Electric Power Generation

Installation and maintenance

LSAH 44.3

Low Voltage Alternator - 4 pole

5577 en -

4 - SERVICING - MAINTENANCE

4.1 - Safety measures

Servicing or troubleshooting must be 

carried out strictly in accordance with 

instructions so as to avoid the risk of 

accidents and to maintain the machine in 

its original state.

All such operations performed on the 

alternator should be undertaken by 

personnel trained in the commissioning, 

servicing and maintenance of electrical 

and mechanical components, who must

wear personal protective equipment 

appropriate for mechanical and electrical 

hazards.

Before  any  intervention  on  the  machine, 

ensure that it cannot be started by a manual 

or automatic system and that you have 

understood the operating principles of the 

system.

Also check that no liquid is leaking from the 

cooling circuit.

Warning : During and after running, the 

alternator will reach temperatures hot 

enough to cause injury, such as burns.

4.2 - Routine maintenance

• Checks after start-up

After approximately 20 hours of operation, 

check that all fixing bolts on the machine are 

still  tight,  plus  the  general  state  of  the 

machine and the various electrical 

connections in the installation.

• Electrical servicing

Commercially-available volatile degreasing 

agents can be used.

Do not use: trichlorethylene, perchlo-

rethylene, trichloroethane or any alkaline 

products.

These operations must be performed at a 

cleaning station, equipped with a 

vacuum system that collects and flushes 

out the products used.

The insulating components and the 

impregnation system are not at risk of 

damage from solvents. Avoid letting the 

cleaning product run into the slots.

Apply  the  product  with  a  brush,  sponging 

frequently to avoid accumulation in the 

housing. Dry the winding with a dry cloth. Let 

any traces evaporate before reassembling 

the machine.

• Mechanical servicing

Cleaning the machine using water or a 

highpressure washer is strictly prohi-

bited. Any problems arising from such 

treatment are not covered by our 

warranty.

Check regularly that no liquid is leaking from 

the cooling circuit.

Degreasing: Use a brush and detergent 

(suitable for paintwork).

Dusting: Use an air gun.

If the machine is fitted with air inlet and outlet 

filters,  the  maintenance  personnel  should 

clean them routinely at regular intervals. In 

the case of dry dust, the filter can be cleaned 

using compressed air and/or replaced if it is 

clogged.

After cleaning the alternator, it is essential to 

check the winding insulation (see sections 

3.2 and 4.5).

WARNING

WARNING

Содержание LEROY-SOMER LSAH 44.3

Страница 1: ...LSAH 44 3 Low Voltage Alternator 4 pole Installation and maintenance...

Страница 2: ...e to stand in front of the air outlet guards in case anything is ejected from them b Do not allow children younger than 14 to go near the air outlet guards Aset of self adhesive stickers depicting the...

Страница 3: ...3 INSTALLATION 6 3 1 Assembly 6 3 2 Checks prior to first use 6 3 3 Terminal connection diagrams 7 3 4 Commissioning 8 3 5 Setting up 8 4 SERVICING MAINTENANCE 9 4 1 Safety measures 9 4 2 Routine mai...

Страница 4: ...tact the transporter you may be able to claim on their insurance and after a visual check turn the machine by hand to detect any malfunction 1 3 Identification The alternator is identified by means of...

Страница 5: ...th SAE flange and standard cylindrical shaft extension Enclosed machine cooled by heat transfer fluid Degree of protection IP 44 T1 T2 T3 T4 T5 T6 5 6 D350 AREP SYSTEM STATOR 6 wire marking T1 to T6 E...

Страница 6: ...analysis of the transmission alternators data are available on request checking the dimensions of the flywheel and its housing the flange coupling discs and offset WARNING When coupling the alternator...

Страница 7: ...order 1 2 3 For anti clockwise rotation swap 2 and 3 the winding connection corresponds to the site operating voltage see section 3 3 WARNING At the first start up or after an extended shutdown allow...

Страница 8: ...terminal box is connected to the electrical earth circuit The earth terminal is connected to the frame The connections inside the terminal box must never be subjected to stress due to cables connecte...

Страница 9: ...lectrical connections in the installation Electrical servicing Commercially available volatile degreasing agents can be used Do not use trichlorethylene perchlo rethylene trichloroethaneoranyalkaline...

Страница 10: ...f the grease has turned black change the bearing Bearing not fully locked abnormal play in the bearing cage End shields incorrectly aligned Abnormal temperature Excessive overheating of alternator fra...

Страница 11: ...rnt out Revolving field coil short circuited Check the resistance Speed too low Increase the drive speed do not touch theAVR voltage pot P2 before running at the correct speed Voltage too high AdjustA...

Страница 12: ...diode 12V battery Rh 50 300W ASSEMBLY A Field Assembly B Connect a Variac variable power supply and a diode bridge on both exciter field wires 5 and 6 Both these systems should have characteristics w...

Страница 13: ...4 Draining the cooling circuit Leave the machine stationary for 6 hours before draining the cooling circuit operating temperature 70 C The cooling circuit must be drained using a fluid recovery syste...

Страница 14: ...he machine To facilitate mounting screw two threaded rods into inner bearing retainer 78 and slide them into the holes of the shield 30 by reassembling the drive end shield 30 Finish the assembly of i...

Страница 15: ...pe Stator L N Rotor Exciter field Exciter armature M4 0 021 2 64 8 07 0 920 M6 0 022 2 89 8 07 0 920 L8 0 015 3 15 8 07 0 920 VL12 0 010 3 86 8 07 0 920 Resistances of auxiliary windings at 20 C Type...

Страница 16: ...ds These sensors must be linked to adapted sensing relays supplied optionally Cold resistance of cold thermistor sensors 100 to 250 per sensor 5 2 Technical support service Our technical support servi...

Страница 17: ...17 2020 05 c Electric Power Generation Installation and maintenance LSAH 44 3 Low Voltage Alternator 4 pole 5577 en 5 4 Exploded views parts list and tightening torque Single bearing...

Страница 18: ...18 2020 05 c Electric Power Generation Installation and maintenance LSAH 44 3 Low Voltage Alternator 4 pole 5577 en Two bearing...

Страница 19: ...M6 5 79 1 Preloading wavy washer 17 1 Fan hub 90 1 Exciter field M6 10 22 1 Key 100 1 Exciter armature 28 1 Earth terminal M6 10 107 1 Diode module support M5 6 30 1 Drive end DE shield M12 69 124 1...

Страница 20: ...cial treatment and must be separated from the alternator before the recycling process electronic materials found in the terminal box including the automatic voltage regulator 198 current transformers...

Страница 21: ...047 TAL 0473 TAL 049 LSAH 443 as well as their derivatives manufactured by Leroy Somer or on Leroy Somer s behalf comply with the following International Standards and Directive EN and IEC 60034 1 600...

Страница 22: ...22 2020 05 c Electric Power Generation Installation and maintenance LSAH 44 3 Low Voltage Alternator 4 pole 5577 en...

Страница 23: ...ient repair support and maintenance services Trust your alternator maintenance and support to electric power generation experts Our field personnel are 100 qualified and fully trained to operate in al...

Страница 24: ...www emersonindustrial com 2020 05 c www leroy somer com epg 5577 en Linkedin com company leroy somer Twitter com Leroy_Somer_en Facebook com LeroySomer Nidec en YouTube com LeroySomerOfficiel...

Отзывы: