Defrost Cycle (Low Temperature Models)
The evaporator fin coil is defrosted by an electric defrost heater located on the underside of the coil.
The defrost cycle is initiated and terminated by the controller fitted on the electrical box. This control
not only terminates the defrost cycle, but delays the fan start-up after the defrost cycle to prevent the
residual heat of heater from being blown into the product area.
5. START UP / OPERATION
5.1 Electrical Supply
WARNING: Equipment MUST be GROUNDED!
Wiring of the unit is complete when it is shipped from the factory. The unit is supplied with a three
conductor electrical cord which extends from the rear of cabinet. Plug the cabinet into correct
grounded outlet. It is recommended that a separate circuit be run for each cabinet to prevent the
possibility of another appliance blowing a fuse, causing subsequent loss of product.
Control setting, please see the appendices at the last page. The pre-set parameters in factory as
below:
5.2 Controller parameter
No. Parameter
unit
R2DH2080-01 F2DH2080-01
Value
Value
1
Set
℉
33
-2.2
2
Hy
℉
4
4