DW1500110  Rev.K1 

Sep  18  2015 

15

 

Section 9 

 SPECIFICATIONS 

 

Detector Type 

Photoelectric smoke detector 

LED Visual Indicator 

Alarm - Solid red LED 

Operating Voltage Range 

12VDC to 32VDC peak 

System Voltage 

24VDC 

Stand-by current 

30

μA

. ave. at 24VDC 

Alarm Current 

68mA. max.   
47.5mA at 24VDC 

Voltage Ripple 

20% maximum 

Sensitivity 

1.78 %/Ft. to 3.60 %/Ft. 

Alarm Characteristics 

6VDC in series with 375R between   

+ (Terminal 3) and 

 (Terminal 1, 6) at 25°C 

UL Ambient Installation Temperature 

0 °C to +49 °C (32 °F to 120 °F) 

Operating Temperature 

-10 °C to +55 °C (14 °F to 131 °F) 

Storage Temperature 

-20 °C to +60 °C (-4 °F to 140 °F) 

Relative Humidity 

 RH95% non-condensing 

Maximum Quantity per Module 

20 units 

Start-up Time 

20 seconds 

Standard 

UL 268 

Weight 

118g (Detector head only) 

 

FOR WARRANTY SERVICE, RETURN TO: 

OVERSEAS BUSINESS DIVISION 

NITTAN COMPANY, LIMITED 

1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO, 151-8535, JAPAN 

http://www.nittan.com 

 

 

 

Содержание EVCA-P

Страница 1: ...ow the requirements for the installation of the products in accordance with the Specifications Otherwise it may cause malfunction Note Do not install the product in any location where oil dust iron po...

Страница 2: ...nsect screen therefore reducing the ingress of insects and airborne contaminants The chamber is designed so that the light emitted by the LED is not directed to the photodiode The LED pulses every 8 s...

Страница 3: ...imension of EVCA P Section 4 TERMINALS The EVCA P smoke detector has three terminal connections and the terminals are configured as follows Terminal Description 1 Zone negative in 3 Zone positive in o...

Страница 4: ...please consider the following items Otherwise the detector might not provide optimum performance Indoor use only Place the detector away from a ventilation fan or the air outlet of air conditioner at...

Страница 5: ...nals a dirty sensor trouble to the control panel when it reaches the preset limit The dirty sensor trouble indicates the detector is in need of servicing 6 2 2 Spacing of Smoke Detectors The recommend...

Страница 6: ...ing as shown in Figure 2 Figure 2 Smoke detector layout accounting for stratification 6 2 4 Partitions It is recommended that the distance between smoke detectors should not exceed a nominal spacing o...

Страница 7: ...the bottom of the joists Figure 3 Smoke detector spacing solid joist construction side view Figure 4 Smoke detector spacing solid joist construction plan view Note Joists less than 10 cm 4 in deep ar...

Страница 8: ...W H is greater than 0 4 Smoke detectors shall be located on the bottom of each beam if either the ratio of beam depth D to ceiling height H D H is less than 0 1 or the ratio of beam spacing W to ceili...

Страница 9: ...nd of the ceiling Additional detectors if required must be located based on the horizontal projection of the ceiling and the type of ceiling construction For a ceiling slope of less than 30 degrees al...

Страница 10: ...g sure the wiring does not obstruct mounting of the detector head Push the detector into the mounting base while turning it clockwise until the detector locks into place Use a small hexagonal wrench t...

Страница 11: ...th is 1km Refer to the instruction manual of EVA ZMU SCI Zone Module for connection to NFU 7000 series Use cable AWG12 20 for wiring Do not connect different gauge cables at one terminal in order to p...

Страница 12: ...15 12 Figure 10 Correct and incorrect wiring method For system monitoring For terminals 1 and 6 do not use looped wire under terminals Break wire run to provide monitoring of connections CAUTION Corre...

Страница 13: ...control panel must be set to One Man Walk Test mode prior to the test Sensors offer maximum performance when tested and maintained in compliance with NFPA 72 The sensor may be tested in the following...

Страница 14: ...of residual aerosol Section 8 MAINTENANCE Notes Before cleaning notify the proper authorities that the system is undergoing maintenance and therefore the system will temporarily be out of service Dis...

Страница 15: ...rm Characteristics 6VDC in series with 375R between Terminal 3 and Terminal 1 6 at 25 C UL Ambient Installation Temperature 0 C to 49 C 32 F to 120 F Operating Temperature 10 C to 55 C 14 F to 131 F S...

Страница 16: ...e this had been paid And the warranty period is three 3 years from the shipment from Nittan s factory 9 3 Notwithstanding anything to the contrary in this warranty terms Nittan shall not be liable to...

Отзывы: