The analog output setting is determined by the value of the second digit : 

the green SW1 LED should be flashing during the setting.

The switch output setting is determined by the value of the first digit :

 the red SW2 LED should be flashing during the setting.

There are four operation modes. These are shown in the diagrams below.

Note 1. In the Separate Mode, setting 1 corresponds to SW1, and Setting 2 corresponds to SW2.

Note 2. In the Window Comparator Mode, the minimum value for SW1 and SW2 corresponds to Setting 1 and the

     maximum value corresponds to Setting 2.

Value selected

Value selected

1
2
3

R mode(Compound pressure output)
G mode(Positive pressure output)
V mode (Negative pressure output)

Mode

−Pr           0           +Pr

(Vzero)

1V
1V

1V

5V

5V
5V

In the Operations Mode, press the
  and  buttons simultaneously to
enter the Initial Settings Mode.

Press the  button until the
SW1 LED under the second
digit flashes.

Set the value of the second
digit to “1” using the  and
  buttons.

An example of setting the R mode in the 102R range.

Notes:V mode for 102R are set prior to shipment.R/G mode for 103R can only be selected.

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

+/−

SW1

SW2

In the operations mode,  

press the   and   

buttons simultaneously 

to enter the Initial 

Settings Mode.

Press the   button

until the SW2 LED 

under the first digit 

flashes.

Set the value of the

first digit to“7” 

using the  

  and   buttons.

Press the   button 

for more than one 

second to return to 

the Operations Mode.

Press the   and   buttons

simultaneously to enter 

the Pressure Settings Mode. 

(The SW1 LED flashes.)

The LED of an item flashes 

when selected using the     button.

Press the   button to select

between switch output 1 setting

(SW1), switch output 2 setting

(SW2), or the hysteresis setting.

Set the value 

using the  

and     buttons.

Press the   button for

more than one second 

to return to the Operations

Mode.

Output

Mode

Operation

1
2
3
4
5
6
7
8

SW1 output

Separate

H


L


A


B


H

L

A

B

Window comparator

Note 1

Setting 1

Note 2

Minimum: Setting 1

Maximum: Setting  2

Minimum: Setting 1

Maximum: Setting  2

Note 1

Setting 2

Note 2

Separate Window comparator

SW2 output

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

■Window Comparator Mode

(An example of setting the value“7”

for the mode shown in the diagram.)

ON

ON

OFF

OFF

SW1

SW2

Setting

value 1

Setting

value 2

Hysteresis

Hysteresis

Separate Mode

Window Comparator Mode

Analog Output Setting

Switch Output Setting

Hysteresis setting

Switch output 2

setting

Switch output 1

setting

Press the  button for more 
than one second to return to 
the Operations Mode.

Low

High

(H operation)

OFF

ON

−Pr

Pr

H

H

P1:SW1

P2:SW2

ON

OFF

−Pr

Pr

H

H

P1:SW1

P2:SW2

(L operation)

(A operation)

OFF

ON

ON

−Pr

Pr

H

H

P1

P2

P1

P2

(B operation)

OFF

OFF

ON

−Pr

Pr

H

H

F-0:Response Time=5ms

F-1:Response Time=25ms

F-2:Response Time=250ms

F-3:Response Time=2.5s

Digital filter setting

+/−

SW1

SW2

P1≦P2 or P1≧P2

P1≦P2−2H

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

kPa

+/−

SW1

SW2

C O PA L   E L E C T R O N I C S

Pressure Settings Mode

Note:+50%F.S. is set prior to delivery.

An example of setting 60kPa for switch output 1(SW1 LED is flashing)with 102R.

To set switch output 1 the SW1 LED should be flashing. (To set switch output 2 the SW2 LED should be flashing.)

Switch Output Setting

Press the     button until 

the SW1 LED flashes.

Set the value to“60.0”

using the  and   

buttons.

Press the  button for 

more than one second

to return to the 

Operations Mode.

Press the  and  buttons 

Содержание PG-35L

Страница 1: ...s in the setting buttons and damage them Do not insert wires etc in the pressure port as this may damage the internal diaphragm and cause malfunctioning gasket type Do not touch or scratch the edge of...

Страница 2: ...ypes Materials at pressure receiving area Net Weight Accessories Negative pressure display Display accuracy IP protection Operating temperature Operating humidity Insulation resistance Dielectric stre...

Страница 3: ...de Pressure Settings Mode 1 1 2 0 0102 3 10 2 4 7 501 5 102 6 0 01 7 10 8 0 145 9 0 000145 A 0 001 b 0 2953 When the power is swiched on the Operations Mode is automatically selected Settings remain i...

Страница 4: ...tting SW2 or the hysteresis setting Set the value using the and buttons Press the button for more than one second to return to the Operations Mode Output Mode Operation 1 2 3 4 5 6 7 8 SW1 output Sepa...

Страница 5: ...me wet with oil or water which may enter the case through the air intake connect a silicon tube or similar to the intake and position the end of the tube in a suitably safe place Be sure not to bend t...

Страница 6: ...Mode kPa SW1 SW2 C O PA L E L E C T R O N I C S kPa SW1 SW2 C O PA L E L E C T R O N I C S kPa SW1 SW2 C O PA L E L E C T R O N I C S kPa SW1 SW2 C O PA L E L E C T R O N I C S To enable Non Display F...

Страница 7: ...ly Product name Model no Description Applicable model Holder cover set for protection of gauge sides Panel holder cover panel holder ACPG 004 PG 30 35 PG 35 Pressure ranges 102 100 to100kPa 103 100 to...

Отзывы: