NICOR VT2 LED VAPORTITE Скачать руководство пользователя страница 3

NICOR, Inc.   2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393  www.nicorlighting.com

 April 12, 2018 11:25AM VT2-20 rev 1.1 

Page 3 of 4

If using a motion sensor 
(sold separately), remove 
bottom plug and install 
desired sensor (hole is 1/2” 
KO through hole). NOTE: 
Check clearance of  
motion sensor with  
conduit. A drop neck 
sensor may be required.

Slide luminair toward endcap and connect  
wiring as shown. If using motion sensor, wire 
according to sensor wiring diagram.

For condensation valve use (recommended in 
certain enviroments): remove top plug from  
opposite end of power input and insert  
Condensation Valve (sold separately) (hole is 
threaded 1/2” NPT)

Reattach endcap to fixture ensuring cap seats 
fully on gasket and tighten cord grip fully.

Remove endcap bolts and endcap using M3 
hex/allen wrench.

Attach endcap 
to conduit via 
fitting. Pull wiring 
through conduit 
leaving 6”  
exposed for  
wiring to fixture.

Remove top plug from 
fixture end and insert 
proper conduit  
connector. (Liquid tight 
fitting is required. Hole 
is threaded 1/2” NPT).

Push up luminaire and 
press it into mounting 
brackets until fixture 
snaps into place.

6

10

7

11

4

8

5

9

INSTALLATION WITH CONDUIT

   

(conduit connector not included)

NOTE:

 

Use of condensation valve prevents through wiring/continuous run.

NOTE:

 

Fixture is pre-wired for through wiring. 

ATTENTION:

 Order of installation for continuous run is as follows:

1) Follow steps 4-8 above, step 9 was completed previously. Do not tighten the conduit connector to conduit until endcap is fully re-installed.
2) As fixture is mounted to conduit, the endcap and conduit assembly must be pulled towards fixture. Leave sufficient space for wiring access.
3) Pull wire through conduit and connect per step 10.
4) Pull conduit assembly fully to fixture and follow step 11 above to finalize installation.

CAUTION: For continuous runs the maximum number of fixtures is as follows: 2ft = 40, 4ft = 20

6” Typ

.

Com

Line

1 - 10V (-)

1 - 10V (+)

Luminaire

Purple

Gray

GND

White

Black

GND

Отзывы: