Installation
EN - 9 of 39
2 Installation
Warnings
Work on the device/system by unqualified personnel or failure to comply with
warnings can result in severe personal injury or serious damage to material.
Only suitably qualified personnel trained in the set-up, installation,
commissioning and operation of the product should carry out work on the
device/system.
This equipment must be grounded.
The following terminals can carry dangerous voltages even if the EC-
Controller is inoperative:
•
the power supply terminals L1, N
•
the motor terminals U, V, W
2.1 Ambient Operating Conditions
Protection
Class
IP 54
Humidity Range
90% Non-condensing
Altitude
If the inverter is to be installed at an altitude > 1000m, derating is required.
Shock
Do not drop the inverter or expose it to sudden shock.
Vibration
Do not install the inverter in an area where it is likely to be exposed to constant vibration.
Installation
Warnings
The device is designed to be exposed partly to the fan air stream with
maximum medium temperature of 40°C to achieve full power load at all fan
sizes.
Alternatively, a forced cooling can be realized in any other way, for instance by
additional blower. Otherwise, if the operating conditions cause overheating,
the controller would automatically perform self-derating to operate at the
allowed temperature limit, indicating warning "Temperature derating".
Do not cover the device during operation!