Installer manual

Indoor module

NIBE VVM 500

IHB EN 2235-1
731222

Содержание VVM 500

Страница 1: ...Installer manual Indoor module NIBE VVM 500 IHB EN 2235 1 731222 ...

Страница 2: ... described on page 39 Set the indoor climate 2X MY INSTALLATION INDOOR CLIMATE HOT WATER INFO The mode for setting the indoor temperature is accessed by pressing the OK button twice when in the start mode in the main menu Increase hot water volume 2X 1X INDOOR CLIMATE HOT WATER MY INSTALLATION INFO To temporarily increase the amount of hot water first turn the control knob to mark menu 2 water dro...

Страница 3: ... 26 Optional connections 30 Connecting accessories 31 6 Commissioning and adjusting 31 Preparations 31 Filling and venting 32 Start up and inspection 34 Setting the heating curve 35 Cooling in 2 pipe system 35 Setting hot water circulation 35 Pool 35 SG Ready 37 7 Control Introduction 37 Display unit 37 Menu system 41 8 Control Menus 41 Menu 1 INDOOR CLIMATE 42 Menu 2 HOT WATER 42 Menu 3 INFO 43 M...

Страница 4: ...plashes cannot cause harm The entire length of the overflow pipe must be inclined to prevent water pockets and must also be frost proof The overflow pipe must be at least the same size as the safety valve The overflow pipe must be visible and its mouth must be open and not placed close to elec trical components VVM 500 must be installed via an isolator switch The cable area has to be dimen sioned ...

Страница 5: ...ection must be carried out by a suitably qualified person In addition fill in the page for the installation data in the User Manual Date Signature Notes Description Heating medium see section System diagram System flushed System vented Expansion vessel Particle filter Safety valve Shut off valves System pressure Connected according to outline diagram Hot water see section Cold and hot water Shut o...

Страница 6: ...0V Part no 064 220 S2125 12 3x400V Part no 064 217 S2125 12 1x230V Part no 064 218 F2300 F2300 20 Part no 064 064 NIBE SPLIT HBS 05 HBS 05 12 Part no 067 480 AMS 10 12 Part no 064 110 HBS 05 16 Part no 067 536 AMS 10 16 Part no 064 035 NIBE SPLIT HBS 20 6 Part no 067 668 AMS 20 6 Part no 064 235 HBS 20 10 Part no 067 819 AMS 20 10 Part no 064 319 Check the software version of compatible older NIBE...

Страница 7: ...0 mm 20 55 mm The space where VVM 500 is located must be frost free Because water can exit the safety valve1 for hot water when connected to VVM 500 the space where VVM 500 is placed must be provided with a floor drain 1 Not enclosed INSTALLATION AREA Leave a free space of 800 mm in front of the product All service on VVM 500 can be carried out from the front 800 10 25 50 50 NOTE Leave 10 25 mm fr...

Страница 8: ...O rings LE K LE K LE K Current sensor LEK Cable APH Flow meter Union nut Copper pipe with flange to energy meter Only applies to Norway LOCATION The kit of supplied items is placed on top of the product NIBE VVM 500 Chapter 2 Delivery and handling 8 ...

Страница 9: ...e panels can be removed to make installation easier Caution 50 mm space required to remove the side panels 1 Remove the screws from the upper and lower edges 2 Twist the panel slightly outwards 3 Move the panel backwards and slightly to the side 4 Pull the panel to one side 5 Pull the panel forwards 6 Assembly takes place in the reverse order 9 Chapter 2 Delivery and handling NIBE VVM 500 ...

Страница 10: ...Z3 PZ1 GP12 QN10 AA2 SF1 UB1 AA4 XF4 AA4 AA4 XF3 GP1 BT63 BT2 UB2 XL8 XL9 XL4 XL30 XL2 XL3 XL14 XL13 XL19 XL18 XL1 QN11 BT6 BT54 QM20 BT7 PZ3 PZ1 XL39 XL39 XL18 XL14 XL19 XL13 AA7 W130 BT3 NIBE VVM 500 Chapter 3 Design VVM 500 10 Design VVM 500 ...

Страница 11: ...valve addition QN11 Reversing valve climate system water heating return line QN35 SENSORS ETC Temperature sensors heating medium flow BT2 Temperature sensor heating medium return1 BT3 Temperature sensor hot water control1 BT6 Temperature sensor hot water display1 BT7 Temperature sensor solar coil1 BT54 Temperaturesensor heatingmediumsupplyafterimmer sion heater BT63 1 Not visible in the image ELEC...

Страница 12: ...9 F2050 6 F2050 10 Minimum re commended pipe dimen sion mm Minimum re commended pipe dimen sion DN Minimum flow duringdefrost ing 100 pump speed l s Air waterheat pump 28 25 0 38 F2120 16 3x400V 35 32 0 48 F2120 20 3x400V Minimum re commended pipe dimen sion mm Minimum re commended pipe dimen sion DN Minimum flow duringdefrost ing 100 pump speed l s Air waterheat pump 28 25 0 32 S2125 8 1x230V S21...

Страница 13: ...damaged SYSTEM VOLUME H Internal volume in VVM 500 for calculating expansion vessel is 500 l The expansion vessel s volume must be at least 5 of the system s total volume Example table Volume l ex pansion vessel Total volume l indoor module andclimatesys tem 25 500 35 700 50 1 000 NOTE Expansion vessels are not supplied with the product Equip the product with an expansion vessel The pre pressure o...

Страница 14: ...sists of a hot water coil immersion heater circulation pumps buffer vessel control system and is pre pared for use with solar panels VVM 500 connects to the climate system VVM 500 is directly adapted for connection and communic ation with a compatible NIBE air water heat pump see sec tion Outdoor modules and together they constitute a complete heating installation When it is cold outdoors the air ...

Страница 15: ... 290 648 25 50 XL8 XL9 XL4 XL2 XL3 XL1 XL30 Pipe connections G25 int XL1 Connection heating medium supply line G25 int XL2 Connection heating medium return line G25 int XL3 Connection cold water G25 ext XL4 Connection hot water G25 int XL8 Connection docking from heat pump G25 int XL9 Connection docking to heat pump G25 int XL30 Connection expansion vessel 15 Chapter 4 Pipe connections NIBE VVM 50...

Страница 16: ... that regulates the indoor temperature with the help of the control system in VVM 500 and for example radiators underfloor heating underfloor cooling fan coils etc CONNECTING THE CLIMATE SYSTEM Install as follows expansion vessel in connection XL30 pressure gauge in connection XL30 pressure relief valve Recommended opening pressure is 0 25 MPa 2 5 bar For information about max opening pressure see...

Страница 17: ...s installed A mixer valve is then installed on the outgoing hot water from the water heater Water heater with immersion heater In a water heater with an immersion heater the water is initially heated by the heat pump The immersion heater in the water heater is used for keeping warm and when the heat pump does not have sufficient power The water heater s flow is connected after VVM 500 EXTRA CLIMAT...

Страница 18: ...indoor module from the back to the front APH VVM 500 B AB APH UB2 UB1 SF1 NOTE The switch SF1 must not be set to or until the boiler has been filled with water and the radi ator system vented Otherwise the temperature limiter thermostat and the immersion heater can be damaged NOTE If the supply cable is damaged only NIBE its ser vice representative or similar authorised person may replace it to pr...

Страница 19: ...of the electrical boxes is opened using a screwdriver NOTE The cover for the input card is opened without a tool Removing the cover input circuit board 1 2 1 Push the catch down 2 Angle out the cover and remove it Removingthecover immersionheatercircuit board 1 2 A B 1 Insert the screwdriver A and pry the catch carefully downwards B 2 Angle out the cover and remove it Removing the cover base board...

Страница 20: ...CABLE LOCK Use a suitable tool to release lock cables in the indoor module terminal blocks LEK 1 2 2 3 1 2 3 3 4 1 2 LEK 1 1 2 2 3 3 1 2 3 3 4 1 2 1 2 NIBE VVM 500 Chapter 5 Electrical connections 20 ...

Страница 21: ...cordance with current norms and directives The connection cable can be found on the reverse of VVM 500 See dimensions diagram below 140 60 30 1690 Connection 3x400V AA1 X1 PE1 L1 1 L2 L3 PE 0 N B B A A VVM225 AA1 X1 TARIFF CONTROL If the voltage to the immersion heater disappears during a certain period there must also be blocking via the AU input see Connection options Possible selection for AU i...

Страница 22: ... AA1 X11 as illustrated 1 2 3 4 5 6 ON L1 1 L2 L3 PE PE 0 N N L 1x230V N PE 1x230V N PE operating voltage AA1 AA1 X8 AA1 X2 AA1 X9 AA1 X11 Tariff control If the voltage to the immersion heater is lost for some time Tariff blocking must be selected at the same time via the selectable inputs see section Selectable inputs CONNECTING SENSOR AA3 X6 Outside sensor The outdoor temperature sensor BT1 is p...

Страница 23: ...M 500 the sensor must be fitted Connect the room sensor to X6 3 and X6 4 on the input board AA3 If the room sensor is to have a controlling function it is ac tivated in menu 1 9 4 If the room sensor is used in a room with underfloor heating it should only have an indicatory function not control of the room temperature F1245 RG 05 2 3 4 5 AA3 X6 BT50 External VVM 500 Caution Changes of temperature ...

Страница 24: ...VVM 500 and F2300 A GND B AA21 J2 Inomhusmodul AA3 X4 B GND A 14 13 12 11 10 15 F2300 VVM 500 F2300 NIBE VVM 500 Chapter 5 Electrical connections 24 ...

Страница 25: ...he current sensors are connected the indoor module monitors the phase currents NOTE If the current sensors are not connected the in door module performs a calculation of how high the currents will be if the relevant power steps are added If the currents are higher than the set fuse size the power step is not allowed to cut in See chapter Load monitor on page 26 EMERGENCY MODE When the indoor modul...

Страница 26: ... sensors NOTE If the installed air water heat pump is frequency controlled it will be limited when all power stages are disconnected A current sensor should be installed on each incoming phase conductor in to the distribution box to measure the current The distribution box is an appropriate installation point Connect the current sensors to a multi core cable in an en closure directly adjacent to t...

Страница 27: ...or NC stove monitor for accessory ERS Stove monitor is a thermostat that is connected to the chimney When the negative pressure is too low the fans in ERS NC are switched off pressure switch for climate system NC External activation of functions An external switch function can be connected to VVM 500 to activate various functions The function is activated during the time the switch is closed Possi...

Страница 28: ...the Software tab to download the latest software to your installation Caution In systems with both underfloor heating and ra diators NIBE ECS 40 41 should be used for op timum operation External blocking of functions An external switch function can be connected to VVM 500 for blocking various functions The switch must be potential free and a closed switch results in blocking NOTE Blocking entails ...

Страница 29: ...e cooling is activated by the temperature of the outdoor temperature sensor BT1 and any room sensor BT50 room unit or separate room sensor for cooling BT74 if two different rooms are to be heated or cooled at the same time for example When cooling is required the cooling reversing valve EQ1 QN12 and the cooling circula tion pump EQ1 GP12 in the indoor module VVM are activ ated Cooling production i...

Страница 30: ... LiYY EKKX or similar Refer to the accessory manual for further instructions 1 2 3 4 5 6 7 8 AA5 X4 15 A B GND A B GND A B GND A B GND A B GND 14 13 AA3 X4 1 2 3 4 5 6 7 8 AA5 X4 Indoor module Accessory card 1 Accessory card 2 ON 1 2 3 4 5 6 7 8 X9 X2 24 20 21 22 23 15 16 17 18 19 10 11 12 13 14 5 6 7 8 9 1 1 N L PE PE 1 2 3 4 5 6 7 8 2 3 4 5 6 7 8 9 2 3 4 X8 X4 X10 X1 AA5 X4 ON 1 2 3 4 5 6 7 8 X9...

Страница 31: ... of the climate system are filled with water 3 When the water exiting the vent valves QM20 is not mixed with air close the vent valves After a while the pressure rises on the externally mounted pressure gauge When the opening pressure for the externally mounted safety valve has been reached it starts to re lease water Close the filler valve 4 Open the externally mounted safety valve until the pres...

Страница 32: ...orwards to help vent VVM 500 Caution As long as the start guide is active no function in VVM 500 will start automatically The start guide will appear at each restart of VVM 500 until it is deselected on the last page Operation in the start guide language 4 6 If the start guide is left on this page it closes automatically in 60 min A Page C Option setting B Name and menu number A Page Here you can ...

Страница 33: ...s using control and external heating requirement Available pressure circulation pump GP1 0 10 20 30 40 50 60 70 80 0 0 0 1 0 2 0 3 0 4 0 5 0 6 Tillgängligt tryck kPa Vattenflöde l s 20 100 40 60 80 Available pressure kPa Flow l s Available pressure charge pump GP12 0 10 20 30 40 50 60 70 80 0 0 0 1 0 2 0 3 0 4 0 5 0 6 Tillgängligt tryck kPa Vattenflöde l s 20 100 40 60 80 Flow l s Available pressure...

Страница 34: ...rther adjustment CURVE OFFSET An offset of the heating curve means that the supply tem perature changes by the same amount for all outdoor tem peratures e g a curve offset of 2 steps increases the supply temperature by 5 C at all outdoor temperatures 20 0 10 0 10 20 30 40 30 40 50 60 70 80 Framledningstempereratur C Utetemperatur C Offset heating curve Supply temperature Outdoor temperature SUPPLY...

Страница 35: ...settings for the climate system are adjusted in the indoor climate menu menu 1 Setting hot water circulation operating time Setting range 1 60 min Factory setting 60 min downtime Setting range 0 60 min Factory setting 0 min Set the hot water circulation for up to three periods per day here During the set periods the hot water circulation pump will run according to the settings above operating time...

Страница 36: ...operation immersion heater not permitted With over capacity mode of SG Ready the hot water is set to activate temp lux immersion heater permitted affect cooling accessory required Here you set whether room temperature during cooling op eration should be affected when activating SG Ready With low price mode of SG Ready and cooling operation the indoor temperature is not affected With overcapacity m...

Страница 37: ...door module display is not illuminated and the status lamp illuminates yellow F USB PORT The USB port is hidden beneath the plastic badge with the product name on it The USB port is used to update the software Visit nibeuplink com and click the Software tab to download the latest software for your installation G Menu system When the door to the indoor module is opened the menu system s four main m...

Страница 38: ... that blocks one of them Blocking the compressor Blocking additional heat This symbol appears if periodic increase or lux mode for the hot water is activated This symbol indicates whether holiday setting is active in 4 7 This symbol indicates whether VVM 500 has con tact with NIBE Uplink This symbol indicates the actual speed of the fan if the speed has changed from the normal setting Accessory ne...

Страница 39: ...t another option 1 Mark the applicable option One of the options is pre selected white 2 Press the OK button to confirm the selected option The selected option has a green tick SETTING A VALUE time date 4 4 time day year month 24 h 12 h date Values to be changed To set a value 1 Mark the value you want to set using the control knob 2 Press the OK button The background of the value becomes green wh...

Страница 40: ...dows Current menu window Number of windows in the menu Scroll through the windows in the start guide language 4 6 If the start guide is left on this page it closes automatically in 60 min Arrows to scroll through window in start guide 1 Turn the control knob until one of the arrows in the top left corner at the page number has been marked 2 Press the OK button to skip between the steps in the star...

Страница 41: ...ating curve 1 9 1 curve 1 9 advanced 1 9 1 2 cooling curve 1 9 2 external adjustment 1 9 3 1 heating 1 9 3 min flow line temp 1 9 3 2 cooling 1 9 4 room sensor settings 1 9 5 cooling settings 1 9 6 fan return time 1 9 7 1 heating 1 9 7 own curve 1 9 7 2 cooling 1 9 8 point offset 1 9 9 night cooling 1 9 11 Adjust Accessories are needed 41 Chapter 8 Control Menus NIBE VVM 500 Control Menus ...

Страница 42: ...ATER 2 2 comfort mode 2 3 scheduling 2 9 2 hot water recirc 2 9 advanced Menu 3 INFO 3 1 service info 3 INFO 3 2 compressor info 3 3 add heat info 3 4 alarm log 3 5 indoor temp log Accessories are needed NIBE VVM 500 Chapter 8 Control Menus 42 ...

Страница 43: ...riods electricity 4 1 8 6 tariff per ext shunt add 4 1 8 7 tariff per ext step add 4 1 8 8 tariff periods OPT10 Menu 4 1 10 solar electricity 4 2 op mode 4 3 my icons 4 4 time date 4 6 language 4 7 holiday setting 4 9 1 op prioritisation 4 9 advanced 4 9 2 auto mode setting 4 9 3 degree minute setting 4 9 4 factory setting user 4 9 5 schedule blocking 4 9 6 schedule silent mode 4 9 7 tools Accesso...

Страница 44: ...settings 5 2 4 accessories 5 3 2 shunt controlled add heat 5 3 accessory settings 5 3 3 extra climate system 5 3 4 solar heating 5 3 7 external addition 5 3 11 modbus 5 3 12 exhaust supply air module 5 3 14 F135 5 3 16 humidity sensor 5 3 18 pool 5 3 19 active cooling 4 pipe 5 3 21 flow sensor energy meter 5 4 soft in outputs 5 5 factory setting service 5 6 forced control 5 7 start guide 5 8 quick...

Страница 45: ... temp lux 55 C Here you set the start and stop temperature of the hot water for the different comfort options in menu 2 2 MENU 5 1 2 MAX FLOW LINE TEMPERATURE climate system Setting range 5 80 C Default value 60 C Here you set the maximum supply temperature for the cli mate system If the installation has more than one climate system individual maximum supply temperatures can be set for each system...

Страница 46: ...on for cooling you can also set the heating medium pump speed during active respectively cooling operating modes the heating medium pump then runs in manual operation MENU 5 1 12 INTERNAL ELECTRICAL ADDITION max connected el add Setting range 0 9 Default values 9 kW fuse size Setting range 1 400 A Factory setting 16 A Here you set the max electrical output of the internal elec trical addition in V...

Страница 47: ...ressing OK You can now set at what temper atures the max and min frequencies respectively will occur This menu can consist of several windows one for each available demand use the navigation arrows in the top left corner to change between the windows MENU 5 1 25 TIME FILTER ALARM months btwn filter alarms Setting range 1 24 Factory setting 3 Here you set the number of months between alarms for a r...

Страница 48: ...nd use in heating mode while for 4 pipe cooling you can only se lect one option Caution This setting option only appears if the heat pump is activated for cooling operation in menu 5 2 4 mixing valve amplifier mixing valve step delay Here you set the shunt amplification and shunt waiting time for the various extra climate systems that are installed Contr pump GP10 Here you can set the speed of the...

Страница 49: ... word swap instead of the preset standard big endian See the accessory installation instructions for function de scription MENY5 3 12 EXHAUST SUPPLYAIRMODULE months btwn filter alarms Setting range 1 24 Default value 3 lowest extract air temp Setting range 0 10 C Default value 5 C bypass at excess temperature Setting range 2 10 C Default value 4 C bypass during heating Setting range on off Factory...

Страница 50: ...you select which pump to use in the system MENU5 3 21 FLOWSENSOR ENERGYMETER Supply temperature sensor set mode Setting range EMK150 EMK300 310 EMK500 Factory setting EMK150 energy per pulse Setting range 0 10000 Wh Factory setting 1000 Wh pulses per kWh Setting range 1 10000 Factory setting 500 Energy meter set mode Setting range energy per pulse pulses per kWh Default value energy per pulse ener...

Страница 51: ...t be a heating cooling or hot water de mand to start the compressor NOTE Do not quick start the compressor too many times over a short period of time as this could damage the compressor and its surrounding equipment MENU 5 9 FLOOR DRYING FUNCTION length of period 1 7 Setting range 0 30 days Factory setting period 1 3 5 7 2 days Factory setting period 4 3 days temp period 1 7 Setting range 15 70 C ...

Страница 52: ...es 100 Set the speed at which the charge pump is to operate in the present operating mode Select auto if the speed of the charge pump is to be regulated automatically factory set ting for optimal operation If auto is activated for heating operation you can also make the setting min allowed speed and max allowed speed which restricts the charge pump and prevents it from running at a lower or higher...

Страница 53: ...additional heat are active The electrical additional heat power in emer gency mode is set in the immersion heater board AA1 See page 25 for instructions EMPTYING THE HOT WATER COIL The hot water coil is most easily drained by detaching the cold water pipe at the coils s entry to the reservoir NOTE There may be some hot water risk of scalding DRAINING THE CLIMATE SYSTEM In order to carry out servic...

Страница 54: ...rect file can be selected through choose another file start updating Select start updating if you want to start the update You are asked whether you really want to update the software Respond yes to continue or no to undo If you responded yes to the previous question the update starts and you can now follow the progress of the update on the display When the update is complete VVM 500 re starts TIP...

Страница 55: ...ng activated A log file is now created where the temperature and the immersion heater output can be read off Logging contin ues until logging floor drying activated is deselected or until floor drying function is stopped Caution Deselect logging floor drying activated before you remove the USB memory Menu 7 3 manage settings manage settings 7 3 save settings recover settings Here you can manage sa...

Страница 56: ...used the alarm reset alarm In many cases it is sufficient to select reset alarm for the product to revert to normal operation If a green light comes on after selecting reset alarm the alarm has been remedied If the red light is still on and a menu called alarm is visible in the display the problem causing the alarm still remains aid mode aid mode is a type of emergency mode This means that the ind...

Страница 57: ...lected select a higher value on stop heating in menu 4 9 2 If mode manual is selected select heating If this is not enough select addition Too low set value on the automatic heating control Enter menu 1 1 temperature and adjust the offset heating curve up If the room temperature is only low in cold weather the curve slope in menu 1 9 1 heating curve needs adjusting up Too low or no operating prior...

Страница 58: ... running the heat pump in add heat only This means that additional heating only is used to heat the house SET THE INSTALLATION TO ADDITIONAL HEAT MODE 1 Go to menu 4 2 op mode 2 Mark add heat only using the control knob and then press the OK button 3 Return to the main menus by pressing the Back button NIBE VVM 500 Chapter 10 Disturbances in comfort 58 ...

Страница 59: ... Part no 066 075 The accessory requires that NIBE air water heat pump is installed HRV UNIT ERS This accessory is used to supply the accommodation with energy that has been recovered from the ventilation air The unit ventilates the house and heats the supply air as neces sary ERS 20 2501 Part no 066 068 ERS S10 4001 Part no 066 163 ERS 30 4001 Part no 066 165 1 A preheater may be required AUXILIAR...

Страница 60: ...n e g wood oil gas pellet boiler is to be connected to VVM 500 An accessory card is also required if for example an external circu lation pump is connected to VVM 500 at the same time that the buzzer alarm is activated Part no 067 060 BUFFER VESSEL UKV A buffer vessel is an accumulator tank that is suitable for connec tion to a heat pump or another external heat source and can have several differe...

Страница 61: ... 691 725 791 900 734 756 66 85 382 760 296 154 73 61 57 660 381 290 648 25 50 19 28 43 1788 691 725 791 900 734 756 66 85 382 760 296 154 73 61 57 660 381 290 648 25 50 61 Chapter 12 Technical data NIBE VVM 500 Technical data ...

Страница 62: ...n int G25 Heat pump connections Miscellaneous Indoor module 22 8 l Volume hot water coil 500 l Volume total indoor module 80 l Volume buffer vessel 2 l Volume solar coil 1 0 MPa Cut off pressure hot water coil 10 bar 0 3 3 bar MPa Max permitted pressure in indoor module Capacity hot water heating According to EN 16147 390 litre Amount of hot water 40 C Dimensions and weight 760 mm Width 900 mm Dep...

Страница 63: ... X 400 V Part Specification Sheet 450195 8 Page 2 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 11 14 400V 3N 50Hz 9kW WIRING DIAGRAM VVM500 ELSCHEMA VVM 500 450195 8 63 Chapter 12 Technical data NIBE VVM 500 ...

Страница 64: ...fication Sheet 450195 8 Page 3 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 11 14 400V 3N 50Hz 9kW WIRING DIAGRAM VVM500 ELSCHEMA VVM 500 450195 8 NIBE VVM 500 Chapter 12 Technical data 64 ...

Страница 65: ...fication Sheet 450195 8 Page 4 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 11 14 400V 3N 50Hz 9kW WIRING DIAGRAM VVM500 ELSCHEMA VVM 500 450195 8 65 Chapter 12 Technical data NIBE VVM 500 ...

Страница 66: ...fication Sheet 450195 8 Page 5 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 11 14 400V 3N 50Hz 9kW WIRING DIAGRAM VVM500 ELSCHEMA VVM 500 450195 8 NIBE VVM 500 Chapter 12 Technical data 66 ...

Страница 67: ...fication Sheet 450195 8 Page 6 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 11 14 400V 3N 50Hz 9kW WIRING DIAGRAM VVM500 ELSCHEMA VVM 500 450195 8 67 Chapter 12 Technical data NIBE VVM 500 ...

Страница 68: ...ternatives Two or more climate systems 17 Draining the climate system 53 Draining the hot water heater 53 E Electrical addition maximum output 25 Power steps of the immersion heater 25 Electrical circuit diagram 63 Electrical connections 18 23 Accessibility electrical connection 19 Cable lock 20 Communication 23 Connecting accessories 30 Connecting external operating voltage for the control system...

Страница 69: ...AUX inputs 27 Possible selection for AUX output potential free variable relay 28 Post adjustment venting 33 Power connection 21 Preparations 31 Pump speed 33 R Recovery 5 Removing panels 9 Removing the cover base board 19 Removing the cover immersion heater circuit board 19 Removing the hatch input circuit board 19 Room sensor 23 S Safety information 4 Marking 4 Serial number 4 Symbols 4 Scroll th...

Страница 70: ......

Страница 71: ...ie 3 01510 Vantaa Tel 358 0 9 274 6970 info nibe fi nibe fi NORWAY NETHERLANDS GREAT BRITAIN ABK Qviller AS Brobekkveien 80 0582 Oslo Tel 47 23 17 05 20 post abkqviller no nibe no NIBE Energietechniek B V Energieweg 31 4906 CG Oosterhout Tel 31 0 168 47 77 22 info nibenl nl nibenl nl NIBE Energy Systems Ltd 3C Broom Business Park Bridge Way S41 9QG Chesterfield Tel 44 0 330 311 2201 info nibe co u...

Страница 72: ...tems All product illustrations facts and data are based on the available information at the time of the publication s approval NIBE Energy Systems makes reservations for any factual or printing errors in this publication 2022 NIBE ENERGY SYSTEMS 731222 WS name Gemensamt WS version a995 WS release date 2022 06 28 10 07 Publish date 2022 09 01 07 24 ...