Over capacity mode means that the electricity supplier has
set the tariff very low and the system uses this to reduce
the costs as much as possible.
affect room temperature
Here you set whether room temperature should be affected
when activating "SG Ready".
With low price mode on "SG Ready", the parallel offset for
the indoor temperature is increased by "+1". If a room sensor
is installed and activated, the desired room temperature is
increased instead by 1 °C.
With overcapacity mode on "SG Ready", the parallel offset
for the indoor temperature is increased by "+2". If a room
sensor is installed and activated, the desired room temper-
ature is increased instead by 2 °C.
affect hot water
Here you set whether the temperature of the hot water
should be affected when activating "SG Ready".
With low price mode on "SG Ready" the stop temperature of
the hot water is set as high as possible at only compressor
operation (immersion heater not permitted).
With over capacity mode of "SG Ready" the hot water is set
to "activate temp lux" (immersion heater permitted).
affect cooling (accessory required)
Here you set whether room temperature during cooling op-
eration should be affected when activating "SG Ready".
With low price mode of "SG Ready" and cooling operation
the indoor temperature is not affected.
With overcapacity mode on "SG Ready" and cooling opera-
tion, the parallel offset for the indoor temperature is de-
creased by "-1". If a room sensor is installed and activated,
the desired room temperature is decreased instead by 1 °C.
affect pool temperature (accessory is
required)
Here you set whether pool temperature should be affected
when activating "SG Ready".
With low price mode on "SG Ready", the desired pool temper-
ature (start and stop temperature) is increased by 1 °C.
With overcapacity mode on "SG Ready", the desired pool
temperature (start and stop temperature) is increased by
2 °C.
NOTE
The function must be connected to two AUX inputs
and activated in menu 5.4.
NIBE VVM 500
Chapter 6 | Commissioning and adjusting
36