
Standard
For most applications
1
Fast
For fast changing level
2
Special
Only for special applications
(measuring range is reduced to 50% of the nominal value)
The measuring window (P25) is inactive and the EasyTREK will respond practically instantly to any
target. Recommended to fast target tracking, but usually not applicable for level metering.
FACTORY DEFAULT: 0
P25: - - - a
Selection of Echo within the measuring window
A so-called measuring window is formed around the echo signal. The position of this measuring window determines the flight time for calculation
of the distance of the target. (the picture below can be seen on the test oscilloscope)
Received
signal
amplitude
Echo 1.
t
"t" ultrasound flight time
Echo 2.
Some applications involve multiple ( disturbing) echoes even within the measuring window. Basic echo selection will be done by the
Quest + software automatically. This parameter only influences the echo selection within the measuring window.
a
Echo in the window to be selected
Remark
0
With the highest amplitude
For most applications (both with liquids)
1
First one
For liquids applications with multiple echoes within the Measuring Window
2
Largest one
Recommended if multiple echoes within the Measuring Window
FACTORY DEFAULT: 0