4
The analog output setting is determined by the value of the second digit :
the green SW1 LED should be flashing during the setting.
The switch output setting is determined by the value of the first digit :
the red SW2 LED should be flashing during the setting.
There are four operation modes. These are shown in the diagrams below.
Note 1. In the Separate Mode, setting 1 corresponds to SW1, and Setting 2 corresponds to SW2.
Note 2. In the Window Comparator Mode, the minimum value for SW1 and SW2 corresponds to Setting 1 and the
maximum value corresponds to Setting 2.
Value selected
Value selected
1
2
3
R mode(Compound pressure output)
G mode(Positive pressure output)
V mode (Negative pressure output)
Mode
−Pr 0 +Pr
(Vzero)
1V
1V
1V
5V
5V
5V
In the Operations Mode, press the
and buttons simultaneously to
enter the Initial Settings Mode.
Press the button until the
SW1 LED under the second
digit flashes.
Set the value of the second
digit to “1” using the and
buttons.
An example of setting the R mode in the 102R range.
Notes:V mode for 102R are set prior to shipment.R/G mode for 103R can only be selected.
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
+/−
SW1
SW2
In the operations mode,
press the and
buttons simultaneously
to enter the Initial
Settings Mode.
Press the button
until the SW2 LED
under the first digit
flashes.
Set the value of the
first digit to“7”
using the
and buttons.
Press the button
for more than one
second to return to
the Operations Mode.
Press the and buttons
simultaneously to enter
the Pressure Settings Mode.
(The SW1 LED flashes.)
The LED of an item flashes
when selected using the button.
Press the button to select
between switch output 1 setting
(SW1), switch output 2 setting
(SW2), or the hysteresis setting.
Set the value
using the
and buttons.
Press the button for
more than one second
to return to the Operations
Mode.
Output
Mode
Operation
1
2
3
4
5
6
7
8
SW1 output
Separate
H
○
○
L
○
○
A
○
○
B
○
○
H
○
○
L
○
○
A
○
○
B
○
○
Window comparator
Note 1
Setting 1
Note 2
Minimum: Setting 1
Maximum: Setting 2
Minimum: Setting 1
Maximum: Setting 2
Note 1
Setting 2
Note 2
Separate Window comparator
SW2 output
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
■Window Comparator Mode
(An example of setting the value“7”
for the mode shown in the diagram.)
ON
ON
OFF
OFF
SW1
SW2
Setting
value 1
Setting
value 2
Hysteresis
Hysteresis
Separate Mode
Window Comparator Mode
■
Analog Output Setting
■
Switch Output Setting
Hysteresis setting
Switch output 2
setting
Switch output 1
setting
Press the button for more
than one second to return to
the Operations Mode.
Low
High
(H operation)
OFF
ON
−Pr
Pr
H
H
P1:SW1
P2:SW2
ON
OFF
−Pr
Pr
H
H
P1:SW1
P2:SW2
(L operation)
(A operation)
OFF
ON
ON
−Pr
Pr
H
H
P1
P2
P1
P2
(B operation)
OFF
OFF
ON
−Pr
Pr
H
H
F-0:Response Time=5ms
F-1:Response Time=25ms
F-2:Response Time=250ms
F-3:Response Time=2.5s
Digital filter setting
+/−
SW1
SW2
P1≦P2 or P1≧P2
P1≦P2−2H
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
kPa
+/−
SW1
SW2
C O PA L E L E C T R O N I C S
Pressure Settings Mode
Note:+50%F.S. is set prior to delivery.
An example of setting 60kPa for switch output 1(SW1 LED is flashing)with 102R.
To set switch output 1 the SW1 LED should be flashing. (To set switch output 2 the SW2 LED should be flashing.)
■
Switch Output Setting
Press the button until
the SW1 LED flashes.
Set the value to“60.0”
using the and
buttons.
Press the button for
more than one second
to return to the
Operations Mode.
Press the and buttons