Installation Leaflet EV-SCM Issue 1

EV-SCM

Installation Leaflet EV-SCM Issue 1

Fig. 1 EV-SCM Sounder Notification Module

© 2009 Nittan UK

© 2009 Nittan UK

INTRODUCTION

The 

EV-SCM

Sounder Control Module is designed to

provide an output, in response to a command

signalled from a controller, to activate a number of

polarised and suppressed sounders. The sounders

are powered from an independent power supply

and the module is capable of passing up to a

maximum of 2A.

FEATURES

Use an EN54 approved PSU, to supply the source

power for EV-SCM dc applications:

EV-SCM

can switch up to 2A

EV-SCM

supervises power supply.

EV-SCM

monitors the wiring to signalling

devices and will not switch on (even if                 

commanded to do so), if a short circuit occurs.

This prevents a single short circuit condition

from disabling more than the output that

contains the short-circuit.

An LED reports 

EV-SCM

status to the user. The 

LED lights when the 

EV-SCM

has been commanded 

to activate.

TECHNICAL SPECIFICATION

Type Identification Value:

      65

System Compatibility: 

            Use only with Evolution 

                                            Fire Alarm Panels which 

                                            support this product

Environment:

                           Indoor Application only

Operating Temperature:

        -25ºC to +70ºC

Storage Temperature:

            -40ºC to +80ºC

Operating Humidity:

              Up to 95%

                                            non-condensing

Dimensions (HWD): 

                87 x 148 x 14mm

Mounting Requirements: 

       One MK backbox

                                            surface mount 

Wire Size: 

                                 Min 1.5mm

2

                                            Max 2.5mm

2

Battery Requirements:

Standby current:                  0.75mA max

Alarm current:                     4.5mA max

Addressable Device Conditions:

• Normal

• Short Circuit wiring fault

• Open Circuit wiring fault

• Input Power fault

• Device Type invalid

• Device No Response

Notification Circuit:

Max. Circuit Voltage Drop: 3.0V dc

Notification Circuit EOL:     27k ohms, 0.5 watt

Output Current:                  2A max @ 24V dc

ELECTROMAGNETIC COMPATIBILITY

The EV-SCM complies with the following:

Product family standard EN50130-4 in respect of

Conducted Disturbances, Radiated Immunity,

Electrostatic Discharge, Fast Transients and 

Slow High Energy

EN50081-1 for Emissions

Fig. 4 Simplified Wiring Diagram

showing Sounders wired in

a Spur Configuration

CIE

www.acornfiresecurity.com

www.acornfiresecurity.com