Section 9 - ADDRESS SETTING 

(EV-AD)

• Insert sensor to be programmed into the base.

• Press any key on the keypad to bring the programmer 

out of ‘Sleep’ mode, then enter the password
(default is 4466), then press ‘OK’.

• The menu now shows ‘Enter’ (selected) and 

'New.Pwd.' Use the Right Arrow button (6) to change 
the selected operation then press ‘OK’.

• If 'New.Pwd' is selected then entry of a new password,

followed by confirmation of the new password will
be prompted.

• If the current password is not to be changed, press 

‘OK’ with ‘Enter’ selected.  The address programmer 
will then scan for the attached sensor.

• If a sensor is fitted the programmer will report the 

sensor’s current address and its group, then prompt
for the next address to be programmed.  The current 
address can be changed by simply entering a new 3
digit address, then pressing ‘OK’.

• Once the sensor address has been programmed, the 

programmer will automatically increment the address 
to be programmed by one (1), and prompt for the 
next sensor to be fitted.

• If no detector is fitted, the programmer will report 

'No Unit Found, Comm Error 1'. Fit a new sensor and 
press ‘OK’.

• At any time there has been no key pressed for 30 

seconds, or no programming operation is being 
carried out, the backlight will switch OFF and the 
programmer will revert to its ‘Sleep’ mode in order to 
preserve battery life.

• The programmer has an automatic 'Low Battery' 

warning, which will appear on the LCD when the unit 
powers up.  When this appears there is still sufficient 
charge left in the batteries to program a significant 
number of Evolution devices, however the 
programmer should be recharged as soon as possible.

• The batteries should be removed from the 

Programmer battery compartment, and placed in a 
stand-alone external charger , which is suitable for 
charging NiMh batteries.
Follow charging instructions supplied with the 
external charger unit.
Do not overcharge the batteries since this will shorten 
their working life.

8

• Ref No: NISM/EV-DP/03  • Date: 16.04.09  •  Issue: 3

•  Evolution  • EV-DP •  analogue addressable photoelectric sensor 

instruction manual

Содержание EV-DP

Страница 1: ...e www nittan co uk E mail sales nittan co uk Ref No NISM EV DP 03 Date 16 04 09 Issue 3 Evolution EV DP Dual Wavelength photoelectric sensor instruction manual EV DP Analogue Addressable Dual Waveleng...

Страница 2: ...EV UV are all elegantly designed low profile fire sensors which are aesthetically pleasing thus enabling them to blend unobtrusively into modern working environments The evolution analogue addressable...

Страница 3: ...ng terminals provide a switched current sink function which operates when the detector goes into alarm condition suitable for the operation of an auxiliary function such as a remote indicator Terminal...

Страница 4: ...ss must be set before the sensor is fitted into place Fit the plastic dust cover supplied over the sensor to keep out dust etc until the system is commissioned If the dust cover is not fitted and the...

Страница 5: ...l It may be advisable to ensure that such cleaning is conducted regularly in the future iv Ensure no equipment which may generate combustion products has been installed in the vicinity of the detector...

Страница 6: ...proceeding to the next sensor ensure that the sensor previously tested does not re operate due to the presence of residual smoke Functional Tests The functional test checks the sensor operation These...

Страница 7: ...ve Humidity of up to 95 measured at 50 C non condensing Section 8 EMC Installation The installation shall be in accordance with the regulations either of the approval body for an approved system or ot...

Страница 8: ...ncrement the address to be programmed by one 1 and prompt for the next sensor to be fitted If no detector is fitted the programmer will report No Unit Found Comm Error 1 Fit a new sensor and press OK...

Страница 9: ...olution EV DP analogue addressable photoelectric sensor instruction manual Auxiliary terminal RIL current limited to 3mA Base control is not current limited as the auxiliary equipment provides the lim...

Страница 10: ...ct your local city office or your household waste disposal service Section 13 ROHS COMPLIANCE STATEMENT RoHS compliant and lead free This product complies with the RoHS Restriction of Hazardous Substa...

Отзывы: