6.4 IN/- and OUTPUTs
Digital Inputs DI
(day/night; enable group)
+24V
DI (Voltage)
10mA (minimum current source capacity)
4 kV (isolating voltage against internal circuit)
Analogue Inputs AI
(Sensor
values-,
Speed
setting)
0 … 0.5 … 10V (=)
from 0.5V linear
40 k
(internal resistance)
3,75 kV
(isolating voltage against
internal circuit)
Digital Outputs DO
(Error relays)
as low-active or high-active programmable
60V (max. Voltage as peak AC / DC)
500mA (max. Current as peak AC / DC)
1,5 kV (max. Current as peak AC / DC)
Analogue Outputs AO
Sensor Power Supply
+10V (=)
20mA (max. Current as peak AC / DC)
+24V (=)
100mA (max. Current as peak AC / DC)
min 1kV (isolating voltage across DC/DC converter)
6.5 Fan Network
Hardware
RS485
Maximum Subscriber
200 at 2 Lines
(100 / Line)
Maximum line length
400m (per Line)
Baud rate
according type of subscriber
cable
(recommended) Cat. 5
isolating
voltage
against
internal circuit
2,5 kV (overvoltage class 2)