Troubleshooting

Zero point Adjustment

Others

Press the  and  buttons.

Press the  button until 

all LED do not flashe.

Set the value to “F-3”

using the  and  

buttons.

Press the  button for 

more than one second to 

return to the Operations 

Mode.

■If the following error messages are displayed, follow the procedures in the table.

Display and problem

Cause

Solution

E-1

E-2

E-3

,

E-4

999

 Flashing

Flashing of the pressure value

Black out of the display

Disable the key operation

Output current is exceeding 100mA.

Turn off the power and verify the load 

connected switch output 1 and 2.
Press M button and return the applied pressure to the 

atmospheric pressure and try zero-point adjustment again.
Please contact us. Please use a regulated DC power 

supply and measures for the power line noise.

Normal state 

Normal state

Normal state(See Non-display mode.)

Normal state(See Key protection mode.)

Pressure was applied at the zero point 

adjustment.

Failure of the internal circuit.

Pressure values exceed the display range.
Pressure values exceed the rated pressure 

range.(110%FS)

Non-display mode

Key protection mode

If there is any possibility that the sensor may become wet with oil or water, which may 

enter the case through the air intake, connect a silicon tube, or similar, to the intake 

and position the end of the tube in a suitably safe place. Be sure not to bend the tube 

or block the end of the tube.

Note:20digits is set prior to delivery.

An example of setting a hysteresis value of 8.0kPa with the 102R(kPa).

Example of a tube with 

external diameter of φ4 

and internal diameter 

of  φ2.5

Hysteresis setting

Digital Filter setting

Tube at atmospheric pressure intake

To set hysteresis the

“−”

LED should be flashing. 

To set Digital Filter all LED should be not flashing. An example of setting 2.5s response time by Digital Filter.

Press the  and  buttons.

Press the  button until 

the −LED flashes.

Set the value to “8.0”

using the  and  

buttons.

Press the  button for 

more than one second to 

return to the Operations 

Mode.

Note:“F-0”is set prior to delivery.

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

Use a wrench on a hexagon of fitting part. Do not hold the main body when tightening.

Piping

Pressing     the     and buttons simultaneously in the Operations Mode 
displays   on the screen. One second later this change to     than 
the    and     buttons are released.(If the pressure port is opened to 
the atmosphere.)

Note:You have to adjust Zero under open air condition.

Otherwise you can be seen E‐2 error as you adjusted Zero with residual pressure.

Содержание PG-35L

Страница 1: ...s in the setting buttons and damage them Do not insert wires etc in the pressure port as this may damage the internal diaphragm and cause malfunctioning gasket type Do not touch or scratch the edge of...

Страница 2: ...ypes Materials at pressure receiving area Net Weight Accessories Negative pressure display Display accuracy IP protection Operating temperature Operating humidity Insulation resistance Dielectric stre...

Страница 3: ...de Pressure Settings Mode 1 1 2 0 0102 3 10 2 4 7 501 5 102 6 0 01 7 10 8 0 145 9 0 000145 A 0 001 b 0 2953 When the power is swiched on the Operations Mode is automatically selected Settings remain i...

Страница 4: ...tting SW2 or the hysteresis setting Set the value using the and buttons Press the button for more than one second to return to the Operations Mode Output Mode Operation 1 2 3 4 5 6 7 8 SW1 output Sepa...

Страница 5: ...me wet with oil or water which may enter the case through the air intake connect a silicon tube or similar to the intake and position the end of the tube in a suitably safe place Be sure not to bend t...

Страница 6: ...Mode kPa SW1 SW2 C O PA L E L E C T R O N I C S kPa SW1 SW2 C O PA L E L E C T R O N I C S kPa SW1 SW2 C O PA L E L E C T R O N I C S kPa SW1 SW2 C O PA L E L E C T R O N I C S To enable Non Display F...

Страница 7: ...ly Product name Model no Description Applicable model Holder cover set for protection of gauge sides Panel holder cover panel holder ACPG 004 PG 30 35 PG 35 Pressure ranges 102 100 to100kPa 103 100 to...

Отзывы: