Docking
VVM 240
18
The safety equipment must be installed in accordance
with current regulations for all docking options. See
www.nibe.se/vvs for more docking options.
General
VVM 240 docked to FIGHTER 2010
95
FIGHTER 2010
VVM 240
AV
AV
SÄK
SF
RC
TV
FG
RG
UG
VVM 240 controls FIGHTER 2010, which works with
floating condensing against the heating system.
FIGHTER 2010 works in stage 1 or stage 2 depending
on outdoor air temperature.
If FIGHTER 2010 cannot meet the heating require-
ment, additional heating is shunted in from VVM 240.
When the outside temperature drops below the set
stop temperature VVM 240 engages and takes over
the heating.
The controller in FIGHTER 2010 must be version 2.30
or later for docking to VVM 240. The version can be
seen on the FIGHTER 2010 display during start up.
F - 2 0 1 0
v 2 .
3
0