Section 6 - SPECIFICATIONS

Model Reference:

- EV-DP

Computer Reference:

- F14N82105

Sensor Type:

- Dual wavelength  

photoelectric smoke
sensor

Sensitivity:

- Uniform response in all

EN-54 Fire Tests

Operating Current:

- 200 microamps

fire alarm (LED on)
5.2mA

Standard:

- EN54 Part 7:2001

Mass:

- 118g (excluding base)

Charging Time:

- 20 seconds

Ambient Temperature
Range:

- -10 ºC to +55 ºC

IP Rating:

- 41

Certified to standard:
CE certificate:

- 0832-CPD-0219

LPCB certificate:

- 041f/02

Section 7 - ENVIRONMENTAL

PARAMETERS

Temperature Considerations:

Over the range from -10 ºC to +55 ºC

Humidity:

Relative Humidity of up to 95%, measured at 50 ºC,
non condensing.

Section 8 - EMC

Installation

The installation shall be in accordance with the regulations either of
the approval body for an approved system, or otherwise, to the
national code of practice/ regulations for the installation of the fire
alarm system, e.g. BS 5839 part 1.

Electromagnetic Compatibility (EMC)

On a site where there is an unusually high level of potential electrical
interference, e.g. where heavy currents are being switched or where
high levels of R.F. are prevalent, care then must be taken in the type
and routing of cables.  Particular care should be given to the
separation of zone wiring from the cable carrying the interference.

7

• Ref No: NISM/EV-DP/03  • Date: 16.04.09  •  Issue: 3

•  Evolution  • EV-DP •  analogue addressable photoelectric sensor 

instruction manual

Содержание EV-DP

Страница 1: ...e www nittan co uk E mail sales nittan co uk Ref No NISM EV DP 03 Date 16 04 09 Issue 3 Evolution EV DP Dual Wavelength photoelectric sensor instruction manual EV DP Analogue Addressable Dual Waveleng...

Страница 2: ...EV UV are all elegantly designed low profile fire sensors which are aesthetically pleasing thus enabling them to blend unobtrusively into modern working environments The evolution analogue addressable...

Страница 3: ...ng terminals provide a switched current sink function which operates when the detector goes into alarm condition suitable for the operation of an auxiliary function such as a remote indicator Terminal...

Страница 4: ...ss must be set before the sensor is fitted into place Fit the plastic dust cover supplied over the sensor to keep out dust etc until the system is commissioned If the dust cover is not fitted and the...

Страница 5: ...l It may be advisable to ensure that such cleaning is conducted regularly in the future iv Ensure no equipment which may generate combustion products has been installed in the vicinity of the detector...

Страница 6: ...proceeding to the next sensor ensure that the sensor previously tested does not re operate due to the presence of residual smoke Functional Tests The functional test checks the sensor operation These...

Страница 7: ...ve Humidity of up to 95 measured at 50 C non condensing Section 8 EMC Installation The installation shall be in accordance with the regulations either of the approval body for an approved system or ot...

Страница 8: ...ncrement the address to be programmed by one 1 and prompt for the next sensor to be fitted If no detector is fitted the programmer will report No Unit Found Comm Error 1 Fit a new sensor and press OK...

Страница 9: ...olution EV DP analogue addressable photoelectric sensor instruction manual Auxiliary terminal RIL current limited to 3mA Base control is not current limited as the auxiliary equipment provides the lim...

Страница 10: ...ct your local city office or your household waste disposal service Section 13 ROHS COMPLIANCE STATEMENT RoHS compliant and lead free This product complies with the RoHS Restriction of Hazardous Substa...

Отзывы: