background image

Technical Manual: ST-PY-AS - 000026  (Changes are subject to DCRN)

The maintenance procedures described below should be conducted

with the following frequency:

One month after installation:

Routine Inspection and every 3 

months after.

Every 6 months:

Operational Test.

Every 12 months:

Functional Test and Cleaning.

All above frequencies of maintenance are dependent on ambient

conditions.

Routine Inspection

i) Ensure the sensor head is secure and undamaged.

ii)Check the smoke entry apertures are in no way obstructed.

iii)Ensure that the surface of the sensor's outer cover is clean. If 

there are deposits due to the presence of oil vapour, dust etc, then

the sensor should be cleaned in accordance with the cleaning

instructions detailed later in this manual. It may be advisable to

ensure that such cleaning is conducted regularly in future.

iv)Ensure that no equipment which may generate excessive heat has

been installed in the vicinity of the sensor since the last routine

inspection. If such equipment has been installed, then you should

notify the Fire Safety Officer or other competent authority that its

presence may cause false alarms.

v) Ensure no equipment which may generate combustion products or

fine airborne particles has been installed in the vicinity of the

sensor since the last routine inspection. If such equipment has been

installed, then you should notify the Fire Safety Officer or other

competent authority that its presence may cause false alarms.

 

Ref No:

NISM/STPYAS/02    

Date:

16.04.09     

Issue:

2

• sensortec   • ST-PY-AS

• analogue addressable photoelectric sensor

instruction manual

sensortec

sensortec

4

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Sensortec ST-PY-AS

Страница 1: ...sortec sensortec ST PY AS analogue addressable photoelectric sensor instruction manual Quality System Certificate No 041 Assessed to BS EN ISO 9001 2000 www acornfiresecurity com www acornfiresecurity com ...

Страница 2: ...the sensor goes into alarm condition suitable for the operation of an auxiliary function such as a remote indicator Terminal 3 RIL is limited to 2mA Section 3 BASE MODELS A variety of bases are available for use with the ST PY AS sensor It is important to use the correct base for each application The available base models are i UB 4 base for standard use with ST PY AS series sensor ii STB 4SE base...

Страница 3: ...ioned If the dust cover is not fitted and the environment is slightly dusty such as when building work is being completed for example problems of false alarms are likely to occur after commissioning unless cleaning of the sensor is undertaken At commissioning the dust cover should be removed and discarded NOTE THE PLASTIC DUST COVER MUST BE REMOVED FROM THE SENSOR IN ORDER FOR THE SENSOR TO FUNCTI...

Страница 4: ...later in this manual It may be advisable to ensure that such cleaning is conducted regularly in future iv Ensure that no equipment which may generate excessive heat has been installed in the vicinity of the sensor since the last routine inspection If such equipment has been installed then you should notify the Fire Safety Officer or other competent authority that its presence may cause false alarm...

Страница 5: ...disperse iv Before proceeding to the next sensor ensure that the sensor just tested does not re operate due to the presence of residual smoke Functional Tests The functional test checks the sensors operation These detectors may be returned to our factory for Functional Testing Cleaning Note The sensor head should NOT be disassembled i Carefully remove the sensor from its base ii Use a soft lint fr...

Страница 6: ...tion 8 EMC Installation The installation shall be in accordance with the regulations either of the approval body for an approved system or otherwise to the national code of practice regulations for the installation of the fire alarm system e g BS 5839 part 1 Electromagnetic Compatibility EMC On a site where there is an unusually high level of potential electrical interference e g where heavy curre...

Страница 7: ...OWN Button 7 A Single press increments or decrements by 1 holding the button down speeds up the increment or decrement change 8 Select the desired address and press Set 9 LCD displays WAIT then new address Type and OK and beeps 10 Remove detector and repeat from step 3 11 If no keys are pressed for 1 minute the programmer will power down into a power saving mode LCD goes blank It will be necessary...

Страница 8: ...ortec 8 If ve supply derived from loop RIL must be LED type UB 4 STB 4SE Bases RIL must be 6v 2mA max Auxiliary terminal RIL current limited to 2mA If the ve supply for the auxiliary equipment is taken from the loop care must be taken to not cause corruption of the data protocol by excessive current draw 15mm 33mm Ø104m 27 mm 43 mm 20 mm 41 mm 4 5 mm 9 mm 2 8 x 6 mm GRUB SCREW 15 mm 104 5 mm www a...

Страница 9: ...on about where you can drop off your waste equipment for recycling please contact your local city office or your household waste disposal service Section 13 ROHS COMPLIANCE STATEMENT RoHS compliant and lead free This product complies with the RoHS Restriction of Hazardous Substances directive This product complies with the RoHS Restriction of Hazardous Substances directive which restricts the use ...

Отзывы: