clear and especially it is interoperable. That means, the 3010PL Power
Controller can be used in connection with network components by other
manufactures. The following table contains a survey of the network
variables defining the 3010PL Power Controller network interface and their
assignment.
NV Name
Type
Allocated Object
nviSwitch
SNVT_switch
Closed-Loop Actuator
nvoSwitch
SNVT_switch
Closed-Loop Actuator
and Open-Loop Sensor
nviSwInput
SNVT_switch
Nico Tech. Signal Input
Switch Processor
nvoSwOutput
SNVT_switch
Nico Tech. Signal Input
Switch Processor
Table 4.4 Allocation of NVs and LonMark objects
Under the order code 3010L a data carrier containing the interface
describing file
Nico_PwrCtrl-3010PL_r1.XIF
and the application
Nico_PwrCtrl-3010PL_r1.APB
is provided free of charge at simultaneous
purchase of a 3010PL Power Controller. The XIF-file is necessary for
integration with LonMaker for Windows or any other LonWorks network
management tool.
6 System
Objects
This chapter describes the LonMark objects implemented in the 3010PL
Power Controller. For each it states the network variable les used, special
configuration properties, general object properties, response during
modification of the configuration and after a reset, and, if available, further
object properties.
Finally the relevant plug-in designated to configure the object is described.
Details about handling of the plug-ins can be found in chapter 7.
6.1
Node Object
The functionality of the node object is defined in the Application Layer
Guidelines of LonMark Interoperability Association
(
www.lonmark.org
).
Network Variables
NV Name
NV Type
Comment
nviRequest
SNVT_obj_request
Status request