WIRING NOTES

The following notes apply:

1)

There are no user-required settings (such as

switches or headers) on 

EV-SCM

.

2)

All wiring must conform to the current edition

of IEE Wiring Regulations and BS5839 part 1.

3)

All conductors to be free of earths.

4)

All Notification appliances must be polarised

and suppressed.

5)

Verify the correct polarity of wiring before

connecting the 

EV-SCM

to the addressable

loop circuit.

6)

For 

EV-SCM

typical wiring configurations

(see Figures 4 and 5).

© 2009 Nittan UK

© 2009 Nittan UK

ADDRESS SETTINGS

 

The 

EV-SCM

must be set to the loop address of the

device using the EV-AD2 Address Programing Tool.

The EV-SCM may be programmed with the address

prior to being installed by using the internal

programming port (see Fig. 2) or after being installed

by using the programming port on the front cover

(see Fig. 3).

Note:

Once the address has been programmed, take

note of the device location and address               

number, to include on site drawings.

CABLING

Cables are to be selected in accordance with the

requirements of the current issue of BS5839. A

maximum of one 1.5m

2

or one 2.5m

2

cable may be

connected at any one terminal.

CABLING

The module fits onto a standard dual-gang MK box.

The module may drive a 

EV-SBM

Sounder Booster

Module.