4.3 Electrical Connections

      Solis-2.5K-2G can transfer the power available to the utility at any input DC voltage that is 

within the range from 100Vdc to 500Vdc. The maximum input current is 10Adc. The rated 

output voltage of Solis-2.5K-2G is 230Vac or 240Vac.

The electrical connection of the inverter must follow the steps listed below:

1. Switch the Solar Supply Main Switch (AC) OFF.

2. Switch the solar panel DC Isolator OFF.

3. Connect Solis-2.5K-2G to the solar panel DC Isolator. 

a) Make sure the polarity of the output voltage from the solar panel (i.e. the input voltage

     for Solis-2.5K-2G) matches the 

DC+

and

DC-

symbols.

b) Attach the positive DC connector (refer to Figure 4.3) to the solar panel output positive 

    terminal. Attach the negative DC connector (refer to Figure 4.4) to the solar panel 

    output negative terminal.

Figure 4.3 DC+ Connector

Figure 4.4 DC- Connector

The steps to assemble the DC connectors are listed as follows:

    i) Disassemble the connector coat (see Figure 4.5).

    ii) Insert the wire into the bottom part of the connector coat as shown in Figure 4.6.

Figure 4.5 Disassemble the Connector Cap

Figure 4.6 Insert the Wire into the Connector Cap

    ii) Attach the pin top to the wire as shown in Figure 4.7.

i

Figure 4.7 Attach the Pin Top to the wire

iv

     on the bottom part of the connector (as shown in Figure 4.8).

) Insert the pin to the top part of the connector and screw the top part back 

Figure 4.8 Connector with Cap Screwed on

.11.

.12.

4. Installation

4. Installation

        Solis-2.5K-2G is designed for electrical connection without removing the cover. The 

meaning of the symbols located at the bottom of the inverter are listed in Table 4.1.

All electrical installations must be in accordance with all local and national electrical

codes.

Table 4.1 Terminals

+

-

 Positive terminals of  DC input

Negative terminals of DC input

DC 1

DC 1 input terminals positive or negative  

DC 2

DC 2 input terminals positive or negative  

DC SWITCH

Switch of DC input terminals(optional) 

COM

Equipment communication connect terminal

Rs485 communication connect terminal(optional)

RS 485

GRID

Equipment grid wires connect terminal

Содержание Solis-2.5K-2G

Страница 1: ...P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 Email info ginlong com Web www ginlong com Please record the serial number of your inverter and quote this when you contact us Solar PV Grid Tie...

Страница 2: ...up and Stop 5 1 Starting the Inverter 5 2 Stopping the Inverter 6 Operation 6 1 Main Menu 6 2 Information 6 3 Settings 6 3 1 Setting Time 6 3 2 Setting Address 6 3 3 Clearing Energy 6 3 4 Restoring Se...

Страница 3: ...ndicates important safety instructions which if not correctly followed could result in electric shock causing serious injury or death CAUTION CAUTION HOT SURFACE symbol indicates safety instructions w...

Страница 4: ...chnician only Warranty may be void if unauthorized removal of cover CAUTION Solis 2 5K 2G has a heat sink on its top surface which helps in cooling down the internal components The heat sink can reach...

Страница 5: ...ed supplying power The inverter is initializing Alarm or fault condition is detected The inverter stores the last 10 messages The inverter is operating properly Status ON OFF ON OFF OFF ON FLASHING Li...

Страница 6: ...ical position as shown in Figure 4 1 The steps to mount the inverter to the wall are given as follows WARNING 9 10 NOTE Nothing should be stored on or placed against the inverter NOTE Heat sink must b...

Страница 7: ...or coat see Figure 4 5 ii Insert the wire into the bottom part of the connector coat as shown in Figure 4 6 Figure 4 5 Disassemble the Connector Cap Figure 4 6 Insert the Wire into the Connector Cap i...

Страница 8: ...tor as shown in Figure 4 12 b Put the terminal cap on the terminal as shown in Figure 4 13 Figure 4 12 Connect Wires to the Grid Terminal Figure 4 13 Put the Cap on the Terminal c Connect the AC grid...

Страница 9: ...side of Solis 2 5K 2G have power presented the inverter will prepare to generate Initially Solis 2 5K 2G will check both its internal parameters and the parameters of the AC grid to ensure that they a...

Страница 10: ...gs 6 2 Information The Solis 2 5K 2G main menu provides access to operational data and information The information is displayed by selecting Information from the menu and then by scrolling up or down...

Страница 11: ...ss the ESC key to cancel the change and return to the previous menu 6 3 3 Clearing Energy This function is used to clear energy total energy this month energy and last month energy When Clear Energy i...

Страница 12: ...ersion The screen shows the model version and the software version of Solis 2 5K 2G see Figure 6 12 Model 07 Software Version 8E06 Figure 6 12 Model Version and Software Version 6 4 5 Communication Da...

Страница 13: ...ms Press the ENTER key to edit the highlighted item Press the UP DOWN keys again to change the setting Press the ENTER key to save the setting Press the ESC key to cancel the change and return to the...

Страница 14: ...able 8 1 turn off your inverter refer to Section 5 2 to stop your inverter and wait for 30 minutes before restarting it refer to Section 5 1 to start your inverter If the failure has not been cleared...

Страница 15: ...c injection current Rating grid frequency Ef ciency Protection Size Weight Topology Internal consumption Running temperature Ingress protection Interface Design lifetime 2 5kW 2 8kW 230Vac 180 270Vac...

Отзывы: