DW1401831 Rev.K1
Sep 18, 2015
25
Annex A
Quick Instruction of EVA-AD2
This quick instruction of EVA-AD2 is prepared to EVA-PYH
. Please refer to “EVA
-AD2 programmer
instruction manual (DW1401870 Rev.K1)” for details.
Preparation
1. EVA-AD2 requires two 9v PP3 batteries.
a) Before inserting the batteries, confirm the EVA-AD2 is switched off and check polarity of battery, or
damage could result.
Indicate current address
1. Turn the power switch ON.
a)
For one second, all LED’s are lit and the
buzzer sounds.
2. Push the detector into the base on the EVA-AD2 while turning it clockwise until the detector locks into
place.
Figure A.1: Mounting a detector on EVA-AD2
3. Press the [Search] Key
a) Buzzer sounds, then the EVA-AD2 starts transmitting to the detector.
b) Do not remove the detector when transmitting, or damage could result.
4. The 7 segment LED reads [Customer code], [Type of device], [Address] in turn.
a)
The buzzer sounds, ERROR LED lights and the 7 segment LED display’s an ERROR CODE when
an unsupported or defective device is connected.
0.1 0
→
1 2.3
→
0 0 3.
↑
↑
↑
Customer code
Type of device
Address
【
Note - Dot position
】
The 7 segment LED distinguishes the Customer Code, Type and Address by the dot position in the
LED.
The information displayed by the 7 segment LED cycles every second and stops whilst displaying
the [address] at the end of the second cycle.
Type of device is assigned to the detectors as below.
EVA-PYH:
153
1
10
100
ADDRESS
ERR
OK
Set
Address
+1
+10
+100
Power
Search
Address
Address
Programmer
EVA-AD2