FORM NO. 56043058 Hydro-Retriever™ 3800 / 2042 / BR 1100 -
65
ELECTRICAL SYSTEM
SCROLL
DISPLAY
! “ # $ % & ‘ ( )
*
+ , - . /
0 1 2 3 4 5 6 7 8 9 : ; < = > ?
P QR ST U VWX Y Z x º
@A B C D E FG H I J K L M NO
MORE INFO
SPECIAL DIAGNOSTICS MODE
In the
Special Diagnostics
mode, the controller’s diagnostic history file is displayed. This file includes a list of all faults observed and recorded
by the controller since the history was last cleared. (
Note:
The maximum and minimum temperatures recorded by the controller are included in
the Test Menu). Each fault is listed in the diagnostic history file only once, regardless of the number of times it occurred.
OPERATING MODES (CONTINUED)
To access Special Diagnostics, first press the MORE INFO key. Then, while continuing
to hold the MORE INFO key, press the DIAGNOSTICS key. The LED on the DIAGNOS-
TICS key will light, just as when the programmer is in Diagnostics mode. The seat switch
must be open in order to access the diagnostic history file.
The MORE INFO key, when used within the Special Diagnostics mode, causes additional
information to be displayed about the selected item.
To clear the diagnostic history file, put the programmer into the Special Program mode, select “Clear Diagnostic History”, and press the MORE
INFO key for instructions. Clearing the diagnostic history file also resets the maximum/minimum temperatures in the Test Menu.
DIAGNOSTICS AND SPECIAL DIAGNOSTICS MENU
ANTI-TIEDOWN
Mode Select 1 switch closed at startup
CONT COIL/FLD SHORT
Contactor driver overcurrent or field winding short
CURRENT SHUNT FAULT
Current sensor error
EMR REV WIRING
Emerg. Reverse wiring check failed
FIELD OPEN
Motor field winding open
HPD
High-pedal disable (HPD) activated
HW FAILSAFE
Hardware failsafe activated
LOW BATTERY VOLTAGE
Battery voltage too low
M- SHORTED
M- shorted to B-
MAIN CONT WELDED
Welded main contactor
MISSING CONTACTOR
Missing contactor
NO KNOWN FAULTS
No known faults
OVERVOLTAGE
Battery voltage too high
SRO
Static return to off (SRO) activated
THERMAL CUTBACK
Cutback, due to over/under temp
THROTTLE FAULT 1
Throttle wiper input fault
THROTTLE FAULT 2
Throttle low input fault
PEACE-OF-MIND PROGRAMMING
Each time the programmer is connected to the controller, it acquires all the controller’s parameters and stores them in its temporary memory. You
can revert back to these original settings at any time during a programming session via the Special Program Menu. Select “Revert to Previous
Settings” by scrolling it to the top of the display window, press the MORE INFO key, and follow the instructions displayed. Any inadvertent changing
of parameters can be “undone” using this procedure, even if you can’t remember what the previous settings were,
as long as the programmer
has not been unplugged and power has not been removed from the controller
.
PROGRAMMER SELF TEST
You can test the programmer by displaying two
special test screens. Press the MORE INFO key
while the programmer is powering up. During the
Self-Test, you can toggle between the two test
screens by pressing the SCROLL DISPLAY keys
(Figure 9). The first screen turns on every LCD
element and the second screen displays all the
characters used in the various menus. As part of
the Self-Test, you can also test the keys by press-
ing each one and observing whether its corner
LED lights up. To exit the Self-Test, unplug the
programmer or turn off the controller, and then
repower it without holding the MORE INFO key.
FIGURE 9
DIAGNOSTICS
revised 12/02