SETTINGS OF THE AUTOMATIC FUNCTIONS
Automatic closing
Automatic closing is set on the S2 selector.
The closing times can be set on a value between 0 and 240 seconds.
Special function:
If there is a photoelectric barrier, the time is reduced by 5 seconds
after passage.
Time setting
0 Automatic
closing disabled
1 5
seconds
2
10
seconds
3 20
seconds
4 30
seconds
5 45
seconds
6
60
seconds
7 90
seconds
8 120
seconds
9
240
seconds
5
4 6
3
7
2
8
1
90
s2 rotary
switch
Automatic adaptation to the ground
DIP 2 = ON
This function can be used if there is an SBA
sensor.
Advance notice traffi c lights
DIP 3 = ON
With this function the red traffi c lights (terminals
1+2) begin to fl ash 3 seconds before closing of
the door.
Reversed movement function
DIP 4 = ON
The door blocks and reverses its direction for
about 50 cm if the sensitive edge is enabled
during the downward movement.
Meaning of display messages
Upper segment:
fl ashing --> upper fi nal position setting in progress
ON --> upper fi nal position setting completed
Lower segment:
fl ashing --> lower fi nal position setting in progress
ON--> lower fi nal position setting completed
movement UP,
movement
DOWN,
upper fi nal position,
preliminary limit switch
,
lower fi nal
position.
Error 3
sensitive edge tripped, for example
In normal operating conditions, the
status of the door and/or the number
of the error present are shown on the
display.
Operation functions
In normal operating conditions, the
status of the door and/or the number
of the error present are shown on the
display. In this case position all DIP
switches on OFF!
Fault display (represented with fl ashing):
1 Safety circuit
2
Lower sensitive edge fault
3
Lower sensitive edge tripped
4
Lower fi nal position not reached
(time limit)
5
Upper fi nal position not reached
(time limit)
6
Incorrect direction of rotation of motor
7
Power during lifting deactivation
8
Door in the safety limit switch sector
9
The door is not in one of the fi nal
positions. Correction of the fi nal position
is impossible
0
Digital limit switch error
DIP switch functions:
DIP-1 “ON“ and 2, 3, 4 “OFF“
Setting of the fi nal positions
DIP-1, 2, 4 “ON“ and 3 “OFF“
Precision setting of the fi nal position (upward
movement)
DIP-1, 3, 4 “ON“ and 2 “OFF“
Precision setting of the fi nal position
(downward movement)
WARNING:
It is possible to lengthen the duration of the waiting time of a factor
by choice (with selector in position 6 to 9) using the K5 module. The
parameter to be used is P28.
DIP 4 = OFF
The door blocks and reaches the upper fi nal position if the
sensitive edge is enabled during the downward movement.