5. Setup and Stop

4.4 System Installation Requirement

Figure 4.15 is a simple guidance for installing a solar system with PV inverter. A DC isolator 

is required to be installed in the system between the PV panels and the inverter.

Figure 4.15 Guidance for a Simple Installation of an Inverter Solar Energy System

4.5 Grounding

Solis-2.5K-2G must be earthed securely. Inside the inverter, the earth wire is in yellow and green. 

When the inverter is connected to the grid through the AC grid terminal connector, the earth 

wire will be connected to the Earth and hence ensure safety.

5.1 Starting the Inverter

To start up Solis-2.5K-2G, it is important that the following steps are strictly adhered to:

1. Switch the Solar Supply Main Switch (AC) ON first.

2. Switch the solar panel DC Isolator ON. If the solar panels provide normal power 

    supply, Solis-2.5K-2G will turn on ( the red light displays and the LCD show the model name of 

the inverter ).

Solis-2.5K-2G

Figure 5.1 Company Name and Model Name on LCD

3. When both the DC side and AC grid side of Solis-2.5K-2G have power presented, the inverter 

    will prepare to generate. Initially, Solis-2.5K-2G will check both its internal parameters and 

    the parameters of the AC grid to ensure that they are within the acceptable limits. At 

    this time, the green light will flash and the LCD displays the information of INITIALIZING.

4. After 3 mins, Solis-2.5K-2G will generate electricity normally. The green light will remain 

    on and the LCD displays GENERATING.

WARNING: 

Do not touch the heat sink when the inverter is operating. Some parts may be 
hot and cause burns.

!

5.2 Stopping the Inverter

To stop Solis-2.5K-2G, the following steps must be strictly followed:

1. Switch the Solar Supply Main Switch (AC) OFF. 

2. Wait 30 seconds. Switch the solar panel DC Isolator OFF. All the LEDs of the inverter will 

    be off in a minute.

Isolation switch

Solar supply 

main switch

Consumers

mains

(to grid)

Main

switch

MAIN SWITCHBOARD

Circuits not

protected by

RCDs

Circuits Protected

by RCDs

Isolation device

Inverter with

integral grid

Protection device

Solar

(PV)

array

1

1

2

NOTE: 
1. The RCD should not be placed between the consumers mains and the solar 
    supply.
2. More than one RCD may be used. Each RCD can protect one or more 
    circuits.

.15.

.16.

4. Installation

Содержание Solis-2.5K-2G

Страница 1: ...P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 Email info ginlong com Web www ginlong com Please record the serial number of your inverter and quote this when you contact us Solar PV Grid Tie...

Страница 2: ...up and Stop 5 1 Starting the Inverter 5 2 Stopping the Inverter 6 Operation 6 1 Main Menu 6 2 Information 6 3 Settings 6 3 1 Setting Time 6 3 2 Setting Address 6 3 3 Clearing Energy 6 3 4 Restoring Se...

Страница 3: ...ndicates important safety instructions which if not correctly followed could result in electric shock causing serious injury or death CAUTION CAUTION HOT SURFACE symbol indicates safety instructions w...

Страница 4: ...chnician only Warranty may be void if unauthorized removal of cover CAUTION Solis 2 5K 2G has a heat sink on its top surface which helps in cooling down the internal components The heat sink can reach...

Страница 5: ...ed supplying power The inverter is initializing Alarm or fault condition is detected The inverter stores the last 10 messages The inverter is operating properly Status ON OFF ON OFF OFF ON FLASHING Li...

Страница 6: ...ical position as shown in Figure 4 1 The steps to mount the inverter to the wall are given as follows WARNING 9 10 NOTE Nothing should be stored on or placed against the inverter NOTE Heat sink must b...

Страница 7: ...or coat see Figure 4 5 ii Insert the wire into the bottom part of the connector coat as shown in Figure 4 6 Figure 4 5 Disassemble the Connector Cap Figure 4 6 Insert the Wire into the Connector Cap i...

Страница 8: ...tor as shown in Figure 4 12 b Put the terminal cap on the terminal as shown in Figure 4 13 Figure 4 12 Connect Wires to the Grid Terminal Figure 4 13 Put the Cap on the Terminal c Connect the AC grid...

Страница 9: ...side of Solis 2 5K 2G have power presented the inverter will prepare to generate Initially Solis 2 5K 2G will check both its internal parameters and the parameters of the AC grid to ensure that they a...

Страница 10: ...gs 6 2 Information The Solis 2 5K 2G main menu provides access to operational data and information The information is displayed by selecting Information from the menu and then by scrolling up or down...

Страница 11: ...ss the ESC key to cancel the change and return to the previous menu 6 3 3 Clearing Energy This function is used to clear energy total energy this month energy and last month energy When Clear Energy i...

Страница 12: ...ersion The screen shows the model version and the software version of Solis 2 5K 2G see Figure 6 12 Model 07 Software Version 8E06 Figure 6 12 Model Version and Software Version 6 4 5 Communication Da...

Страница 13: ...ms Press the ENTER key to edit the highlighted item Press the UP DOWN keys again to change the setting Press the ENTER key to save the setting Press the ESC key to cancel the change and return to the...

Страница 14: ...able 8 1 turn off your inverter refer to Section 5 2 to stop your inverter and wait for 30 minutes before restarting it refer to Section 5 1 to start your inverter If the failure has not been cleared...

Страница 15: ...c injection current Rating grid frequency Ef ciency Protection Size Weight Topology Internal consumption Running temperature Ingress protection Interface Design lifetime 2 5kW 2 8kW 230Vac 180 270Vac...

Отзывы: