If using a motion sensor
(sold separately), remove
bottom plug and install
desired sensor (hole is 1/2”
KO through hole). NOTE:
Check clearance of
motion sensor with
conduit. A drop neck
sensor may be required.
Slide luminair toward endcap and connect
wiring as shown. If using motion sensor, wire
according to sensor wiring diagram.
For condensation valve use (recommended in
certain enviroments): remove top plug from
opposite end of power input and insert
Condensation Valve (sold separately) (hole is
threaded 1/2” NPT)
Reattach endcap to fixture ensuring cap seats
fully on gasket and tighten cord grip fully.
Remove endcap bolts and endcap using M3
hex/allen wrench.
Attach endcap
to conduit via
fitting. Pull wiring
through conduit
leaving 6”
exposed for
wiring to fixture.
Remove top plug from
fixture end and insert
proper conduit
connector. (Liquid tight
fitting is required. Hole
is threaded 1/2” NPT).
Push up luminaire and
press it into mounting
brackets until fixture
snaps into place.
6
10
7
11
4
8
5
9
INSTALLATION WITH CONDUIT
(conduit connector not included)
NOTE:
Use of condensation valve prevents through wiring/continuous run.
NOTE:
Fixture is pre-wired for through wiring.
ATTENTION:
Order of installation for continuous run is as follows:
1) Follow steps 4-8 above, step 9 was completed previously. Do not tighten the conduit connector to conduit until endcap is fully re-installed.
2) As fixture is mounted to conduit, the endcap and conduit assembly must be pulled towards fixture. Leave sufficient space for wiring access.
3) Pull wire through conduit and connect per step 10.
4) Pull conduit assembly fully to fixture and follow step 11 above to finalize installation.
CAUTION: For continuous runs the maximum number of fixtures is as follows: 2ft = 40, 4ft = 20
6” Typ
.
Com
Line
1 - 10V (-)
1 - 10V (+)
Luminaire
Purple
Gray
GND
White
Black
GND