Model
Power supply
network
Main fuses
1
External fuses
supplied with the
drive for HSCCR
(b)
Cables cross
section **
Terminals
Max torque
HighSCCR
(UL)
(b)
2/2
5
5.4.1 POWER CABLES AND POWER SUPPL
Y FUSES
Input Output
AD1A086F
AC
125x3
FWH-225A
2/0
70
M6 M8
10
7.37
65
AD1A108F
AC
175x3
FWH-225A
3/0
95,0
M6 M8
10
7.37
65
AD1A125F
AC
200x3
FWH-300A
4/0
35
M8 M8
10
7.37
65
AD1A150F
AC
250x3
FWH-300A
250
120
M8 M8
10
7.37
65
AD1A166F
AC
250x3
FWH-300A
250
120
M8 M8
10
7.37
65
AD1A210F
AC
300x3
3xFWH-450A
2X2/0
2X95
3x1xM10
22.5
16.59
65
AD1A260F
AC
350x3
3xFWH-500A
2X3/0
2X95
3x1xM10
22.5
16.59
65
AD1A290F
AC
500x3
3xFWH-600A
3X3/0
2X95
3x4xM10
22.5
16.59
65
AD1A350F
AC
600x3
3xFWH-700A
3X4/0
3X120
3x4xM10
22.5
16.59
65
AD1A370F
AC
770x3
3xFWH-800A
4X4/0
4X120
3x4xM10
22.5
16.59
65
AD1A440F
AC
800x3
3xFWH-1000A
4X4/0
4X120
3x4xM10
22.5
16.59
65
AD1A480F
AC
800x3
3xFWH-1000A
4X4/0
4X120
3x4xM10
22.5
16.59
65
AD1A520F
AC
850x3
3xFWH-1000A/1200A 4X4/0
4X120
3x4xM10
22.5
16.59
65
F = Three-phase supply voltage 380V, 415V, 440V, 460V, 480V / Y=510-650VDC ±10%
[A]
(UL)
AWG
mm
2
Nm
lbf ft
kA
The drive is suitable for use in a circuit with short circuit current
not greater than the specific High Short Circuit Current rating_
(Arms) Symmetrical Amperes value, shown in Table 5.4.1.2, 480 V
ac + 10% max, provided that it is protected by the related fuse for
semiconductor indicated in Table 5.4.1.2, Brand Bussmann, supplied
with the drive.
The user must also install, upstream of the fuses of table 5.4.1.2,
some not resettable cartridge fuses (JDDZ/JDDZ7), Class J, with the
right voltage and current gauge.
** The cables cross-section in the table is indicative. Refer to local
wiring rules for correct sizing. In some cases a larger cross-section may
be required to prevent excessive voltage drops.