background image

Manual: EV-DPH Manual 000027  (Changes are subject to DCRN)

Section 10 - CONNECTIONS

9

CIE

+ve Line Out

-ve Line Out

+ve Line In

-ve Line In

RIL

+ve Line Out

-ve Line Out

UB-4-EV Base

STB-4SE-EV

-ve Line In

6

3

2

1

6

3

2

1

+ve Line In

• Ref No: NISM/EV-DPH/01 •  May 2010 •  Issue: 1

•  Evolution  •  EV-DPH  •  analogue addressable 

photoelectric / heat sensor 

Auxiliary terminal RIL current limited to 3mA. Base control is not current

limited as the auxiliary equipment provides the limiting.  If the +ve supply for

the auxiliary equipment is taken from the 

EV

loop, care must be taken to not

cause corruption of the EV protocol by excessive current draw.

Section 11 - DIMENSIONS

27 mm

43 mm

20 mm

41 mm

4.5 mm

9 mm

2.8 x 

6

 mm

G

RUB 

SC

REW

15 mm

104.5 mm

15mm

33mm

104mm

Содержание EV-DPH

Страница 1: ...www nittan co uk E mail sales nittan co uk EV DPH Analogue Addressable Dual Wavelength Photoelectric Heat Sensor instruction manual Quality System Certificate No 041 Assessed to BS EN ISO 9001 2008 R...

Страница 2: ...analogue addressable fire sensors from Nittan UK Ltd called evolution The EV DPH together with the EV PH EV H EV P are all elegantly designed low profile fire sensors which are aesthetically pleasing...

Страница 3: ...LEDs and supporting a uniform response in any EN 54 Test Fire Resistance to false alarms caused by steam A2R or CS Grade heat detectors EEPROM addressable hand held programmer Low profile stylish appe...

Страница 4: ...plastic dust cover supplied over the sensor to keep out dust etc until the system is commissioned If the dust cover is not fitted and the environment is slightly dusty such as when building work is b...

Страница 5: ...s manual It may be advisable to ensure that such cleaning is conducted regularly in the future iv Ensure no equipment which may generate combustion products has been installed in the vicinity of the d...

Страница 6: ...g to the next sensor ensure that the sensor previously tested does not re operate due to the presence of residual smoke Functional Tests The functional test checks the sensor operation These sensors m...

Страница 7: ...certificate TBA Section 7 ENVIRONMENTAL PARAMETERS Temperature Considerations Over the range from 10 C to 55 C Humidity Relative Humidity of up to 95 measured at 50 C non condensing Section 8 EMC Inst...

Страница 8: ...or another detector change the detector and then repeat from step 3 To finish changing addresses turn the POWER SW off 1 Stand by mode EV AD2 will switch to STAND BY MODE to save battery power if ther...

Страница 9: ...olution EV DPH analogue addressable photoelectric heat sensor Auxiliary terminal RIL current limited to 3mA Base control is not current limited as the auxiliary equipment provides the limiting If the...

Страница 10: ...that protects human health and the environment For more information about where you can drop off your waste equipment for recycling please contact your local city office or your household waste dispo...

Отзывы: