3010PL Power Controller
User’s Manual
14
Rev.1.0
5 Application Software for Lighting Control
On the 3010PL Power Controller an application for switch control is
implemented, making output functionality as well as switch control functions
available. Therefore the relevant LonMark profiles stated in Table 4.1 are
implemented. The use of network variables (NV) compiles with the LonMark
standard, no customized network variables are used. SCPT’s are used for
parameterization by applying the read/write-memory method.
Title
Present
Version
Identification
LonMark Application Layer Interoperability Guidelines
V3.1
078-0120-01D
The SNVT Master List and Programmer’s Guide
V 8.0
The SCPT Master List
V 8.0
LonMark Functional Profile Open Loop Sensor
V 1.0
001
LonMark Functional Profile Close Loop Actuator
V 1.0
004
Signal Input Switch Process Object
Table 4.1 Referring document about LonMark profiles
5.1
System Scope
The 3010PL Power Controller is equipped with twenty channels, ten
channels for Relay Output and other ten channels for Dry Contact input.
The relay outputs of the 3010PL Power Controller allow the connection of
actuator. A Closed-Loop Actuator (CLA) object and Open-Loop Sensor
(OLS) object according to LonMark Standard can be assigned to these
output and configured.
Furthermore the 3010PL Power Controller can act as constant switch
controller and sensor controller. The switch and sensor detect either
generated by the internal CLA and OLS object; via an input network
variable.
The 3010PL Power Controller is equipped with ten relay outputs circuit to
connect e.g. Fluorescent Light, Motorize Screen.
Other ten dry contact input circuit to connect e.g. Motion Sensor, Smoke
detect, Alarm speaker.
5.2
Interoperable Interface
The
LonMark profile
004
is
realized in the 3010PL Power Controller. As no
customized NVs are used, the network interface remains standardized,