0472-0008-01

2. Run reverse

Pressing the Function key will run the drive in the reverse direction, the start button will run the drive in the forward direction.

3. Jog

Pressing the Function key will jog the drive. As with the normal jog function the drive needs to be stopped for the jog function to operate. Giving 
the drive a start command when jogging will cause the motor to run at the speed reference selected in menu 1.

4.  Auto 

On power up of the SK-Keypad Remote, Stop (off) mode is assumed. The following modes are entered with the appropriate key press in each 
mode. 

The Function key LED flashes to indicate waiting for a user action in Stop (off) mode and Keypad (Hand) mode .
The Function key LED stays on when in Terminal (Auto) mode.
5. User defined function

In this mode no function is assigned to the Function key, this mode allows the user to define their own function. This would normally be done 
through a user program in a LogicStick using Pr 

6.11 

to monitor key presses (Pr

 6.11

 = state of Function key).

3      Panel mounting the SK-Keypad Remote

The SK-Keypad Remote is connected to the drive by a straight-through shielded RJ45 to RJ45 cable, from the socket on the rear of the keypad to the 
RJ45 serial communications connection on the drive. For EMC compliance the cable shield should be clamped to the panel upon which the SK-
Keypad Remote is mounted so that it makes a good electrical connection. The maximum cable length allowed is 30m (100ft).
More information on serial communications and RJ45 pin configuration is available in the drive Advanced User Guide.

Communications auto configuration

The SK-Keypad Remote will scan and identify the current drive communication settings on power-up and auto configures the drive to establish the 
communications link with '19200'-baud rate, leaving the drive to retain EEPROM stored parameter values.
To ensure the EEPROM communications parameters are correctly restored, the drive must be in status mode and powered down before the SK-
Keypad Remote is unplugged.

N

It is only possible to connect the SK-Keypad Remote to one drive at a time. 

Figure 3-1 shows the dimensions of the cut out required to mount the 
SK-Keypad Remote on a panel or cubicle door.

In order to meet IP65 rating:

The rubber ‘O’ ring must be fitted around the RJ45 connection.
The required screws and seal are provided in a bag with the SK-
Keypad Remote.

Figure 3-1 Panel cut-out

Figure 3-2 Rear of the SK-Keypad Remote and accessories

Stop Mode

(Off) - LED Flashes

Terminal Mode

(Auto) - LED On

Keypad Mode

(Hand) - LED Flashes

17.8mm

(0.70in)

10.9mm

(0.43in)

8.0mm

(0.32in)

17

.2

mm

(0

.6

8i

n)

15

.6

mm

(0

.61i

n)

41

.0

mm

(1

.6

4i

n)

37.6mm

(1.48in)

37.6mm

(1.48in)

3.5mm

(0.14in)

20mm

(0.79in)

6.8mm

(0.27in)

‘O’ ring seal

   R 45 
connector

J

Screws

Screw

Maximum screw torque of 0.8Nm

Only use the three M3 x 14 screws supplied

NOTE